| 123456789101112131415161718192021222324252627282930313233343536373839404142434445464748495051525354555657585960616263646566676869707172737475767778798081828384858687888990919293949596979899100101102103104105106107108109110111112113114115116117118119120121122123124125126127128129130131132133134135136137138139140141142143144145146147148149150151152153154155156157158159160161162163164165166167168169170171172173174175176177178179180181182183184185186187188189190191192193194195196197198199200201202203204205206207208209210211212213214215216217218219220221222223224225226227228229230231232233234235236237238239240241242243244245246247248249250251252253254255256257258259260261262263264265266267268269270271272273274275276277278279280281282283284285286287288289290291292293294295296297298299300301302303304305306 |
- {
- "WTG01": {
- "功率模块温度": "良好",
- "水冷系统": "良好",
- "直流母线": "不可判",
- "保护动作": "优秀",
- "变压器油温": "报警",
- "评估结论和维护建议": "变压器满负荷油温73.6℃,机群中位57.0℃;峰值101℃,超85℃累计843时段为第二名的11倍。宜查变压器室通风与本体散热,并作红外实测比对。"
- },
- "WTG02": {
- "功率模块温度": "良好",
- "水冷系统": "报警",
- "直流母线": "不可判",
- "保护动作": "报警",
- "变压器油温": "优秀",
- "评估结论和维护建议": "自2026年6月29日起反复跳闸至窗末累计166次,末次距窗末1.5小时;冷却水位类报警近半年26次居首;另有3时段冷却水温低于厂家规定的5℃绝对下限。宜优先核实跳闸原因与冷却水位。"
- },
- "WTG03": {
- "功率模块温度": "良好",
- "水冷系统": "良好",
- "直流母线": "不可判",
- "保护动作": "良好",
- "变压器油温": "优秀",
- "评估结论和维护建议": "冷却水温度高实际发生17.0小时,末次距窗末96天,近半年仅1次;对地绝缘动作16次集中于414天前单日。宜随下次登机顺带核查散热能力(换热面、三通阀、风扇、流量)。"
- },
- "WTG04": {
- "功率模块温度": "优秀",
- "水冷系统": "报警",
- "直流母线": "不可判",
- "保护动作": "优秀",
- "变压器油温": "良好",
- "评估结论和维护建议": "冷却水温度高实际发生30.6小时居全场之首,共10条跨5个月份,其中近半年4条。宜排查散热能力下降的成因:换热面污堵、三通阀动作与限位、风扇投入、冷却液流量,据分辨结果再定处置。"
- },
- "WTG05": {
- "功率模块温度": "优秀",
- "水冷系统": "优秀",
- "直流母线": "不可判",
- "保护动作": "优秀",
- "变压器油温": "良好",
- "评估结论和维护建议": "变压器油温超85℃累计12时段,峰值86℃,属零星峰值。无需专项处理。"
- },
- "WTG06": {
- "功率模块温度": "优秀",
- "水冷系统": "优秀",
- "直流母线": "不可判",
- "保护动作": "优秀",
- "变压器油温": "优秀",
- "评估结论和维护建议": "无异常。"
- },
- "WTG07": {
- "功率模块温度": "良好",
- "水冷系统": "优秀",
- "直流母线": "不可判",
- "保护动作": "优秀",
- "变压器油温": "优秀",
- "评估结论和维护建议": "功率模块温差单项存疑。宜随下次登机同步核查。"
- },
- "WTG08": {
- "功率模块温度": "优秀",
- "水冷系统": "良好",
- "直流母线": "不可判",
- "保护动作": "优秀",
- "变压器油温": "优秀",
- "评估结论和维护建议": "2025年7月2日电抗器底部冷却器水管断裂并触发烟雾报警,当日处置完毕;冷却水温低于加热器启动定值20℃的154时段集中于2025年4月,最低14.9℃,此后未再发生。宜纳入水管专项排查。 停机期间加热环节本应投入(依据见第6章),故该证据成立:低温呈连续成段,最长一段连续10.0小时低于定值、全窗6段,期间控制器通道存活、共模占比为0,属加热回路异常候选,不作部件定名,宜实测加热器投入与三通阀执行器动作。"
- },
- "WTG09": {
- "功率模块温度": "优秀",
- "水冷系统": "报警",
- "直流母线": "不可判",
- "保护动作": "优秀",
- "变压器油温": "优秀",
- "评估结论和维护建议": "冷却水温低于加热器启动定值20℃的时段累计1485个居全场之首,其中停机(出力≤0)683个、有出力时段802个;有出力侧功率中位仅153千瓦(额定的3.8%),超过1000千瓦的仅5个。停机期间加热环节本应投入(依据见第6章),故该证据成立:本台停机态水温逐月中位在多数月份与全场同步(约40℃),唯2026年4月塌至16.8℃而同月全场为39.5℃,5月即恢复39.9℃;低温呈连续成段,最长一段连续66.7小时低于定值、全窗8段,期间控制器通道存活率100%、共模占比为0,属加热回路异常候选,不作部件定名。冷却水位传感器故障自5月18日至6月23日反复9次,窗内未见终止。宜先修复水位测点,修复前以视镜目视确认液量;并实测加热器投入与三通阀执行器动作。"
- },
- "WTG10": {
- "功率模块温度": "良好",
- "水冷系统": "良好",
- "直流母线": "不可判",
- "保护动作": "优秀",
- "变压器油温": "优秀",
- "评估结论和维护建议": "冷却水温波动幅度高于机群水平。宜核查三通阀执行器动作与限位。"
- },
- "WTG11": {
- "功率模块温度": "优秀",
- "水冷系统": "良好",
- "直流母线": "不可判",
- "保护动作": "优秀",
- "变压器油温": "良好",
- "评估结论和维护建议": "冷却水温度高末次距窗末227天;变压器油温超85℃累计10时段。无需专项处理。"
- },
- "WTG12": {
- "功率模块温度": "优秀",
- "水冷系统": "良好",
- "直流母线": "不可判",
- "保护动作": "报警",
- "变压器油温": "优秀",
- "评估结论和维护建议": "对地绝缘动作26次居首,集中于2026年4月16日至6月9日;工单两次查明机侧功率模块损坏,换件后仍复发。宜查模块本体及共因。"
- },
- "WTG13": {
- "功率模块温度": "优秀",
- "水冷系统": "良好",
- "直流母线": "不可判",
- "保护动作": "优秀",
- "变压器油温": "良好",
- "评估结论和维护建议": "变压器满负荷油温自2025年9月起的11个月中有10个月高于机群8℃以上,中位偏离10.3K。同期全场另有两台呈相同趋势,属场级现象,本台偏离居三台之末。绝对值未越限,峰值83℃,超85℃为零。宜随场级变压器散热核查一并跟踪。"
- },
- "WTG14": {
- "功率模块温度": "优秀",
- "水冷系统": "优秀",
- "直流母线": "不可判",
- "保护动作": "优秀",
- "变压器油温": "优秀",
- "评估结论和维护建议": "无异常。"
- },
- "WTG15": {
- "功率模块温度": "优秀",
- "水冷系统": "良好",
- "直流母线": "不可判",
- "保护动作": "优秀",
- "变压器油温": "优秀",
- "评估结论和维护建议": "冷却水位类报警实际发生33.5小时超判定线,近半年19次;冷却水温低于加热器启动定值20℃的521时段集中于2026年4月,当月全场共7台同类、同月中位356时段,该台为1.5倍。宜查视镜液位与液位计。 停机期间加热环节本应投入(依据见第6章),故该证据成立:低温呈连续成段,最长一段连续86.8小时低于定值、全窗1段,期间控制器通道存活、共模占比为0,属加热回路异常候选,不作部件定名,宜实测加热器投入与三通阀执行器动作。"
- },
- "WTG16": {
- "功率模块温度": "优秀",
- "水冷系统": "良好",
- "直流母线": "不可判",
- "保护动作": "优秀",
- "变压器油温": "优秀",
- "评估结论和维护建议": "冷却水位类报警累计69.8小时居首。宜查视镜液位与液位计。"
- },
- "WTG17": {
- "功率模块温度": "优秀",
- "水冷系统": "优秀",
- "直流母线": "不可判",
- "保护动作": "优秀",
- "变压器油温": "优秀",
- "评估结论和维护建议": "无异常。"
- },
- "WTG18": {
- "功率模块温度": "优秀",
- "水冷系统": "报警",
- "直流母线": "不可判",
- "保护动作": "优秀",
- "变压器油温": "优秀",
- "评估结论和维护建议": "冷却水温低于加热器启动定值20℃的592时段集中于2026年2月,为当月同类9台中位的85倍;最低4.3℃,其中66时段低于厂家硬件手册规定的5℃绝对下限,另有9时段低于当时露点。(同上);其中低于5℃硬件下限的66时段集中于2026年2月9日单日、连续约11小时,当时机组处于停机状态。宜结合冬季长时间停机期间的保温与防凝露措施一并评估,不单独派工核查加热回路。"
- },
- "WTG19": {
- "功率模块温度": "优秀",
- "水冷系统": "良好",
- "直流母线": "不可判",
- "保护动作": "优秀",
- "变压器油温": "优秀",
- "评估结论和维护建议": "冷却水位类报警近半年零发生,累计时长在线下。宜随下次登机顺带核查。"
- },
- "WTG20": {
- "功率模块温度": "不可判",
- "水冷系统": "良好",
- "直流母线": "不可判",
- "保护动作": "优秀",
- "变压器油温": "优秀",
- "评估结论和维护建议": "温度测点存在静态偏置,横向比较不可直接采信;冷却水温低于加热器启动定值20℃的491时段集中于2026年4月,为当月同类7台中位的1.4倍。宜先校表再复评。 停机期间加热环节本应投入(依据见第6章),故该证据成立:低温呈连续成段,最长一段连续81.8小时低于定值、全窗1段,期间控制器通道存活、共模占比为0,属加热回路异常候选,不作部件定名,宜实测加热器投入与三通阀执行器动作。"
- },
- "WTG21": {
- "功率模块温度": "优秀",
- "水冷系统": "良好",
- "直流母线": "不可判",
- "保护动作": "优秀",
- "变压器油温": "优秀",
- "评估结论和维护建议": "冷却水温度高末次距窗末332天,近半年未再发生。无需专项处理。"
- },
- "WTG22": {
- "功率模块温度": "不可判",
- "水冷系统": "优秀",
- "直流母线": "不可判",
- "保护动作": "优秀",
- "变压器油温": "优秀",
- "评估结论和维护建议": "塔底柜外温度测点读数偏高,停机时高于机群8.4℃。宜校准或更换温度计。"
- },
- "WTG23": {
- "功率模块温度": "优秀",
- "水冷系统": "优秀",
- "直流母线": "不可判",
- "保护动作": "优秀",
- "变压器油温": "优秀",
- "评估结论和维护建议": "无异常。"
- },
- "WTG24": {
- "功率模块温度": "优秀",
- "水冷系统": "良好",
- "直流母线": "不可判",
- "保护动作": "优秀",
- "变压器油温": "优秀",
- "评估结论和维护建议": "冷却水温度高与加热热过载继电器动作同时命中,为全场仅有两台之一。宜一次登机查清水位、加热器整定与水位传感器。"
- },
- "WTG25": {
- "功率模块温度": "优秀",
- "水冷系统": "良好",
- "直流母线": "不可判",
- "保护动作": "优秀",
- "变压器油温": "优秀",
- "评估结论和维护建议": "冷却水温低于加热器启动定值20℃的157时段集中于2026年1月,为当月同类13台中位7时段的22倍,最低6.5℃。(同上),本次不派工。"
- },
- "WTG26": {
- "功率模块温度": "优秀",
- "水冷系统": "报警",
- "直流母线": "不可判",
- "保护动作": "优秀",
- "变压器油温": "报警",
- "评估结论和维护建议": "冷却水温低于加热器启动定值20℃的975时段居全场第二,最低9.4℃,其中345时段集中于2026年2月、为当月同类中位的49倍。该975时段虽全部发生于停机工况,但停机期间加热环节本应投入(机群检验:全场38台长停机且环温低于15℃时水温中位均维持31.0至34.6℃,而环温中位仅8.7℃),故该证据成立:低温呈连续成段,最长一段连续55.0小时低于定值、全窗11段,期间控制器通道存活率100%、共模占比为0,属加热回路异常候选,不作部件定名。水冷系统列报警;因未触及5℃硬件下限,不再上调。变压器油温超85℃累计77时段居全场第二、峰值91℃,该项为独立依据,宜查变压器室通风。宜实测加热器投入与三通阀执行器动作。"
- },
- "WTG27": {
- "功率模块温度": "不可判",
- "水冷系统": "良好",
- "直流母线": "不可判",
- "保护动作": "优秀",
- "变压器油温": "优秀",
- "评估结论和维护建议": "冷却水温低于加热器启动定值20℃的240时段集中于2026年1月,为当月同类13台中位的34倍。停机期间加热环节本应投入(依据见第6章),故该证据成立。该台曾记为最低0.0℃及低于5℃硬件下限13时段,经核水温读数为精确0.0,属通道哨兵值而非实测低温,不计入。加热热过载继电器动作7次居全场之首,该项为独立依据,宜据此核查加热器整定与执行回路,并校表。"
- },
- "WTG28": {
- "功率模块温度": "优秀",
- "水冷系统": "良好",
- "直流母线": "不可判",
- "保护动作": "优秀",
- "变压器油温": "良好",
- "评估结论和维护建议": "冷却水位类报警累计61.9小时超线,近半年13次。宜查视镜液位与液位计。"
- },
- "WTG29": {
- "功率模块温度": "优秀",
- "水冷系统": "良好",
- "直流母线": "不可判",
- "保护动作": "优秀",
- "变压器油温": "优秀",
- "评估结论和维护建议": "2026年7月7日冷却水管漏水,当日更换并补液。宜纳入水管专项排查。"
- },
- "WTG30": {
- "功率模块温度": "优秀",
- "水冷系统": "良好",
- "直流母线": "不可判",
- "保护动作": "良好",
- "变压器油温": "优秀",
- "评估结论和维护建议": "对地绝缘动作18次集中于2026年6月20日至25日,成因已查明并于6月26日处置完毕,此后至数据窗末未再发生。宜按闭环跟踪,下次登机时测绝缘电阻留档。"
- },
- "WTG31": {
- "功率模块温度": "优秀",
- "水冷系统": "良好",
- "直流母线": "不可判",
- "保护动作": "优秀",
- "变压器油温": "优秀",
- "评估结论和维护建议": "2025年11月15日塔外冷却系统漏水,紧固后补液;同期塔底开关跳开导致主控失电。宜核查管路紧固与塔底供电回路。"
- },
- "WTG32": {
- "功率模块温度": "良好",
- "水冷系统": "优秀",
- "直流母线": "不可判",
- "保护动作": "优秀",
- "变压器油温": "报警",
- "评估结论和维护建议": "数据窗末已停机64.7小时,停机时刻与未闭合报警分钟级吻合;变压器峰值94℃,超85℃累计66时段居第三。宜先电话确认是否已复电。"
- },
- "WTG33": {
- "功率模块温度": "优秀",
- "水冷系统": "优秀",
- "直流母线": "不可判",
- "保护动作": "优秀",
- "变压器油温": "优秀",
- "评估结论和维护建议": "无异常。"
- },
- "WTG34": {
- "功率模块温度": "报警",
- "水冷系统": "报警",
- "直流母线": "不可判",
- "保护动作": "优秀",
- "变压器油温": "优秀",
- "评估结论和维护建议": "冷却水温度高实际发生28.6小时居全场第二;发电中冷却水温超55℃累计10时段居首。宜排查散热能力下降的成因(换热面、三通阀、风扇、流量)并复测模块温差,据分辨结果再定处置。"
- },
- "WTG35": {
- "功率模块温度": "优秀",
- "水冷系统": "优秀",
- "直流母线": "不可判",
- "保护动作": "优秀",
- "变压器油温": "优秀",
- "评估结论和维护建议": "塔底柜外温度测点读数偏低约7℃而同台其余通道正常。宜随下次登机顺带核对温度计。"
- },
- "WTG36": {
- "功率模块温度": "不可判",
- "水冷系统": "良好",
- "直流母线": "不可判",
- "保护动作": "优秀",
- "变压器油温": "优秀",
- "评估结论和维护建议": "2025年7月30日电抗器底部水管断裂,工单记为通讯故障,累计停机100小时;冷却水温低于加热器启动定值20℃的455时段集中于2025年12月,最低7.0℃。宜纳入水管专项排查并校表。 停机期间加热环节本应投入(依据见第6章),故该证据成立:低温呈连续成段,最长一段连续75.8小时低于定值、全窗3段,期间控制器通道存活、共模占比为0,属加热回路异常候选,不作部件定名,宜实测加热器投入与三通阀执行器动作。"
- },
- "WTG37": {
- "功率模块温度": "优秀",
- "水冷系统": "优秀",
- "直流母线": "不可判",
- "保护动作": "优秀",
- "变压器油温": "良好",
- "评估结论和维护建议": "变压器油温超85℃累计32时段,峰值91℃,属零星峰值。无需专项处理。"
- },
- "WTG38": {
- "功率模块温度": "优秀",
- "水冷系统": "良好",
- "直流母线": "不可判",
- "保护动作": "优秀",
- "变压器油温": "报警",
- "评估结论和维护建议": "变压器油温峰值99℃越过厂家95℃报警线,超85℃累计8时段;冷却水位类报警累计40.7小时超线。宜核查变压器散热与冷却水位。"
- }
- }
|