| 123456789101112131415161718192021222324252627282930313233343536373839404142434445464748495051525354555657585960616263646566676869707172737475767778798081828384858687888990919293949596979899100101102103104105106107108109110111112113114115116117118119120121122123124125126127128129130131132133134135136137138139140141142143144145146147148149150151152153154155156157158159160161162163164165166167168169170171172173174175176177178179180181182183184185186187188189190191192193194195196197198199200201202203204205206207208209210211212213214215216217218219220221222223224225226227228229230231232233234235236237238239240241242243244245246247248249250251252253254255256257258259260261262263264265266267268269270271272273274275276277278279280281282283284285286287288289290291292293294295296297298299300301302303304305306307308309310311312313314315316317318319320321322323324325326327328329330331332333334335336337338339340341342343344345346347348349350351352353354355356357358359360361362363364365366367368369370371372373374375376377378379380381382383384385386387388389390391392393394395396397398399400401402403404405406407408409410411412413414415416417418419420421422423424425426427428429430431432433434435436437438439440441442443444445446447448449450451452453454455456457458459460461462463464465466467468469470471472473474475476477478479480481482483484485486487488489490491492493494495496497498499500501502503504505506507508509510511512513514515516517518519520521522523524525526527528529530531532533534535536537 |
- {
- "meta": {
- "source": "Moog Pitch RTS Help Z111(4MW)/Z108(1.5MW), PitchRTS工具随包",
- "arch": "TCU(主控)-PCU(Moog变桨控制器)-MPSD(伺服驱动)×3轴",
- "coding": "ID=错误类, LOC=轴位/部位; 完整排障步骤见原PDF",
- "sensitivity": "internal",
- "cross_model": "Z108(1.5MW)与Z111(4MW)各103码逐条同题 ⇒ Moog PCS 错误码跨机型通用, 对其他 Moog 变桨远景机型大概率适用",
- "applicability_warning": "⚠ **'跨机型通用'仅指 Moog 变桨系统内部通用 (Z108-1.5MW ≡ Z111-4MW 各103码逐条同题), 不等于对所有远景场适用**。变桨厂家不同则整份码表无效 — 已知反例: 神木场变桨=天仁 TR-1.5G ⇒ 本表在该场 100% 不适用; 九宫口 EN15=**Envision 自研变桨**(配置特征块逐字 `变桨=Envision`, 2026-09-02 九宫口更正; 先前'天仁'系据包内资料目录与平台通用SOE码误判)亦不适用。**用前必先核该场变桨供应商**。",
- "provenance": {
- "kind": "OEM 调试包解析产物 (生成器/模板层), **非整机回读**",
- "evidence_grade": "**模板值** — 按三级标签(实机回读/模板值·生效/模板值·空置), 本包**无一条够得上'实机回读'**",
- "not": "不是任何一台机的实际设定; '一致/闭环/自洽'指模板与模板 或 模板与实测数据 之间的一致, **不代表某台机的实际值**",
- "usage": "证据强度=模板值 × 用途: 作**分组依据/设计意图**合格; 作**阈值锚不合格**",
- "see": "README '证据规矩' 节 + param_dict.json meta.SELF_CORRECTION_2026_09_02",
- "stamped": "2026-09-02 结构污染审计补标",
- "extra": "Moog 变桨专用; 变桨厂家不同则整表无效(天仁/其他场100%不适用)"
- },
- "vendor_identification_rule": "**判变桨/硬件供应商: 配置特征块 > 包内资料目录 > SOE码族**。SOE字典平台通用(含全部供应商变体), '码里有X'≠'本场用X' — 与'SC-1独有码全是false friend'同类: 字典的存在性≠本场的实例性。神木'天仁TR-1.5G'来自契约(无包无配置块), 维持但标'待配置块核'"
- },
- "codes": {
- "ID-1_LOC-1": {
- "title": "Communication Error MPSD axis 1",
- "description": "This fault occurs if the CAN communication between the Moog Pitch Servo Drive in axis 1 and the PCU is disturbed.",
- "troubleshooting_n": 13
- },
- "ID-1_LOC-2": {
- "title": "Communication Error MPSD axis 2",
- "description": "This fault occurs if the CAN communication between the Moog Pitch Servo Drive in axis 2 and the PCU is disturbed.",
- "troubleshooting_n": 11
- },
- "ID-1_LOC-3": {
- "title": "Communication Error MPSD axis 3",
- "description": "This fault occurs if the CAN communication between the Moog Pitch Servo Drive in axis 3 and the PCU is disturbed.",
- "troubleshooting_n": 13
- },
- "ID-2_LOC-0": {
- "title": "Communication Error TCU",
- "description": "This fault occurs if the Profibus communication between the Moog PCU in the center box and the TCU is disturbed.",
- "troubleshooting_n": 6
- },
- "ID-3_LOC-0": {
- "title": "Safety line TCU open",
- "description": "This fault occurs if the safety line from the TCU to the PCS is open. Slip ring signal is wired from TCU to center box and from center box to each axis box In the axis box it is connected to the digital input DI02 of the Moog Pitch Servo Drive.",
- "troubleshooting_n": 10
- },
- "ID-4_LOC-0": {
- "title": "PCU opens safety line first",
- "description": "This fault occurs if the safety line from the PCS to the TCU is opened before the TCU opens the safety line. This information is helpful to find out who opens the safety line first – PCS or TCU",
- "troubleshooting_n": 18
- },
- "ID-5_LOC-0": {
- "title": "TCU opens safety line first",
- "description": "This fault occurs if the safety line from the TCU to the PCS is opened before the pitchsystem opens the safety line. This information is helpful to find out who opens the safety line first – PCS or TCU",
- "troubleshooting_n": 4
- },
- "ID-6_LOC-0": {
- "title": "Emergency mode command from TCU via fieldbus",
- "description": "This fault occurs if the TCU sends the emergency command bit on the controlword via primary field bus",
- "troubleshooting_n": 3
- },
- "ID-7_LOC-1": {
- "title": "Safety run started autonomous by the Pitch Servo Drive A1",
- "description": "This fault occurs if the MPSD in axis 1 starts a safety run autonomously.",
- "troubleshooting_n": 4
- },
- "ID-7_LOC-2": {
- "title": "Safety run started autonomous by the Pitch Servo Drive A2",
- "description": "This fault occurs if the MPSD in axis 2 starts a safetyrun autonomously.",
- "troubleshooting_n": 4
- },
- "ID-7_LOC-3": {
- "title": "Safety run started autonomous by the Pitch Servo Drive A3",
- "description": "This fault occurs if the MPSD in axis 3 starts a safetyrun autonomously.",
- "troubleshooting_n": 15
- },
- "ID-8_LOC-0": {
- "title": "Safety run timeout",
- "description": "This fault occurs if the emergency state is active and not all blades reaches a limit switch within a configurable time.",
- "troubleshooting_n": 6
- },
- "ID-9_LOC-1": {
- "title": "Grid supply error axis 1",
- "description": "This fault occurs if the MPSD in axis 1 detects a grid supply error at the input bridge and additionally the voltage amplitude is lower than a configurable limit. (Limit see Pitch RTS parameter ID 913) This fault is deactived during the backup condition monitoring test",
- "troubleshooting_n": 8
- },
- "ID-9_LOC-2": {
- "title": "Grid supply error axis 2",
- "description": "This fault occurs if the MPSD in axis 2 detects a grid supply error at the input bridge and additionally the voltage amplitude is lower than a configurable limit. (Limit see Pitch RTS parameter ID 913) This fault is deactived during the backup condition monitoring test",
- "troubleshooting_n": 9
- },
- "ID-9_LOC-3": {
- "title": "Grid supply error axis 3",
- "description": "This fault occurs if the MPSD in axis 3 detects a grid supply error at the input bridge and additionally the voltage amplitude is lower than a configurable limit. (Limit see Pitch RTS parameter ID 913). This fault is deactived during the backup condition monitoring test",
- "troubleshooting_n": 8
- },
- "ID-10_LOC-4": {
- "title": "24V supply axis 1",
- "description": "This fault occurs if the MPSD in axis 1 detects a fault in the 24V supply output from the MPSD Reloader unit.",
- "troubleshooting_n": 2
- },
- "ID-10_LOC-5": {
- "title": "24V supply axis 2",
- "description": "This fault occurs if the MPSD in axis 2 detects a fault in the 24V supply output from the MPSD Reloader unit.",
- "troubleshooting_n": 2
- },
- "ID-10_LOC-6": {
- "title": "24V supply axis 3",
- "description": "This fault occurs if the MPSD in axis 3 detects a fault in the 24V supply output from the MPSD Reloader unit.",
- "troubleshooting_n": 3
- },
- "ID-10_LOC-7": {
- "title": "24V supply overcurrent axis 1",
- "description": "This fault occurs if the MPSD in axis 1 detects an overcurrent fault in the 24V supply output from the MPSD Reloader unit.",
- "troubleshooting_n": 4
- },
- "ID-10_LOC-8": {
- "title": "24V supply overcurrent axis 2",
- "description": "This fault occurs if the MPSD in axis 2 detects an overcurrent fault in the 24V supply output from the MPSD Reloader unit.",
- "troubleshooting_n": 13
- },
- "ID-10_LOC-9": {
- "title": "24V supply overcurrent axis 3",
- "description": "This fault occurs if the MPSD in axis 3 detects an overcurrent fault in the 24V supply output from the MPSD Reloader unit.",
- "troubleshooting_n": 6
- },
- "ID-11_LOC-0": {
- "title": "LVRT error",
- "description": "This fault occurs if the PCS is in a low voltage ride through and exceeds the LVRT timeout. The timeout is configurable via Pitch RTS. (LVRT timeout see Pitch RTS parameter ID 917)",
- "troubleshooting_n": 5
- },
- "ID-12_LOC-1": {
- "title": "DC link fuse error axis 1",
- "description": "This fault occurs if the DC link fuse in axis 1 has tripped",
- "troubleshooting_n": 4
- },
- "ID-12_LOC-2": {
- "title": "DC link fuse error axis 2",
- "description": "This fault occurs if the DC link fuse in axis 2 has tripped",
- "troubleshooting_n": 4
- },
- "ID-12_LOC-3": {
- "title": "DC link fuse error axis 3",
- "description": "This fault occurs if the DC link fuse in axis 3 has tripped",
- "troubleshooting_n": 5
- },
- "ID-13_LOC-1": {
- "title": "Diode monitoring fuse axis 1",
- "description": "This fault occurs if the Diode monitoring circuit breaker in axis 1 has tripped",
- "troubleshooting_n": 4
- },
- "ID-13_LOC-2": {
- "title": "Diode monitoring fuse axis 2",
- "description": "This fault occurs if the Diode monitoring circuit breaker in axis 2 has tripped",
- "troubleshooting_n": 4
- },
- "ID-13_LOC-3": {
- "title": "Diode monitoring fuse axis 3",
- "description": "This fault occurs if the Diode monitoring circuit breaker in axis 3 has tripped",
- "troubleshooting_n": 5
- },
- "ID-15_LOC-1": {
- "title": "Undervoltage backup axis 1",
- "description": "This fault occurs if the voltage measured by the MPSD in axis 1 is lower than a configurable parameter. (see Pitch RTS parameter ID 915)",
- "troubleshooting_n": 6
- },
- "ID-15_LOC-2": {
- "title": "Undervoltage backup axis 2",
- "description": "This fault occurs if the voltage measured by the MPSD in axis 2 is lower than a configurable parameter. (see Pitch RTS parameter ID 915)",
- "troubleshooting_n": 7
- },
- "ID-15_LOC-3": {
- "title": "Undervoltage backup axis 3",
- "description": "This fault occurs if the voltage measured by the MPSD in axis 3 is lower than a configurable parameter. (see Pitch RTS parameter ID 915)",
- "troubleshooting_n": 9
- },
- "ID-16_LOC-1": {
- "title": "Overvoltage backup axis 1",
- "description": "This fault occurs if the voltage measured by the MPSD in axis 1 is higher than a configurable parameter. (see Pitch RTS parameter ID 916)",
- "troubleshooting_n": 6
- },
- "ID-16_LOC-2": {
- "title": "Overvoltage backup axis 2",
- "description": "This fault occurs if the voltage measured by the MPSD in axis 2 is higher than a configurable parameter. (see Pitch RTS parameter ID 916)",
- "troubleshooting_n": 16
- },
- "ID-16_LOC-3": {
- "title": "Overvoltage backup axis 3",
- "description": "This fault occurs if the voltage measured by the MPSD in axis 3 is higher than a configurable parameter. (see Pitch RTS parameter ID 916)",
- "troubleshooting_n": 6
- },
- "ID-17_LOC-1": {
- "title": "Error charger axis 1",
- "description": "This fault occurs if a charger error in the MPSD reloader unit in axis 1 occurs",
- "troubleshooting_n": 5
- },
- "ID-17_LOC-2": {
- "title": "Error charger axis 2",
- "description": "This fault occurs if a charger error in the MPSD reloader unit in axis 2 occurs",
- "troubleshooting_n": 5
- },
- "ID-17_LOC-3": {
- "title": "Error charger axis 3",
- "description": "This fault occurs if a charger error in the MPSD reloader unit in axis 3 occurs",
- "troubleshooting_n": 12
- },
- "ID-18_LOC-1": {
- "title": "Error heating axis 1",
- "description": "Not used",
- "troubleshooting_n": 4
- },
- "ID-18_LOC-2": {
- "title": "Error heating axis 1",
- "description": "Not used",
- "troubleshooting_n": 3
- },
- "ID-18_LOC-3": {
- "title": "Error heating axis 1",
- "description": "Not used",
- "troubleshooting_n": 4
- },
- "ID-19_LOC-1": {
- "title": "Overtemperature axis box 1",
- "description": "This fault occurs if an overtemperature is detected in axis box 1. Limit is configurable via parameter. (See Pitch RTS parameter ID 920)",
- "troubleshooting_n": 6
- },
- "ID-19_LOC-2": {
- "title": "Overtemperature axis box 2",
- "description": "This fault occurs if an overtemperature is detected in axis box 2. Limit is configurable via parameter. (See Pitch RTS parameter ID 920)",
- "troubleshooting_n": 16
- },
- "ID-19_LOC-3": {
- "title": "Overtemperature axis box 3",
- "description": "This fault occurs if an overtemperature is detected in axis box 3. Limit is configurable via parameter. (See Pitch RTS parameter ID 920)",
- "troubleshooting_n": 8
- },
- "ID-20_LOC-1": {
- "title": "Overtemperature backup box 1",
- "description": "This fault occurs if an overtemperature is detected in backup box 1. (Limit see Pitch RTS parameter ID 921)",
- "troubleshooting_n": 8
- },
- "ID-20_LOC-2": {
- "title": "Overtemperature backup box 2",
- "description": "This fault occurs if an overtemperature is detected in backup box 2. (Limit see Pitch RTS parameter ID 921)",
- "troubleshooting_n": 7
- },
- "ID-20_LOC-3": {
- "title": "Overtemperature backup box 3",
- "description": "This fault occurs if an overtemperature is detected in backup box 3. (Limit see Pitch RTS parameter ID 921)",
- "troubleshooting_n": 17
- },
- "ID-21_LOC-1": {
- "title": "Overtemperature motor axis 1",
- "description": "This fault occurs if a motor overtemperature is detected in axis 1. Limit is configurable via parameter. (See Pitch RTS parameter ID 924)",
- "troubleshooting_n": 11
- },
- "ID-21_LOC-2": {
- "title": "Overtemperature motor axis 2",
- "description": "This fault occurs if a motor overtemperature is detected in axis 2. Limit is configurable via parameter. (See Pitch RTS parameter ID 924)",
- "troubleshooting_n": 12
- },
- "ID-21_LOC-3": {
- "title": "Overtemperature motor axis 3",
- "description": "This fault occurs if a motor overtemperature is detected in axis 3. Limit is configurable via parameter. (See Pitch RTS parameter ID 924)",
- "troubleshooting_n": 21
- },
- "ID-22_LOC-1": {
- "title": "Undertemperature axis box 1",
- "description": "This fault occurs if an undertemperature is detected in axis box 1. Limit is configurable via parameter. (See Pitch RTS parameter ID 926)",
- "troubleshooting_n": 7
- },
- "ID-22_LOC-2": {
- "title": "Undertemperature axis box 2",
- "description": "This fault occurs if an undertemperature is detected in axis box 2. Limit is configurable via parameter. (See Pitch RTS parameter ID 926)",
- "troubleshooting_n": 6
- },
- "ID-22_LOC-3": {
- "title": "Undertemperature axis box 3",
- "description": "This fault occurs if an undertemperature is detected in axis box 3. Limit is configurable via parameter. (See Pitch RTS parameter ID 926)",
- "troubleshooting_n": 8
- },
- "ID-23_LOC-1": {
- "title": "Undertemperature backup box 1",
- "description": "This fault occurs if an undertemperature is detected in the backup box 1. Limit is configurable via parameter. (See Pitch RTS parameter ID 927)",
- "troubleshooting_n": 16
- },
- "ID-23_LOC-2": {
- "title": "Undertemperature backup box 2",
- "description": "This fault occurs if an undertemperature is detected in the backup box 2. Limit is configurable via parameter. (See Pitch RTS parameter ID 927)",
- "troubleshooting_n": 5
- },
- "ID-23_LOC-3": {
- "title": "Undertemperature backup box 3",
- "description": "This fault occurs if an undertemperature is detected in the backup box 3. Limit is configurable via parameter. (See Pitch RTS parameter ID 927)",
- "troubleshooting_n": 6
- },
- "ID-24_LOC-1": {
- "title": "Undertemperature motor axis 1",
- "description": "This fault occurs if a motor undertemperature is detected in axis 1. Limit is configurable via parameter. (See Pitch RTS parameter ID 930)",
- "troubleshooting_n": 6
- },
- "ID-24_LOC-2": {
- "title": "Undertemperature motor axis 2",
- "description": "This fault occurs if a motor undertemperature is detected in axis 2. Limit is configurable via parameter. (See Pitch RTS parameter ID 930)",
- "troubleshooting_n": 5
- },
- "ID-24_LOC-3": {
- "title": "Undertemperature motor axis 3",
- "description": "This fault occurs if a motor undertemperature is detected in axis 3. Limit is configurable via parameter. (See Pitch RTS parameter ID 930)",
- "troubleshooting_n": 5
- },
- "ID-25_LOC-1": {
- "title": "Wirebreak temperature sensor axis box 1",
- "description": "This fault occurs if a wirebreak of the temperature sensor in axis box 1 is detected. Limit is configurable via parameter. (See Pitch RTS parameter ID 943)",
- "troubleshooting_n": 6
- },
- "ID-25_LOC-2": {
- "title": "Wirebreak temperature sensor axis box 2",
- "description": "This fault occurs if a wirebreak of the temperature sensor in axis box 2 is detected. Limit is configurable via parameter. (See Pitch RTS parameter ID 943)",
- "troubleshooting_n": 6
- },
- "ID-25_LOC-3": {
- "title": "Wirebreak temperature sensor axis box 3",
- "description": "This fault occurs if a wirebreak of the temperature sensor in axis box 3 is detected. Limit is configurable via parameter. (See Pitch RTS parameter ID 943)",
- "troubleshooting_n": 5
- },
- "ID-26_LOC-1": {
- "title": "Wirebreak temperature sensor backup box 1",
- "description": "This fault occurs if a wirebreak of the temperature sensor in the backup box 1 is detected. Limit is configurable via parameter. (See Pitch RTS parameter ID 944)",
- "troubleshooting_n": 5
- },
- "ID-26_LOC-2": {
- "title": "Wirebreak temperature sensor backup box 2",
- "description": "This fault occurs if a wirebreak of the temperature sensor in the backup box 2 is detected. Limit is configurable via parameter. (See Pitch RTS parameter ID 944)",
- "troubleshooting_n": 5
- },
- "ID-26_LOC-3": {
- "title": "Wirebreak temperature sensor backup box 3",
- "description": "This fault occurs if a wirebreak of the temperature sensor in the backup box 3 is detected. Limit is configurable via parameter. (See Pitch RTS parameter ID 944)",
- "troubleshooting_n": 6
- },
- "ID-27_LOC-1": {
- "title": "Wirebreak temperature sensor motor axis 1",
- "description": "This fault occurs if a wirebreak of the motor temperature sensor in axis 1 is detected. Limit is configurable via parameter. (See Pitch RTS parameter ID 946)",
- "troubleshooting_n": 4
- },
- "ID-27_LOC-2": {
- "title": "Wirebreak temperature sensor motor axis 2",
- "description": "This fault occurs if a wirebreak of the motor temperature sensor in axis 2 is detected. Limit is configurable via parameter. (See Pitch RTS parameter ID 946)",
- "troubleshooting_n": 14
- },
- "ID-27_LOC-3": {
- "title": "Wirebreak temperature sensor motor axis 3",
- "description": "This fault occurs if a wirebreak of the motor temperature sensor in axis 3 is detected. Limit is configurable via parameter. (See Pitch RTS parameter ID 946)",
- "troubleshooting_n": 4
- },
- "ID-28_LOC-0": {
- "title": "Wirebreak temperature sensor hub",
- "description": "This fault occurs if a wirebreak of the hub temperature sensor in the center box was detected. Limit is configurable via parameter. (See Pitch RTS parameter ID 945)",
- "troubleshooting_n": 5
- },
- "ID-29_LOC-1": {
- "title": "Position incoherence limit switch A axis 1",
- "description": "This fault occurs if blade encoder position of axis 1 is outside a valid position window during the activation of limit switch A. The expected position of limit switch A can be configured via Pitch RTS parameter ID 931. The valid window around this position is defined as ID 931 +/- ID 934.",
- "troubleshooting_n": 5
- },
- "ID-29_LOC-2": {
- "title": "Position incoherence limit switch A axis 2",
- "description": "This fault occurs if blade encoder position of axis 2 is outside a valid position window during the activation of limit switch A. The expected position of limit switch A can be configured via Pitch RTS parameter ID 931. The valid window around this position is defined as ID 931 +/- ID 934.",
- "troubleshooting_n": 6
- },
- "ID-29_LOC-3": {
- "title": "Position incoherence limit switch A axis 3",
- "description": "This fault occurs if blade encoder position of axis 3 is outside a valid position window during the activation of limit switch A. The expected position of limit switch A can be configured via Pitch RTS parameter ID 931. The valid window around this position is defined as ID 931 +/- ID 934.",
- "troubleshooting_n": 5
- },
- "ID-29_LOC-4": {
- "title": "Position incoherence limit switch B axis 1",
- "description": "This fault occurs if blade encoder position of axis 1 is outside a valid position window during the activation of limit switch B. The expected position of limit switch B can be configured via Pitch RTS parameter ID 932. The valid window around this position is defined as ID 932 +/- ID 935.",
- "troubleshooting_n": 5
- },
- "ID-29_LOC-5": {
- "title": "Position incoherence limit switch B axis 2",
- "description": "This fault occurs if blade encoder position of axis 2 is outside a valid position window during the activation of limit switch B. The expected position of limit switch B can be configured via Pitch RTS parameter ID 932. The valid window around this position is defined as ID 932 +/- ID 935.",
- "troubleshooting_n": 6
- },
- "ID-29_LOC-6": {
- "title": "Position incoherence limit switch B axis 3",
- "description": "This fault occurs if blade encoder position of axis 3 is outside a valid position window during the activation of limit switch B. The expected position of limit switch B can be configured via Pitch RTS parameter ID 932. The valid window around this position is defined as ID 932 +/- ID 935.",
- "troubleshooting_n": 7
- },
- "ID-30_LOC-1": {
- "title": "Limit switch B reached axis 1",
- "description": "This fault occurs when limit switch B in axis 1 is activated. Under normal conditions the blade should never touch limit switch B. Only in manual mode or if the Bypass function of limit switch A has been activated.",
- "troubleshooting_n": 4
- },
- "ID-30_LOC-2": {
- "title": "Limit switch B reached axis 2",
- "description": "This fault occurs when limit switch B in axis 2 is activated. Under normal conditions the blade should never touch limit switch B. Only in manual mode or if the Bypass function of limit switch A has been activated.",
- "troubleshooting_n": 4
- },
- "ID-30_LOC-3": {
- "title": "Limit switch B reached axis 3",
- "description": "This fault occurs when limit switch B in axis 3 is activated. Under normal conditions the blade should never touch limit switch B. Only in manual mode or if the Bypass function of limit switch A has been activated.",
- "troubleshooting_n": 7
- },
- "ID-31_LOC-1": {
- "title": "Encoder incoherence axis 1",
- "description": "This fault occurs if the motor and the blade encoder position difference of axis 1 is higher than a configurable limit. (See Pitch RTS parameter ID 937)",
- "troubleshooting_n": 9
- },
- "ID-31_LOC-2": {
- "title": "Encoder incoherence axis 2",
- "description": "This fault occurs if the motor and the blade encoder position difference of axis 2 is higher than a configurable limit. (See Pitch RTS parameter ID 937)",
- "troubleshooting_n": 8
- },
- "ID-31_LOC-3": {
- "title": "Encoder incoherence axis 3",
- "description": "This fault occurs if the motor and the blade encoder position difference of axis 3 is higher than a configurable limit. (See Pitch RTS parameter ID 937)",
- "troubleshooting_n": 8
- },
- "ID-32_LOC-1": {
- "title": "Error blade symmetry axis 1",
- "description": "This fault occurs if if the position difference of blade 1 compared to blade 2 and 3 is higher than Pitch RTS parameter ID 938.",
- "troubleshooting_n": 4
- },
- "ID-32_LOC-2": {
- "title": "Error blade symmetry axis 2",
- "description": "This fault occurs if if the position difference of blade 2 compared to blade 1 and 3 is higher than Pitch RTS parameter ID 938.",
- "troubleshooting_n": 3
- },
- "ID-32_LOC-3": {
- "title": "Error blade symmetry axis 3",
- "description": "This fault occurs if if the position difference of blade 3 compared to blade 1 and 2 is higher than Pitch RTS parameter ID 938.",
- "troubleshooting_n": 4
- },
- "ID-33_LOC-1": {
- "title": "Error fan Pitchmaster axis 1",
- "description": "This fault occurs if one of the MPSD fans in axis 1 has a failure",
- "troubleshooting_n": 5
- },
- "ID-33_LOC-2": {
- "title": "Error fan Pitchmaster axis 2",
- "description": "This fault occurs if one of the MPSD fans in axis 2 has a failure",
- "troubleshooting_n": 5
- },
- "ID-33_LOC-3": {
- "title": "Error fan Pitchmaster axis 3",
- "description": "This fault occurs if one of the MPSD fans in axis 3 has a failure This fault occurs if the grid supply contactor in the center box was switched to often. (Limitation, see Pitch RTS ID 939)",
- "troubleshooting_n": 24
- },
- "ID-36_LOC-1": {
- "title": "Contactor cycles DC supply axis 1",
- "description": "This fault occurs if if the contactor between backup and MPSD of axis 1 was switched to often. (Limitation, see Pitch RTS ID 940)",
- "troubleshooting_n": 5
- },
- "ID-36_LOC-2": {
- "title": "Contactor cycles DC supply axis 2",
- "description": "This fault occurs if if the contactor between backup and MPSD of axis 2 was switched to often. (Limitation, see Pitch RTS ID 940)",
- "troubleshooting_n": 5
- },
- "ID-36_LOC-3": {
- "title": "Contactor cycles DC supply axis 3",
- "description": "This fault occurs if if the contactor between backup and MPSD of axis 3 was switched to often. (Limitation, see Pitch RTS ID 940)",
- "troubleshooting_n": 5
- },
- "ID-42_LOC-1": {
- "title": "Overtemperature center box",
- "description": "This fault occurs if an overtemperature is detected in the center box. Limit is configurable via parameter. (See Pitch RTS parameter ID 923)",
- "troubleshooting_n": 3
- },
- "ID-43_LOC-1": {
- "title": "Undertemperature center box",
- "description": "This fault occurs if an Undertemperature is detected in the center box. Limit is configurable via parameter. (See Pitch RTS parameter ID 929)",
- "troubleshooting_n": 16
- },
- "ID-44_LOC-0": {
- "title": "Main supply contactor open",
- "description": "This fault occurs if the main supply contactor in the center box is open",
- "troubleshooting_n": 13
- },
- "ID-45_LOC-1": {
- "title": "Backup Switch open axis 1",
- "description": "This fault occurs if if the backup switch at axis box 1 is open.",
- "troubleshooting_n": 5
- },
- "ID-45_LOC-2": {
- "title": "Backup Switch open axis 2",
- "description": "This fault occurs if if the backup switch at axis box 2 is open.",
- "troubleshooting_n": 5
- },
- "ID-45_LOC-3": {
- "title": "Backup Switch open axis 3",
- "description": "This fault occurs if if the backup switch at axis box 3 is open.",
- "troubleshooting_n": 3
- },
- "ID-46_LOC-1": {
- "title": "Overtemperature hub",
- "description": "This fault occurs if an overtemperature is detected in the hub. Limit is configurable via parameter. (See Pitch RTS parameter ID 922)",
- "troubleshooting_n": 5
- },
- "ID-47_LOC-1": {
- "title": "Undertemperature hub",
- "description": "This fault occurs if an undertemperature is detected in the hub. Limit is configurable via parameter. (See Pitch RTS parameter ID 928)",
- "troubleshooting_n": 6
- },
- "ID-48_LOC-1": {
- "title": "Wirebreak temperature sensor center box",
- "description": "This fault occurs if a wirebreak of the center box temperature sensor is detected. Limit is configurable via parameter. (See Pitch RTS parameter ID 952)",
- "troubleshooting_n": 8
- },
- "ID-49_LOC-0": {
- "title": "HVRT detected",
- "description": "This fault occurs if the PCS detects a High Voltage Ride Through. The measured input voltage at the MPSD was higher than Pitch RTS parameter ID 914.",
- "troubleshooting_n": 6
- },
- "ID-50_LOC-0": {
- "title": "HVRT Level 2 detected",
- "description": "This fault occurs if the PCS detects a High Voltage Ride Through. The measured input voltage at the MPSD was higher than Pitch RTS parameter ID 953.",
- "troubleshooting_n": 4
- },
- "ID-51_LOC-0": {
- "title": "HVRT Level 2 too long detected",
- "description": "This fault occurs if HVRT Level 2 was already detected, the main contactor for the grid supply was temporary opened and reconnected and the HVRT Level 2 is still measured.",
- "troubleshooting_n": 6
- },
- "ID-52_LOC-0": {
- "title": "Communication error TCU Field Bus Primary",
- "description": "This fault can only occur if the fieldbus redundancy mode is activated and a timeout on the primary fieldbus appears.",
- "troubleshooting_n": 4
- },
- "ID-52_LOC-1": {
- "title": "Communication error TCU Field Bus Secondary",
- "description": "This fault can only occur if the fieldbus redundancy mode is activated and a timeout on the secondary fieldbus appears.",
- "troubleshooting_n": 21
- }
- }
- }
|