| 123456789101112131415161718192021222324252627282930313233343536373839404142434445464748495051525354555657585960616263646566676869707172737475767778798081828384858687888990919293949596979899100101102103104105106107108109110111112113114115116117118119120121122123124125126127128129130131132133134135136137138139140141142143144145146147148149150151152153154155156157158159160161162163164165166167168169170171172173174175176177178179180181182183184185186187188189190191192193194195196197198199200201202203204205206207208209210211212213214215216217218219220221222223224225226227228229230231232233234235236237238239240241242243244245246247248249250251252253254255256257258259260261262263264265266267268269270271272273274275276277278279280281282283284285286287288289290291292293294295296297298299300301302303304305306307308309310311312313314315316317318319320321322323324325326327328329330331332333334335336337338339340341342343344345346347348349350351352353354355356357358359360361362363364365366367368369370371372373374375376377378379380381382383384385386387388389390391392393394395396397398399400401402403404405406407408409410411412413414415416417418419420421422423424425426427428429430431432433434435436437438439440441442443444445446447448449450451452453454455456457458459460461462463464465466467468469470471472473474475476477478479480481482483484485486487488489490491492493494495496497498499500501502503504505506507508509510511512513514515516517518519520521522523524525526527528529530531532533534535536537538539540541542543544545546547548549550551552553554555556557558559560561562563564565566567568569570571572573574575576577578579580581582583584585586587588589590591592593594595596597598599600601602603604605606607608609610611612613614615616617618619620621622623624625626627628629630631632633634635636637638639640641642643644645646647648649650651652653654655656657658659660661662663664665666667668669670671672673674675676677678679680681682683684685686687688689690691692693694695696697698699700701702703704705706707708709710711712713714715716717718719720721722723724725726727728729730731732733734735736737738739740741742743744745746747748749750751752753754755756757758759760761762763764765766767768769770771772773774775776777778779780781782783784785786787788789790791792793794795796797798799800801802803804805806807808809810811812813814815816817818819820821822823824825826827828829830831832833834835836837838839840841842843844845846847848849850851852853854855856857858859860861862863864865866867868869870871872873874875876877878879880881882883884885886887888889890891892893894895896897898899900901902903904905906907908909910911912913914915916917918919920921922923924925926927928929930931932933934935936937938939940941942943944945946947948949950951952953954955956957958959960961962963964965966967968969970971972973974975976977978979980981982983984985986987988989990991992993994995996997998999100010011002100310041005100610071008100910101011101210131014101510161017101810191020102110221023102410251026102710281029103010311032103310341035103610371038103910401041104210431044104510461047104810491050105110521053105410551056105710581059106010611062106310641065106610671068106910701071107210731074107510761077107810791080108110821083108410851086108710881089109010911092109310941095109610971098109911001101110211031104110511061107110811091110111111121113111411151116111711181119112011211122112311241125112611271128112911301131113211331134113511361137113811391140114111421143114411451146114711481149115011511152115311541155115611571158115911601161116211631164116511661167116811691170117111721173117411751176117711781179118011811182118311841185118611871188118911901191119211931194119511961197119811991200120112021203120412051206120712081209121012111212121312141215121612171218121912201221122212231224122512261227122812291230123112321233123412351236123712381239124012411242124312441245124612471248124912501251125212531254125512561257125812591260126112621263126412651266126712681269127012711272127312741275127612771278127912801281128212831284128512861287128812891290129112921293129412951296129712981299130013011302130313041305130613071308130913101311131213131314131513161317131813191320132113221323132413251326132713281329133013311332133313341335133613371338133913401341134213431344134513461347134813491350135113521353135413551356135713581359136013611362136313641365136613671368136913701371137213731374137513761377137813791380138113821383138413851386138713881389139013911392139313941395139613971398139914001401140214031404140514061407140814091410141114121413141414151416141714181419142014211422142314241425142614271428142914301431143214331434143514361437143814391440144114421443144414451446144714481449145014511452145314541455145614571458145914601461146214631464146514661467146814691470147114721473147414751476147714781479148014811482148314841485148614871488148914901491149214931494149514961497149814991500150115021503150415051506150715081509151015111512151315141515151615171518151915201521152215231524152515261527152815291530153115321533153415351536153715381539154015411542154315441545154615471548154915501551155215531554155515561557155815591560156115621563156415651566156715681569157015711572157315741575157615771578157915801581158215831584158515861587158815891590159115921593159415951596159715981599160016011602160316041605160616071608160916101611161216131614161516161617161816191620162116221623162416251626162716281629163016311632163316341635163616371638163916401641164216431644164516461647164816491650165116521653165416551656165716581659166016611662166316641665166616671668166916701671167216731674167516761677167816791680168116821683168416851686168716881689169016911692169316941695169616971698169917001701170217031704170517061707170817091710171117121713171417151716171717181719172017211722172317241725172617271728172917301731173217331734173517361737173817391740174117421743174417451746174717481749175017511752175317541755175617571758175917601761176217631764176517661767176817691770177117721773177417751776177717781779178017811782178317841785178617871788178917901791179217931794179517961797179817991800180118021803180418051806180718081809181018111812181318141815181618171818181918201821182218231824182518261827182818291830183118321833183418351836183718381839184018411842184318441845184618471848184918501851185218531854185518561857185818591860186118621863186418651866186718681869187018711872187318741875187618771878187918801881188218831884188518861887188818891890189118921893189418951896189718981899190019011902190319041905190619071908190919101911191219131914191519161917191819191920192119221923192419251926192719281929193019311932193319341935193619371938193919401941194219431944194519461947194819491950195119521953195419551956195719581959196019611962196319641965196619671968196919701971197219731974197519761977197819791980198119821983198419851986198719881989199019911992199319941995199619971998199920002001200220032004200520062007200820092010201120122013201420152016201720182019202020212022202320242025202620272028202920302031203220332034203520362037203820392040204120422043204420452046204720482049205020512052205320542055205620572058205920602061206220632064206520662067206820692070207120722073207420752076207720782079208020812082208320842085208620872088208920902091209220932094209520962097209820992100210121022103210421052106210721082109211021112112211321142115211621172118211921202121212221232124212521262127212821292130213121322133213421352136213721382139214021412142214321442145214621472148214921502151215221532154215521562157215821592160216121622163216421652166216721682169217021712172217321742175217621772178217921802181218221832184218521862187218821892190219121922193219421952196219721982199220022012202220322042205220622072208220922102211221222132214221522162217221822192220222122222223222422252226222722282229223022312232223322342235223622372238223922402241224222432244224522462247224822492250225122522253225422552256225722582259226022612262226322642265226622672268226922702271227222732274227522762277227822792280228122822283228422852286228722882289229022912292229322942295229622972298229923002301230223032304230523062307230823092310231123122313231423152316231723182319232023212322232323242325232623272328232923302331233223332334233523362337233823392340234123422343234423452346234723482349235023512352235323542355235623572358235923602361236223632364236523662367236823692370237123722373237423752376237723782379238023812382238323842385238623872388238923902391239223932394239523962397239823992400240124022403240424052406240724082409241024112412241324142415241624172418241924202421242224232424242524262427242824292430243124322433243424352436243724382439244024412442244324442445244624472448244924502451245224532454245524562457245824592460246124622463246424652466246724682469247024712472247324742475247624772478247924802481248224832484248524862487248824892490249124922493249424952496249724982499250025012502250325042505250625072508250925102511251225132514251525162517251825192520252125222523252425252526252725282529253025312532253325342535253625372538253925402541254225432544254525462547254825492550255125522553255425552556255725582559256025612562256325642565256625672568256925702571257225732574257525762577257825792580258125822583258425852586258725882589259025912592259325942595259625972598259926002601260226032604260526062607260826092610261126122613261426152616261726182619262026212622262326242625262626272628262926302631263226332634263526362637263826392640264126422643264426452646264726482649265026512652265326542655265626572658265926602661266226632664266526662667266826692670267126722673267426752676267726782679268026812682268326842685268626872688268926902691269226932694269526962697269826992700270127022703270427052706270727082709271027112712271327142715271627172718271927202721272227232724272527262727272827292730273127322733273427352736273727382739274027412742274327442745274627472748274927502751275227532754275527562757275827592760276127622763276427652766276727682769277027712772277327742775277627772778277927802781278227832784278527862787278827892790279127922793279427952796279727982799280028012802280328042805280628072808280928102811281228132814281528162817281828192820282128222823282428252826282728282829283028312832283328342835283628372838283928402841284228432844284528462847284828492850285128522853285428552856285728582859286028612862286328642865286628672868286928702871287228732874287528762877287828792880288128822883288428852886288728882889289028912892289328942895289628972898289929002901290229032904290529062907290829092910291129122913291429152916291729182919292029212922292329242925292629272928292929302931293229332934293529362937293829392940294129422943294429452946294729482949295029512952295329542955295629572958295929602961296229632964296529662967296829692970297129722973297429752976297729782979298029812982298329842985298629872988298929902991299229932994299529962997299829993000300130023003300430053006300730083009301030113012301330143015301630173018301930203021302230233024302530263027302830293030303130323033303430353036303730383039304030413042304330443045304630473048304930503051305230533054305530563057305830593060306130623063306430653066306730683069307030713072307330743075307630773078307930803081308230833084308530863087308830893090309130923093309430953096309730983099310031013102310331043105310631073108310931103111311231133114311531163117311831193120312131223123312431253126312731283129313031313132313331343135313631373138313931403141314231433144314531463147314831493150315131523153315431553156315731583159316031613162316331643165316631673168316931703171317231733174317531763177317831793180318131823183318431853186318731883189319031913192319331943195319631973198319932003201320232033204320532063207320832093210321132123213321432153216321732183219322032213222322332243225322632273228322932303231323232333234323532363237323832393240324132423243324432453246324732483249325032513252325332543255325632573258325932603261326232633264326532663267326832693270327132723273327432753276327732783279328032813282328332843285328632873288328932903291329232933294329532963297329832993300330133023303330433053306330733083309331033113312331333143315331633173318331933203321332233233324332533263327332833293330333133323333333433353336333733383339334033413342334333443345334633473348334933503351335233533354335533563357335833593360336133623363336433653366336733683369337033713372337333743375337633773378337933803381338233833384338533863387338833893390339133923393339433953396339733983399340034013402340334043405340634073408340934103411341234133414341534163417341834193420342134223423342434253426342734283429343034313432343334343435343634373438343934403441344234433444344534463447344834493450345134523453345434553456345734583459346034613462346334643465346634673468346934703471347234733474347534763477347834793480348134823483348434853486348734883489349034913492349334943495349634973498349935003501350235033504350535063507350835093510351135123513351435153516351735183519352035213522352335243525352635273528352935303531353235333534353535363537353835393540354135423543354435453546354735483549355035513552355335543555355635573558355935603561356235633564356535663567356835693570357135723573357435753576357735783579358035813582358335843585358635873588358935903591359235933594359535963597359835993600360136023603360436053606360736083609361036113612361336143615361636173618361936203621362236233624362536263627362836293630363136323633363436353636363736383639364036413642364336443645364636473648364936503651365236533654365536563657365836593660366136623663366436653666366736683669367036713672367336743675367636773678367936803681368236833684368536863687368836893690369136923693369436953696369736983699370037013702370337043705370637073708370937103711371237133714371537163717371837193720372137223723372437253726372737283729373037313732373337343735373637373738373937403741374237433744374537463747374837493750375137523753375437553756375737583759376037613762376337643765376637673768376937703771377237733774377537763777377837793780378137823783378437853786378737883789379037913792379337943795379637973798379938003801380238033804380538063807380838093810381138123813381438153816381738183819382038213822382338243825382638273828382938303831383238333834383538363837383838393840384138423843384438453846384738483849385038513852385338543855385638573858385938603861386238633864386538663867386838693870387138723873387438753876387738783879388038813882388338843885388638873888388938903891389238933894389538963897389838993900390139023903390439053906390739083909391039113912391339143915391639173918391939203921392239233924392539263927392839293930393139323933393439353936393739383939394039413942394339443945394639473948394939503951395239533954395539563957395839593960396139623963396439653966396739683969397039713972397339743975397639773978397939803981398239833984398539863987398839893990399139923993399439953996399739983999400040014002400340044005400640074008400940104011401240134014401540164017401840194020402140224023402440254026402740284029403040314032403340344035403640374038403940404041404240434044404540464047404840494050405140524053405440554056405740584059406040614062406340644065406640674068406940704071407240734074407540764077407840794080408140824083408440854086408740884089409040914092409340944095409640974098409941004101410241034104410541064107410841094110411141124113411441154116411741184119412041214122412341244125412641274128412941304131413241334134413541364137413841394140414141424143414441454146414741484149415041514152415341544155415641574158415941604161416241634164416541664167416841694170417141724173417441754176417741784179418041814182418341844185418641874188418941904191419241934194419541964197419841994200420142024203420442054206420742084209421042114212421342144215421642174218421942204221422242234224422542264227422842294230423142324233423442354236423742384239424042414242424342444245424642474248424942504251425242534254425542564257425842594260426142624263426442654266426742684269427042714272427342744275427642774278427942804281428242834284428542864287428842894290429142924293429442954296429742984299430043014302430343044305430643074308430943104311431243134314431543164317431843194320432143224323432443254326432743284329433043314332433343344335433643374338433943404341434243434344434543464347434843494350435143524353435443554356435743584359436043614362436343644365436643674368436943704371437243734374437543764377437843794380438143824383438443854386438743884389439043914392439343944395439643974398439944004401440244034404440544064407440844094410441144124413441444154416441744184419442044214422442344244425442644274428442944304431443244334434443544364437443844394440444144424443444444454446444744484449445044514452445344544455445644574458445944604461446244634464446544664467446844694470447144724473447444754476447744784479448044814482448344844485448644874488448944904491449244934494449544964497449844994500450145024503450445054506450745084509451045114512451345144515451645174518451945204521452245234524452545264527452845294530453145324533453445354536453745384539454045414542454345444545454645474548454945504551455245534554455545564557455845594560456145624563456445654566456745684569457045714572457345744575457645774578457945804581458245834584458545864587458845894590459145924593459445954596459745984599460046014602460346044605460646074608460946104611461246134614461546164617461846194620462146224623462446254626462746284629463046314632463346344635463646374638463946404641464246434644464546464647464846494650465146524653465446554656465746584659466046614662466346644665466646674668466946704671467246734674467546764677467846794680468146824683468446854686468746884689469046914692469346944695469646974698469947004701470247034704470547064707470847094710471147124713471447154716471747184719472047214722472347244725472647274728472947304731473247334734473547364737473847394740474147424743474447454746474747484749475047514752475347544755475647574758475947604761476247634764476547664767476847694770477147724773477447754776477747784779478047814782478347844785478647874788478947904791479247934794479547964797479847994800480148024803480448054806480748084809481048114812481348144815481648174818481948204821482248234824482548264827482848294830483148324833483448354836483748384839484048414842484348444845484648474848484948504851485248534854485548564857485848594860486148624863486448654866486748684869487048714872487348744875487648774878487948804881488248834884488548864887488848894890489148924893489448954896489748984899490049014902490349044905490649074908490949104911491249134914491549164917491849194920492149224923492449254926492749284929493049314932493349344935493649374938493949404941494249434944494549464947494849494950495149524953495449554956495749584959496049614962496349644965496649674968496949704971497249734974497549764977497849794980498149824983498449854986498749884989499049914992499349944995499649974998499950005001500250035004500550065007500850095010501150125013501450155016501750185019502050215022502350245025502650275028502950305031503250335034503550365037503850395040504150425043504450455046504750485049505050515052505350545055505650575058505950605061506250635064506550665067506850695070507150725073507450755076507750785079508050815082508350845085508650875088508950905091509250935094509550965097509850995100510151025103510451055106510751085109511051115112511351145115511651175118511951205121512251235124512551265127512851295130513151325133513451355136513751385139514051415142514351445145514651475148514951505151515251535154515551565157515851595160516151625163516451655166516751685169517051715172517351745175517651775178517951805181518251835184518551865187518851895190519151925193519451955196519751985199520052015202520352045205520652075208520952105211521252135214521552165217521852195220522152225223522452255226522752285229523052315232523352345235523652375238523952405241524252435244524552465247524852495250525152525253525452555256525752585259526052615262526352645265526652675268526952705271527252735274527552765277527852795280528152825283528452855286528752885289529052915292529352945295529652975298529953005301530253035304530553065307530853095310531153125313531453155316531753185319532053215322532353245325532653275328532953305331533253335334533553365337533853395340534153425343534453455346534753485349535053515352535353545355535653575358535953605361536253635364536553665367536853695370537153725373537453755376537753785379538053815382538353845385538653875388538953905391539253935394539553965397539853995400540154025403540454055406540754085409541054115412541354145415541654175418541954205421542254235424542554265427542854295430543154325433543454355436543754385439544054415442544354445445544654475448544954505451545254535454545554565457545854595460546154625463546454655466546754685469547054715472547354745475547654775478547954805481548254835484548554865487548854895490549154925493549454955496549754985499550055015502550355045505550655075508550955105511551255135514551555165517551855195520552155225523552455255526552755285529553055315532553355345535553655375538553955405541554255435544554555465547554855495550555155525553555455555556555755585559556055615562556355645565556655675568556955705571557255735574557555765577557855795580558155825583558455855586558755885589559055915592559355945595559655975598559956005601560256035604560556065607560856095610561156125613561456155616561756185619562056215622562356245625562656275628562956305631563256335634563556365637563856395640564156425643564456455646564756485649565056515652565356545655565656575658565956605661566256635664566556665667566856695670567156725673567456755676567756785679568056815682568356845685568656875688568956905691569256935694569556965697569856995700570157025703570457055706570757085709571057115712571357145715571657175718571957205721572257235724572557265727572857295730573157325733573457355736573757385739574057415742574357445745574657475748574957505751575257535754575557565757575857595760576157625763576457655766576757685769577057715772577357745775577657775778577957805781578257835784578557865787578857895790579157925793579457955796579757985799580058015802580358045805580658075808580958105811581258135814581558165817581858195820582158225823582458255826582758285829583058315832583358345835583658375838583958405841584258435844584558465847584858495850585158525853585458555856585758585859586058615862586358645865586658675868586958705871587258735874587558765877587858795880588158825883588458855886588758885889589058915892589358945895589658975898589959005901590259035904590559065907590859095910591159125913591459155916591759185919592059215922592359245925592659275928592959305931593259335934593559365937593859395940594159425943594459455946594759485949595059515952595359545955595659575958595959605961596259635964596559665967596859695970597159725973597459755976597759785979598059815982598359845985598659875988598959905991599259935994599559965997599859996000600160026003600460056006600760086009601060116012601360146015601660176018601960206021602260236024602560266027602860296030603160326033603460356036603760386039604060416042604360446045604660476048604960506051605260536054605560566057605860596060606160626063606460656066606760686069607060716072607360746075607660776078607960806081608260836084608560866087608860896090609160926093609460956096609760986099610061016102610361046105610661076108610961106111611261136114611561166117611861196120612161226123612461256126612761286129613061316132613361346135613661376138613961406141614261436144614561466147614861496150615161526153615461556156615761586159616061616162616361646165616661676168616961706171617261736174617561766177617861796180618161826183618461856186618761886189619061916192619361946195619661976198619962006201620262036204620562066207620862096210621162126213621462156216621762186219622062216222622362246225622662276228622962306231623262336234623562366237623862396240624162426243624462456246624762486249625062516252625362546255625662576258625962606261626262636264626562666267626862696270627162726273627462756276627762786279628062816282628362846285628662876288628962906291629262936294629562966297629862996300630163026303630463056306630763086309631063116312631363146315631663176318631963206321632263236324632563266327632863296330633163326333633463356336633763386339634063416342634363446345634663476348634963506351635263536354635563566357635863596360636163626363636463656366636763686369637063716372637363746375637663776378637963806381638263836384638563866387638863896390639163926393639463956396639763986399640064016402640364046405640664076408640964106411641264136414641564166417641864196420642164226423642464256426642764286429643064316432643364346435643664376438643964406441644264436444644564466447644864496450645164526453645464556456645764586459646064616462646364646465646664676468646964706471647264736474647564766477647864796480648164826483648464856486648764886489649064916492649364946495649664976498649965006501650265036504650565066507650865096510651165126513651465156516651765186519652065216522652365246525652665276528652965306531653265336534653565366537653865396540654165426543654465456546654765486549655065516552655365546555655665576558655965606561656265636564656565666567656865696570657165726573657465756576657765786579658065816582658365846585658665876588658965906591659265936594659565966597659865996600660166026603660466056606660766086609661066116612661366146615661666176618661966206621662266236624662566266627662866296630663166326633663466356636663766386639664066416642664366446645664666476648664966506651665266536654665566566657665866596660666166626663666466656666666766686669667066716672667366746675667666776678667966806681668266836684668566866687668866896690669166926693669466956696669766986699670067016702670367046705670667076708670967106711671267136714671567166717671867196720672167226723672467256726672767286729673067316732673367346735673667376738673967406741674267436744674567466747674867496750675167526753675467556756675767586759676067616762676367646765676667676768676967706771677267736774677567766777677867796780678167826783678467856786678767886789679067916792679367946795679667976798679968006801680268036804680568066807680868096810681168126813681468156816681768186819682068216822682368246825682668276828682968306831683268336834683568366837683868396840684168426843684468456846684768486849685068516852685368546855685668576858685968606861686268636864686568666867686868696870687168726873687468756876687768786879688068816882688368846885688668876888688968906891689268936894689568966897689868996900690169026903690469056906690769086909691069116912691369146915691669176918691969206921692269236924692569266927692869296930693169326933693469356936693769386939694069416942694369446945694669476948694969506951695269536954695569566957695869596960696169626963696469656966696769686969697069716972697369746975697669776978697969806981698269836984698569866987698869896990699169926993699469956996699769986999700070017002700370047005700670077008700970107011701270137014701570167017701870197020702170227023702470257026702770287029703070317032703370347035703670377038703970407041704270437044704570467047704870497050705170527053705470557056705770587059706070617062706370647065706670677068706970707071707270737074707570767077707870797080708170827083708470857086708770887089709070917092709370947095709670977098709971007101710271037104710571067107710871097110711171127113711471157116711771187119712071217122712371247125712671277128712971307131713271337134713571367137713871397140714171427143714471457146714771487149715071517152715371547155715671577158715971607161716271637164716571667167716871697170717171727173717471757176717771787179718071817182718371847185718671877188718971907191719271937194719571967197719871997200720172027203720472057206720772087209721072117212721372147215721672177218721972207221722272237224722572267227722872297230723172327233723472357236723772387239724072417242724372447245724672477248724972507251725272537254725572567257725872597260726172627263726472657266726772687269727072717272727372747275727672777278727972807281728272837284728572867287728872897290729172927293729472957296729772987299730073017302730373047305730673077308730973107311731273137314731573167317731873197320732173227323732473257326732773287329733073317332733373347335733673377338733973407341734273437344734573467347734873497350735173527353735473557356735773587359736073617362736373647365736673677368736973707371737273737374737573767377737873797380738173827383738473857386738773887389739073917392739373947395739673977398739974007401740274037404740574067407740874097410741174127413741474157416741774187419742074217422742374247425742674277428742974307431743274337434743574367437743874397440744174427443744474457446744774487449745074517452745374547455745674577458745974607461746274637464746574667467746874697470747174727473747474757476747774787479748074817482748374847485748674877488748974907491749274937494749574967497749874997500750175027503750475057506750775087509751075117512751375147515751675177518751975207521752275237524752575267527752875297530753175327533753475357536753775387539754075417542754375447545754675477548754975507551755275537554755575567557755875597560756175627563756475657566756775687569757075717572757375747575757675777578757975807581758275837584758575867587758875897590759175927593759475957596759775987599760076017602760376047605760676077608760976107611761276137614761576167617761876197620762176227623762476257626762776287629763076317632763376347635763676377638763976407641764276437644764576467647764876497650765176527653765476557656765776587659766076617662766376647665766676677668766976707671767276737674767576767677767876797680768176827683768476857686768776887689769076917692769376947695769676977698769977007701770277037704770577067707770877097710771177127713771477157716771777187719772077217722772377247725772677277728772977307731773277337734773577367737773877397740774177427743774477457746774777487749775077517752775377547755775677577758775977607761776277637764776577667767776877697770777177727773777477757776777777787779778077817782778377847785778677877788778977907791779277937794779577967797779877997800780178027803780478057806780778087809781078117812781378147815781678177818781978207821782278237824782578267827782878297830783178327833783478357836783778387839784078417842784378447845784678477848784978507851785278537854785578567857785878597860786178627863786478657866786778687869787078717872787378747875787678777878787978807881788278837884788578867887788878897890789178927893789478957896789778987899790079017902790379047905790679077908790979107911791279137914791579167917791879197920792179227923792479257926792779287929793079317932793379347935793679377938793979407941794279437944794579467947794879497950795179527953795479557956795779587959796079617962796379647965796679677968796979707971797279737974797579767977797879797980798179827983798479857986798779887989799079917992799379947995799679977998799980008001800280038004800580068007800880098010801180128013801480158016801780188019802080218022802380248025802680278028802980308031803280338034803580368037803880398040804180428043804480458046804780488049805080518052805380548055805680578058805980608061806280638064806580668067806880698070807180728073807480758076807780788079808080818082808380848085808680878088808980908091809280938094809580968097809880998100810181028103810481058106810781088109811081118112811381148115811681178118811981208121812281238124812581268127812881298130813181328133813481358136813781388139814081418142814381448145814681478148814981508151815281538154815581568157815881598160816181628163816481658166816781688169817081718172817381748175817681778178817981808181818281838184818581868187818881898190819181928193819481958196819781988199820082018202820382048205820682078208820982108211821282138214821582168217821882198220822182228223822482258226822782288229823082318232823382348235823682378238823982408241824282438244824582468247824882498250825182528253825482558256825782588259826082618262826382648265826682678268826982708271827282738274827582768277827882798280828182828283828482858286828782888289829082918292829382948295829682978298829983008301830283038304830583068307830883098310831183128313831483158316831783188319832083218322832383248325832683278328832983308331833283338334833583368337833883398340834183428343834483458346834783488349835083518352835383548355835683578358835983608361836283638364836583668367836883698370837183728373837483758376837783788379838083818382838383848385838683878388838983908391839283938394839583968397839883998400840184028403840484058406840784088409841084118412841384148415841684178418841984208421842284238424842584268427842884298430843184328433843484358436843784388439844084418442844384448445844684478448844984508451845284538454845584568457845884598460846184628463846484658466846784688469847084718472847384748475847684778478847984808481848284838484848584868487848884898490849184928493849484958496849784988499850085018502850385048505850685078508850985108511851285138514851585168517851885198520852185228523852485258526852785288529853085318532853385348535853685378538853985408541854285438544854585468547854885498550855185528553855485558556855785588559856085618562856385648565856685678568856985708571857285738574857585768577857885798580858185828583858485858586858785888589859085918592859385948595859685978598859986008601860286038604860586068607860886098610861186128613861486158616861786188619862086218622862386248625862686278628862986308631863286338634863586368637863886398640864186428643864486458646864786488649865086518652865386548655865686578658865986608661866286638664866586668667866886698670867186728673867486758676867786788679868086818682868386848685868686878688868986908691869286938694869586968697869886998700870187028703870487058706870787088709871087118712871387148715871687178718871987208721872287238724872587268727872887298730873187328733873487358736873787388739874087418742874387448745874687478748874987508751875287538754875587568757875887598760876187628763876487658766876787688769877087718772877387748775877687778778877987808781878287838784878587868787878887898790879187928793879487958796879787988799880088018802880388048805880688078808880988108811881288138814881588168817881888198820882188228823882488258826882788288829883088318832883388348835883688378838883988408841884288438844884588468847884888498850885188528853885488558856885788588859886088618862886388648865886688678868886988708871887288738874887588768877887888798880888188828883888488858886888788888889889088918892889388948895889688978898889989008901890289038904890589068907890889098910891189128913891489158916891789188919892089218922892389248925892689278928892989308931893289338934893589368937893889398940894189428943894489458946894789488949895089518952895389548955895689578958895989608961896289638964896589668967896889698970897189728973897489758976897789788979898089818982898389848985898689878988898989908991899289938994899589968997899889999000900190029003900490059006900790089009901090119012901390149015901690179018901990209021902290239024902590269027902890299030903190329033903490359036903790389039904090419042904390449045904690479048904990509051905290539054905590569057905890599060906190629063906490659066906790689069907090719072907390749075907690779078907990809081908290839084908590869087908890899090909190929093909490959096909790989099910091019102910391049105910691079108910991109111911291139114911591169117911891199120912191229123912491259126912791289129913091319132913391349135913691379138913991409141914291439144914591469147914891499150915191529153915491559156915791589159916091619162916391649165916691679168916991709171917291739174917591769177917891799180918191829183918491859186918791889189919091919192919391949195919691979198919992009201920292039204920592069207920892099210921192129213921492159216921792189219922092219222922392249225922692279228922992309231923292339234923592369237923892399240924192429243924492459246924792489249925092519252925392549255925692579258925992609261926292639264926592669267926892699270927192729273927492759276927792789279928092819282928392849285928692879288928992909291929292939294929592969297929892999300930193029303930493059306930793089309931093119312931393149315931693179318931993209321932293239324932593269327932893299330933193329333933493359336933793389339934093419342934393449345934693479348934993509351935293539354935593569357935893599360936193629363936493659366936793689369937093719372937393749375937693779378937993809381938293839384938593869387938893899390939193929393939493959396939793989399940094019402940394049405940694079408940994109411941294139414941594169417941894199420942194229423942494259426942794289429943094319432943394349435943694379438943994409441944294439444944594469447944894499450945194529453945494559456945794589459946094619462946394649465946694679468946994709471947294739474947594769477947894799480948194829483948494859486948794889489949094919492949394949495949694979498949995009501950295039504950595069507950895099510951195129513951495159516951795189519952095219522952395249525952695279528952995309531953295339534953595369537953895399540954195429543954495459546954795489549955095519552955395549555955695579558955995609561956295639564956595669567956895699570957195729573957495759576957795789579958095819582958395849585958695879588958995909591959295939594959595969597959895999600960196029603960496059606960796089609961096119612961396149615961696179618961996209621962296239624962596269627962896299630963196329633963496359636963796389639964096419642964396449645964696479648964996509651965296539654965596569657965896599660966196629663966496659666966796689669967096719672967396749675967696779678967996809681968296839684968596869687968896899690969196929693969496959696969796989699970097019702970397049705970697079708970997109711971297139714971597169717971897199720972197229723972497259726972797289729973097319732973397349735973697379738973997409741974297439744974597469747974897499750975197529753975497559756975797589759976097619762976397649765976697679768976997709771977297739774977597769777977897799780978197829783978497859786978797889789979097919792979397949795979697979798979998009801980298039804980598069807980898099810981198129813981498159816981798189819982098219822982398249825982698279828982998309831983298339834983598369837983898399840984198429843984498459846984798489849985098519852985398549855985698579858985998609861986298639864986598669867986898699870987198729873987498759876987798789879988098819882988398849885988698879888988998909891989298939894989598969897989898999900990199029903990499059906990799089909991099119912991399149915991699179918991999209921992299239924992599269927992899299930993199329933993499359936993799389939994099419942994399449945994699479948994999509951995299539954995599569957995899599960996199629963996499659966996799689969997099719972997399749975997699779978997999809981998299839984998599869987998899899990999199929993999499959996999799989999100001000110002100031000410005100061000710008100091001010011100121001310014100151001610017100181001910020100211002210023100241002510026100271002810029100301003110032100331003410035100361003710038100391004010041100421004310044100451004610047100481004910050100511005210053100541005510056100571005810059100601006110062100631006410065100661006710068100691007010071100721007310074100751007610077100781007910080100811008210083100841008510086100871008810089100901009110092100931009410095100961009710098100991010010101101021010310104101051010610107101081010910110101111011210113101141011510116101171011810119101201012110122101231012410125101261012710128101291013010131101321013310134101351013610137101381013910140101411014210143101441014510146101471014810149101501015110152101531015410155101561015710158101591016010161101621016310164101651016610167101681016910170101711017210173101741017510176101771017810179101801018110182101831018410185101861018710188101891019010191101921019310194101951019610197101981019910200102011020210203102041020510206102071020810209102101021110212102131021410215102161021710218102191022010221102221022310224102251022610227102281022910230102311023210233102341023510236102371023810239102401024110242102431024410245102461024710248102491025010251102521025310254102551025610257102581025910260102611026210263102641026510266102671026810269102701027110272102731027410275102761027710278102791028010281102821028310284102851028610287102881028910290102911029210293102941029510296102971029810299103001030110302103031030410305103061030710308103091031010311103121031310314103151031610317103181031910320103211032210323103241032510326103271032810329103301033110332103331033410335103361033710338103391034010341103421034310344103451034610347103481034910350103511035210353103541035510356103571035810359103601036110362103631036410365103661036710368103691037010371103721037310374103751037610377103781037910380103811038210383103841038510386103871038810389103901039110392103931039410395103961039710398103991040010401104021040310404104051040610407104081040910410104111041210413104141041510416104171041810419104201042110422104231042410425104261042710428104291043010431104321043310434104351043610437104381043910440104411044210443104441044510446104471044810449104501045110452104531045410455104561045710458104591046010461104621046310464104651046610467104681046910470104711047210473104741047510476104771047810479104801048110482104831048410485104861048710488104891049010491104921049310494104951049610497104981049910500105011050210503105041050510506105071050810509105101051110512105131051410515105161051710518105191052010521105221052310524105251052610527105281052910530105311053210533105341053510536105371053810539105401054110542105431054410545105461054710548105491055010551105521055310554105551055610557105581055910560105611056210563105641056510566105671056810569105701057110572105731057410575105761057710578105791058010581105821058310584105851058610587105881058910590105911059210593105941059510596105971059810599106001060110602106031060410605106061060710608106091061010611106121061310614106151061610617106181061910620106211062210623106241062510626106271062810629106301063110632106331063410635106361063710638106391064010641106421064310644106451064610647106481064910650106511065210653106541065510656106571065810659106601066110662106631066410665106661066710668106691067010671106721067310674106751067610677106781067910680106811068210683106841068510686106871068810689106901069110692106931069410695106961069710698106991070010701107021070310704107051070610707107081070910710107111071210713107141071510716107171071810719107201072110722107231072410725107261072710728107291073010731107321073310734107351073610737107381073910740107411074210743107441074510746107471074810749107501075110752107531075410755107561075710758107591076010761107621076310764107651076610767107681076910770107711077210773107741077510776107771077810779107801078110782107831078410785107861078710788107891079010791107921079310794107951079610797107981079910800108011080210803108041080510806108071080810809108101081110812108131081410815108161081710818108191082010821108221082310824108251082610827108281082910830108311083210833108341083510836108371083810839108401084110842108431084410845108461084710848108491085010851108521085310854108551085610857108581085910860108611086210863108641086510866108671086810869108701087110872108731087410875108761087710878108791088010881108821088310884108851088610887108881088910890108911089210893108941089510896108971089810899109001090110902109031090410905109061090710908109091091010911109121091310914109151091610917109181091910920109211092210923109241092510926109271092810929109301093110932109331093410935109361093710938109391094010941109421094310944109451094610947109481094910950109511095210953109541095510956109571095810959109601096110962109631096410965109661096710968109691097010971109721097310974109751097610977109781097910980109811098210983109841098510986109871098810989109901099110992109931099410995109961099710998109991100011001110021100311004110051100611007110081100911010110111101211013110141101511016110171101811019110201102111022110231102411025110261102711028110291103011031110321103311034110351103611037110381103911040110411104211043110441104511046110471104811049110501105111052110531105411055110561105711058110591106011061110621106311064110651106611067110681106911070110711107211073110741107511076110771107811079110801108111082110831108411085110861108711088110891109011091110921109311094110951109611097110981109911100111011110211103111041110511106111071110811109111101111111112111131111411115111161111711118111191112011121111221112311124111251112611127111281112911130111311113211133111341113511136111371113811139111401114111142111431114411145111461114711148111491115011151111521115311154111551115611157111581115911160111611116211163111641116511166111671116811169111701117111172111731117411175111761117711178111791118011181111821118311184111851118611187111881118911190111911119211193111941119511196111971119811199112001120111202112031120411205112061120711208112091121011211112121121311214112151121611217112181121911220112211122211223112241122511226112271122811229112301123111232112331123411235112361123711238112391124011241112421124311244112451124611247112481124911250112511125211253112541125511256112571125811259112601126111262112631126411265112661126711268112691127011271112721127311274112751127611277112781127911280112811128211283112841128511286112871128811289112901129111292112931129411295112961129711298112991130011301113021130311304113051130611307113081130911310113111131211313113141131511316113171131811319113201132111322113231132411325113261132711328113291133011331113321133311334113351133611337113381133911340113411134211343113441134511346113471134811349113501135111352113531135411355113561135711358113591136011361113621136311364113651136611367113681136911370113711137211373113741137511376113771137811379113801138111382113831138411385113861138711388113891139011391113921139311394113951139611397113981139911400114011140211403114041140511406114071140811409114101141111412114131141411415114161141711418114191142011421114221142311424114251142611427114281142911430114311143211433114341143511436114371143811439114401144111442114431144411445114461144711448114491145011451114521145311454114551145611457114581145911460114611146211463114641146511466114671146811469114701147111472114731147411475114761147711478114791148011481114821148311484114851148611487114881148911490114911149211493114941149511496114971149811499115001150111502115031150411505115061150711508115091151011511115121151311514115151151611517115181151911520115211152211523115241152511526115271152811529115301153111532115331153411535115361153711538115391154011541115421154311544115451154611547115481154911550115511155211553115541155511556115571155811559115601156111562115631156411565115661156711568115691157011571115721157311574115751157611577115781157911580115811158211583115841158511586115871158811589115901159111592115931159411595115961159711598115991160011601116021160311604116051160611607116081160911610116111161211613116141161511616116171161811619116201162111622116231162411625116261162711628116291163011631116321163311634116351163611637116381163911640116411164211643116441164511646116471164811649116501165111652116531165411655116561165711658116591166011661116621166311664116651166611667116681166911670116711167211673116741167511676116771167811679116801168111682116831168411685116861168711688116891169011691116921169311694116951169611697116981169911700117011170211703117041170511706117071170811709117101171111712117131171411715117161171711718117191172011721117221172311724117251172611727117281172911730117311173211733117341173511736117371173811739117401174111742117431174411745117461174711748117491175011751117521175311754117551175611757117581175911760117611176211763117641176511766117671176811769117701177111772117731177411775117761177711778117791178011781117821178311784117851178611787117881178911790117911179211793117941179511796117971179811799118001180111802118031180411805118061180711808118091181011811118121181311814118151181611817118181181911820118211182211823118241182511826118271182811829118301183111832118331183411835118361183711838118391184011841118421184311844118451184611847118481184911850118511185211853118541185511856118571185811859118601186111862118631186411865118661186711868118691187011871118721187311874118751187611877118781187911880118811188211883118841188511886118871188811889118901189111892118931189411895118961189711898118991190011901119021190311904119051190611907119081190911910119111191211913119141191511916119171191811919119201192111922119231192411925119261192711928119291193011931119321193311934119351193611937119381193911940119411194211943119441194511946119471194811949119501195111952119531195411955119561195711958119591196011961119621196311964119651196611967119681196911970119711197211973119741197511976119771197811979119801198111982119831198411985119861198711988119891199011991119921199311994119951199611997119981199912000120011200212003120041200512006120071200812009120101201112012120131201412015120161201712018120191202012021120221202312024120251202612027120281202912030120311203212033120341203512036120371203812039120401204112042120431204412045120461204712048120491205012051120521205312054120551205612057120581205912060120611206212063120641206512066120671206812069120701207112072120731207412075120761207712078120791208012081120821208312084120851208612087120881208912090120911209212093120941209512096120971209812099121001210112102121031210412105121061210712108121091211012111121121211312114121151211612117121181211912120121211212212123121241212512126121271212812129121301213112132121331213412135121361213712138121391214012141121421214312144121451214612147121481214912150121511215212153121541215512156121571215812159121601216112162121631216412165121661216712168121691217012171121721217312174121751217612177121781217912180121811218212183121841218512186121871218812189121901219112192121931219412195121961219712198121991220012201122021220312204122051220612207122081220912210122111221212213122141221512216122171221812219122201222112222122231222412225122261222712228122291223012231122321223312234122351223612237122381223912240122411224212243122441224512246122471224812249122501225112252122531225412255122561225712258122591226012261122621226312264122651226612267122681226912270122711227212273122741227512276122771227812279122801228112282122831228412285122861228712288122891229012291122921229312294122951229612297122981229912300123011230212303123041230512306123071230812309123101231112312123131231412315123161231712318123191232012321123221232312324123251232612327123281232912330123311233212333123341233512336123371233812339123401234112342123431234412345123461234712348123491235012351123521235312354123551235612357123581235912360123611236212363123641236512366123671236812369123701237112372123731237412375123761237712378123791238012381123821238312384123851238612387123881238912390123911239212393123941239512396123971239812399124001240112402124031240412405124061240712408124091241012411124121241312414124151241612417124181241912420124211242212423124241242512426124271242812429124301243112432124331243412435124361243712438124391244012441124421244312444124451244612447124481244912450124511245212453124541245512456124571245812459124601246112462124631246412465124661246712468124691247012471124721247312474124751247612477124781247912480124811248212483124841248512486124871248812489124901249112492124931249412495124961249712498124991250012501125021250312504125051250612507125081250912510125111251212513125141251512516125171251812519125201252112522125231252412525125261252712528125291253012531125321253312534125351253612537125381253912540125411254212543125441254512546125471254812549125501255112552125531255412555125561255712558125591256012561125621256312564125651256612567125681256912570125711257212573125741257512576125771257812579125801258112582125831258412585125861258712588125891259012591125921259312594125951259612597125981259912600126011260212603126041260512606126071260812609126101261112612126131261412615126161261712618126191262012621126221262312624126251262612627126281262912630126311263212633126341263512636126371263812639126401264112642126431264412645126461264712648126491265012651126521265312654126551265612657126581265912660126611266212663126641266512666126671266812669126701267112672126731267412675126761267712678126791268012681126821268312684126851268612687126881268912690126911269212693126941269512696126971269812699127001270112702127031270412705127061270712708127091271012711127121271312714127151271612717127181271912720127211272212723127241272512726127271272812729127301273112732127331273412735127361273712738127391274012741127421274312744127451274612747127481274912750127511275212753127541275512756127571275812759127601276112762127631276412765127661276712768127691277012771127721277312774127751277612777127781277912780127811278212783127841278512786127871278812789127901279112792127931279412795127961279712798127991280012801128021280312804128051280612807128081280912810128111281212813128141281512816128171281812819128201282112822128231282412825128261282712828128291283012831128321283312834128351283612837128381283912840128411284212843128441284512846128471284812849128501285112852128531285412855128561285712858128591286012861128621286312864128651286612867128681286912870128711287212873128741287512876128771287812879128801288112882128831288412885128861288712888128891289012891128921289312894128951289612897128981289912900129011290212903129041290512906129071290812909129101291112912129131291412915129161291712918129191292012921129221292312924129251292612927129281292912930129311293212933129341293512936129371293812939129401294112942129431294412945129461294712948129491295012951129521295312954129551295612957129581295912960129611296212963129641296512966129671296812969129701297112972129731297412975129761297712978129791298012981129821298312984129851298612987129881298912990129911299212993129941299512996129971299812999130001300113002130031300413005130061300713008130091301013011130121301313014130151301613017130181301913020130211302213023130241302513026130271302813029130301303113032130331303413035130361303713038130391304013041130421304313044130451304613047130481304913050130511305213053130541305513056130571305813059130601306113062130631306413065130661306713068130691307013071130721307313074130751307613077130781307913080130811308213083130841308513086130871308813089130901309113092130931309413095130961309713098130991310013101131021310313104131051310613107131081310913110131111311213113131141311513116131171311813119131201312113122131231312413125131261312713128131291313013131131321313313134131351313613137131381313913140131411314213143131441314513146131471314813149131501315113152131531315413155131561315713158131591316013161131621316313164131651316613167131681316913170131711317213173131741317513176131771317813179131801318113182131831318413185131861318713188131891319013191131921319313194131951319613197131981319913200132011320213203132041320513206132071320813209132101321113212132131321413215132161321713218132191322013221132221322313224132251322613227132281322913230132311323213233132341323513236132371323813239132401324113242132431324413245132461324713248132491325013251132521325313254132551325613257132581325913260132611326213263132641326513266132671326813269132701327113272132731327413275132761327713278132791328013281132821328313284132851328613287132881328913290132911329213293132941329513296132971329813299133001330113302133031330413305133061330713308133091331013311133121331313314133151331613317133181331913320133211332213323133241332513326133271332813329133301333113332133331333413335133361333713338133391334013341133421334313344133451334613347133481334913350133511335213353133541335513356133571335813359133601336113362133631336413365133661336713368133691337013371133721337313374133751337613377133781337913380133811338213383133841338513386133871338813389133901339113392133931339413395133961339713398133991340013401134021340313404134051340613407134081340913410134111341213413134141341513416134171341813419134201342113422134231342413425134261342713428134291343013431134321343313434134351343613437134381343913440134411344213443134441344513446134471344813449134501345113452134531345413455134561345713458134591346013461134621346313464134651346613467134681346913470134711347213473134741347513476134771347813479134801348113482134831348413485134861348713488134891349013491134921349313494134951349613497134981349913500135011350213503135041350513506135071350813509135101351113512135131351413515135161351713518135191352013521135221352313524135251352613527135281352913530135311353213533135341353513536135371353813539135401354113542135431354413545135461354713548135491355013551135521355313554135551355613557135581355913560135611356213563135641356513566135671356813569135701357113572135731357413575135761357713578135791358013581135821358313584135851358613587135881358913590135911359213593135941359513596135971359813599136001360113602136031360413605136061360713608136091361013611136121361313614136151361613617136181361913620136211362213623136241362513626136271362813629136301363113632136331363413635136361363713638136391364013641136421364313644136451364613647136481364913650136511365213653136541365513656136571365813659136601366113662136631366413665136661366713668136691367013671136721367313674136751367613677136781367913680136811368213683136841368513686136871368813689136901369113692136931369413695136961369713698136991370013701137021370313704137051370613707137081370913710137111371213713137141371513716137171371813719137201372113722137231372413725137261372713728137291373013731137321373313734137351373613737137381373913740137411374213743137441374513746137471374813749137501375113752137531375413755137561375713758137591376013761137621376313764137651376613767137681376913770137711377213773137741377513776137771377813779137801378113782137831378413785137861378713788137891379013791137921379313794137951379613797137981379913800138011380213803138041380513806138071380813809138101381113812138131381413815138161381713818138191382013821138221382313824138251382613827138281382913830138311383213833138341383513836138371383813839138401384113842138431384413845138461384713848138491385013851138521385313854138551385613857138581385913860138611386213863138641386513866138671386813869138701387113872138731387413875138761387713878138791388013881138821388313884138851388613887138881388913890138911389213893138941389513896138971389813899139001390113902139031390413905139061390713908139091391013911139121391313914139151391613917139181391913920139211392213923139241392513926139271392813929139301393113932139331393413935139361393713938139391394013941139421394313944139451394613947139481394913950139511395213953139541395513956139571395813959139601396113962139631396413965139661396713968139691397013971139721397313974139751397613977139781397913980139811398213983139841398513986139871398813989139901399113992139931399413995139961399713998139991400014001140021400314004140051400614007140081400914010140111401214013140141401514016140171401814019140201402114022140231402414025140261402714028140291403014031140321403314034140351403614037140381403914040140411404214043140441404514046140471404814049140501405114052140531405414055140561405714058140591406014061140621406314064140651406614067140681406914070140711407214073140741407514076140771407814079140801408114082140831408414085140861408714088140891409014091140921409314094140951409614097140981409914100141011410214103141041410514106141071410814109141101411114112141131411414115141161411714118141191412014121141221412314124141251412614127141281412914130141311413214133141341413514136141371413814139141401414114142141431414414145141461414714148141491415014151141521415314154141551415614157141581415914160141611416214163141641416514166141671416814169141701417114172141731417414175141761417714178141791418014181141821418314184141851418614187141881418914190141911419214193141941419514196141971419814199142001420114202142031420414205142061420714208142091421014211142121421314214142151421614217142181421914220142211422214223142241422514226142271422814229142301423114232142331423414235142361423714238142391424014241142421424314244142451424614247142481424914250142511425214253142541425514256142571425814259142601426114262142631426414265142661426714268142691427014271142721427314274142751427614277142781427914280142811428214283142841428514286142871428814289142901429114292142931429414295142961429714298142991430014301143021430314304143051430614307143081430914310143111431214313143141431514316143171431814319143201432114322143231432414325143261432714328143291433014331143321433314334143351433614337143381433914340143411434214343143441434514346143471434814349143501435114352143531435414355143561435714358143591436014361143621436314364143651436614367143681436914370143711437214373143741437514376143771437814379143801438114382143831438414385143861438714388143891439014391143921439314394143951439614397143981439914400144011440214403144041440514406144071440814409144101441114412144131441414415144161441714418144191442014421144221442314424144251442614427144281442914430144311443214433144341443514436144371443814439144401444114442144431444414445144461444714448144491445014451144521445314454144551445614457144581445914460144611446214463144641446514466144671446814469144701447114472144731447414475144761447714478144791448014481144821448314484144851448614487144881448914490144911449214493144941449514496144971449814499145001450114502145031450414505145061450714508145091451014511145121451314514145151451614517145181451914520145211452214523145241452514526145271452814529145301453114532145331453414535145361453714538145391454014541145421454314544145451454614547145481454914550145511455214553145541455514556145571455814559145601456114562145631456414565145661456714568145691457014571145721457314574145751457614577145781457914580145811458214583145841458514586145871458814589145901459114592145931459414595145961459714598145991460014601146021460314604146051460614607146081460914610146111461214613146141461514616146171461814619146201462114622146231462414625146261462714628146291463014631146321463314634146351463614637146381463914640146411464214643146441464514646146471464814649146501465114652146531465414655146561465714658146591466014661146621466314664146651466614667146681466914670146711467214673146741467514676146771467814679146801468114682146831468414685146861468714688146891469014691146921469314694146951469614697146981469914700147011470214703147041470514706147071470814709147101471114712147131471414715147161471714718147191472014721147221472314724147251472614727147281472914730147311473214733147341473514736147371473814739147401474114742147431474414745147461474714748147491475014751147521475314754147551475614757147581475914760147611476214763147641476514766147671476814769147701477114772147731477414775147761477714778147791478014781147821478314784147851478614787147881478914790147911479214793147941479514796147971479814799148001480114802148031480414805148061480714808148091481014811148121481314814148151481614817148181481914820148211482214823148241482514826148271482814829148301483114832148331483414835148361483714838148391484014841148421484314844148451484614847148481484914850148511485214853148541485514856148571485814859148601486114862148631486414865148661486714868148691487014871148721487314874148751487614877148781487914880148811488214883148841488514886148871488814889148901489114892148931489414895148961489714898148991490014901149021490314904149051490614907149081490914910149111491214913149141491514916149171491814919149201492114922149231492414925149261492714928149291493014931149321493314934149351493614937149381493914940149411494214943149441494514946149471494814949149501495114952149531495414955149561495714958149591496014961149621496314964149651496614967149681496914970149711497214973149741497514976149771497814979149801498114982149831498414985149861498714988149891499014991149921499314994149951499614997149981499915000150011500215003150041500515006150071500815009150101501115012150131501415015150161501715018150191502015021150221502315024150251502615027150281502915030150311503215033150341503515036150371503815039150401504115042150431504415045150461504715048150491505015051150521505315054150551505615057150581505915060150611506215063150641506515066150671506815069150701507115072150731507415075150761507715078150791508015081150821508315084150851508615087150881508915090150911509215093150941509515096150971509815099151001510115102151031510415105151061510715108151091511015111151121511315114151151511615117151181511915120151211512215123151241512515126151271512815129151301513115132151331513415135151361513715138151391514015141151421514315144151451514615147151481514915150151511515215153151541515515156151571515815159151601516115162151631516415165151661516715168151691517015171151721517315174151751517615177151781517915180151811518215183151841518515186151871518815189151901519115192151931519415195151961519715198151991520015201152021520315204152051520615207152081520915210152111521215213152141521515216152171521815219152201522115222152231522415225152261522715228152291523015231152321523315234152351523615237152381523915240152411524215243152441524515246152471524815249152501525115252152531525415255152561525715258152591526015261152621526315264152651526615267152681526915270152711527215273152741527515276152771527815279152801528115282152831528415285152861528715288152891529015291152921529315294152951529615297152981529915300153011530215303153041530515306153071530815309153101531115312153131531415315153161531715318153191532015321153221532315324153251532615327153281532915330153311533215333153341533515336153371533815339153401534115342153431534415345153461534715348153491535015351153521535315354153551535615357153581535915360153611536215363153641536515366153671536815369153701537115372153731537415375153761537715378153791538015381153821538315384153851538615387153881538915390153911539215393153941539515396153971539815399154001540115402154031540415405154061540715408154091541015411154121541315414154151541615417154181541915420154211542215423154241542515426154271542815429154301543115432154331543415435154361543715438154391544015441154421544315444154451544615447154481544915450154511545215453154541545515456154571545815459154601546115462154631546415465154661546715468154691547015471154721547315474154751547615477154781547915480154811548215483154841548515486154871548815489154901549115492154931549415495154961549715498154991550015501155021550315504155051550615507155081550915510155111551215513155141551515516155171551815519155201552115522155231552415525155261552715528155291553015531155321553315534155351553615537155381553915540155411554215543155441554515546155471554815549155501555115552155531555415555155561555715558155591556015561155621556315564155651556615567155681556915570155711557215573155741557515576155771557815579155801558115582155831558415585155861558715588155891559015591155921559315594155951559615597155981559915600156011560215603156041560515606156071560815609156101561115612156131561415615156161561715618156191562015621156221562315624156251562615627156281562915630156311563215633156341563515636156371563815639156401564115642156431564415645156461564715648156491565015651156521565315654156551565615657156581565915660156611566215663156641566515666156671566815669156701567115672156731567415675156761567715678156791568015681156821568315684156851568615687156881568915690156911569215693156941569515696156971569815699157001570115702157031570415705157061570715708157091571015711157121571315714157151571615717157181571915720157211572215723157241572515726157271572815729157301573115732157331573415735157361573715738157391574015741157421574315744157451574615747157481574915750157511575215753157541575515756157571575815759157601576115762157631576415765157661576715768157691577015771157721577315774157751577615777157781577915780157811578215783157841578515786157871578815789157901579115792157931579415795157961579715798157991580015801158021580315804158051580615807158081580915810158111581215813158141581515816158171581815819158201582115822158231582415825158261582715828158291583015831158321583315834158351583615837158381583915840158411584215843158441584515846158471584815849158501585115852158531585415855158561585715858158591586015861158621586315864158651586615867158681586915870158711587215873158741587515876158771587815879158801588115882158831588415885158861588715888158891589015891158921589315894158951589615897158981589915900159011590215903159041590515906159071590815909159101591115912159131591415915159161591715918159191592015921159221592315924159251592615927159281592915930159311593215933159341593515936159371593815939159401594115942159431594415945159461594715948159491595015951159521595315954159551595615957159581595915960159611596215963159641596515966159671596815969159701597115972159731597415975159761597715978159791598015981159821598315984159851598615987159881598915990159911599215993159941599515996159971599815999160001600116002160031600416005160061600716008160091601016011160121601316014160151601616017160181601916020160211602216023160241602516026160271602816029160301603116032160331603416035160361603716038160391604016041160421604316044160451604616047160481604916050160511605216053160541605516056160571605816059160601606116062160631606416065160661606716068160691607016071160721607316074160751607616077160781607916080160811608216083160841608516086160871608816089160901609116092160931609416095160961609716098160991610016101161021610316104161051610616107161081610916110161111611216113161141611516116161171611816119161201612116122161231612416125161261612716128161291613016131161321613316134161351613616137161381613916140161411614216143161441614516146161471614816149161501615116152161531615416155161561615716158161591616016161161621616316164161651616616167161681616916170161711617216173161741617516176161771617816179161801618116182161831618416185161861618716188161891619016191161921619316194161951619616197161981619916200162011620216203162041620516206162071620816209162101621116212162131621416215162161621716218162191622016221162221622316224162251622616227162281622916230162311623216233162341623516236162371623816239162401624116242162431624416245162461624716248162491625016251162521625316254162551625616257162581625916260162611626216263162641626516266162671626816269162701627116272162731627416275162761627716278162791628016281162821628316284162851628616287162881628916290162911629216293162941629516296162971629816299163001630116302163031630416305163061630716308163091631016311163121631316314163151631616317163181631916320163211632216323163241632516326163271632816329163301633116332163331633416335163361633716338163391634016341163421634316344163451634616347163481634916350163511635216353163541635516356163571635816359163601636116362163631636416365163661636716368163691637016371163721637316374163751637616377163781637916380163811638216383163841638516386163871638816389163901639116392163931639416395163961639716398163991640016401164021640316404164051640616407164081640916410164111641216413164141641516416164171641816419164201642116422164231642416425164261642716428164291643016431164321643316434164351643616437164381643916440164411644216443164441644516446164471644816449164501645116452164531645416455164561645716458164591646016461164621646316464164651646616467164681646916470164711647216473164741647516476164771647816479164801648116482164831648416485164861648716488164891649016491164921649316494164951649616497164981649916500165011650216503165041650516506165071650816509165101651116512165131651416515165161651716518165191652016521165221652316524165251652616527165281652916530165311653216533165341653516536165371653816539165401654116542165431654416545165461654716548165491655016551165521655316554165551655616557165581655916560165611656216563165641656516566165671656816569165701657116572165731657416575165761657716578165791658016581165821658316584165851658616587165881658916590165911659216593165941659516596165971659816599166001660116602166031660416605166061660716608166091661016611166121661316614166151661616617166181661916620166211662216623166241662516626166271662816629166301663116632166331663416635166361663716638166391664016641166421664316644166451664616647166481664916650166511665216653166541665516656166571665816659166601666116662166631666416665166661666716668166691667016671166721667316674166751667616677166781667916680166811668216683166841668516686166871668816689166901669116692166931669416695166961669716698166991670016701167021670316704167051670616707167081670916710167111671216713167141671516716167171671816719167201672116722167231672416725167261672716728167291673016731167321673316734167351673616737167381673916740167411674216743167441674516746167471674816749167501675116752167531675416755167561675716758167591676016761167621676316764167651676616767167681676916770167711677216773167741677516776167771677816779167801678116782167831678416785167861678716788167891679016791167921679316794167951679616797167981679916800168011680216803168041680516806168071680816809168101681116812168131681416815168161681716818168191682016821168221682316824168251682616827168281682916830168311683216833168341683516836168371683816839168401684116842168431684416845168461684716848168491685016851168521685316854168551685616857168581685916860168611686216863168641686516866168671686816869168701687116872168731687416875168761687716878168791688016881168821688316884168851688616887168881688916890168911689216893168941689516896168971689816899169001690116902169031690416905169061690716908169091691016911169121691316914169151691616917169181691916920169211692216923169241692516926169271692816929169301693116932169331693416935169361693716938169391694016941169421694316944169451694616947169481694916950169511695216953169541695516956169571695816959169601696116962169631696416965169661696716968169691697016971169721697316974169751697616977169781697916980169811698216983169841698516986169871698816989169901699116992169931699416995169961699716998169991700017001170021700317004170051700617007170081700917010170111701217013170141701517016170171701817019170201702117022170231702417025170261702717028170291703017031170321703317034170351703617037170381703917040170411704217043170441704517046170471704817049170501705117052170531705417055170561705717058170591706017061170621706317064170651706617067170681706917070170711707217073170741707517076170771707817079170801708117082170831708417085170861708717088170891709017091170921709317094170951709617097170981709917100171011710217103171041710517106171071710817109171101711117112171131711417115171161711717118171191712017121171221712317124171251712617127171281712917130171311713217133171341713517136171371713817139171401714117142171431714417145171461714717148171491715017151171521715317154171551715617157171581715917160171611716217163171641716517166171671716817169171701717117172171731717417175171761717717178171791718017181171821718317184171851718617187171881718917190171911719217193171941719517196171971719817199172001720117202172031720417205172061720717208172091721017211172121721317214172151721617217172181721917220172211722217223172241722517226172271722817229172301723117232172331723417235172361723717238172391724017241172421724317244172451724617247172481724917250172511725217253172541725517256172571725817259172601726117262172631726417265172661726717268172691727017271172721727317274172751727617277172781727917280172811728217283172841728517286172871728817289172901729117292172931729417295172961729717298172991730017301173021730317304173051730617307173081730917310173111731217313173141731517316173171731817319173201732117322173231732417325173261732717328173291733017331173321733317334173351733617337173381733917340173411734217343173441734517346173471734817349173501735117352173531735417355173561735717358173591736017361173621736317364173651736617367173681736917370173711737217373173741737517376173771737817379173801738117382173831738417385173861738717388173891739017391173921739317394173951739617397173981739917400174011740217403174041740517406174071740817409174101741117412174131741417415174161741717418174191742017421174221742317424174251742617427174281742917430174311743217433174341743517436174371743817439174401744117442174431744417445174461744717448174491745017451174521745317454174551745617457174581745917460174611746217463174641746517466174671746817469174701747117472174731747417475174761747717478174791748017481174821748317484174851748617487174881748917490174911749217493174941749517496174971749817499175001750117502175031750417505175061750717508175091751017511175121751317514175151751617517175181751917520175211752217523175241752517526175271752817529175301753117532175331753417535175361753717538175391754017541175421754317544175451754617547175481754917550175511755217553175541755517556175571755817559175601756117562175631756417565175661756717568175691757017571175721757317574175751757617577175781757917580175811758217583175841758517586175871758817589175901759117592175931759417595175961759717598175991760017601176021760317604176051760617607176081760917610176111761217613176141761517616176171761817619176201762117622176231762417625176261762717628176291763017631176321763317634176351763617637176381763917640176411764217643176441764517646176471764817649176501765117652176531765417655176561765717658176591766017661176621766317664176651766617667176681766917670176711767217673176741767517676176771767817679176801768117682176831768417685176861768717688176891769017691176921769317694176951769617697176981769917700177011770217703177041770517706177071770817709177101771117712177131771417715177161771717718177191772017721177221772317724177251772617727177281772917730177311773217733177341773517736177371773817739177401774117742177431774417745177461774717748177491775017751177521775317754177551775617757177581775917760177611776217763177641776517766177671776817769177701777117772177731777417775177761777717778177791778017781177821778317784177851778617787177881778917790177911779217793177941779517796177971779817799178001780117802178031780417805178061780717808178091781017811178121781317814178151781617817178181781917820178211782217823178241782517826178271782817829178301783117832178331783417835178361783717838178391784017841178421784317844178451784617847178481784917850178511785217853178541785517856178571785817859178601786117862178631786417865178661786717868178691787017871178721787317874178751787617877178781787917880178811788217883178841788517886178871788817889178901789117892178931789417895178961789717898178991790017901179021790317904179051790617907179081790917910179111791217913179141791517916179171791817919179201792117922179231792417925179261792717928179291793017931179321793317934179351793617937179381793917940179411794217943179441794517946179471794817949179501795117952179531795417955179561795717958179591796017961179621796317964179651796617967179681796917970179711797217973179741797517976179771797817979179801798117982179831798417985179861798717988179891799017991179921799317994179951799617997179981799918000180011800218003180041800518006180071800818009180101801118012180131801418015180161801718018180191802018021180221802318024180251802618027180281802918030180311803218033180341803518036180371803818039180401804118042180431804418045180461804718048180491805018051180521805318054180551805618057180581805918060180611806218063180641806518066180671806818069180701807118072180731807418075180761807718078180791808018081180821808318084180851808618087180881808918090180911809218093180941809518096180971809818099181001810118102181031810418105181061810718108181091811018111181121811318114181151811618117181181811918120181211812218123181241812518126181271812818129181301813118132181331813418135181361813718138181391814018141181421814318144181451814618147181481814918150181511815218153181541815518156181571815818159181601816118162181631816418165181661816718168181691817018171181721817318174181751817618177181781817918180181811818218183181841818518186181871818818189181901819118192181931819418195181961819718198181991820018201182021820318204182051820618207182081820918210182111821218213182141821518216182171821818219182201822118222182231822418225182261822718228182291823018231182321823318234182351823618237182381823918240182411824218243182441824518246182471824818249182501825118252182531825418255182561825718258182591826018261182621826318264182651826618267182681826918270182711827218273182741827518276182771827818279182801828118282182831828418285182861828718288182891829018291182921829318294182951829618297182981829918300183011830218303183041830518306183071830818309183101831118312183131831418315183161831718318183191832018321183221832318324183251832618327183281832918330183311833218333183341833518336183371833818339183401834118342183431834418345183461834718348183491835018351183521835318354183551835618357183581835918360183611836218363183641836518366183671836818369183701837118372183731837418375183761837718378183791838018381183821838318384183851838618387183881838918390183911839218393183941839518396183971839818399184001840118402184031840418405184061840718408184091841018411184121841318414184151841618417184181841918420184211842218423184241842518426184271842818429184301843118432184331843418435184361843718438184391844018441184421844318444184451844618447184481844918450184511845218453184541845518456184571845818459184601846118462184631846418465184661846718468184691847018471184721847318474184751847618477184781847918480184811848218483184841848518486184871848818489184901849118492184931849418495184961849718498184991850018501185021850318504185051850618507185081850918510185111851218513185141851518516185171851818519185201852118522185231852418525185261852718528185291853018531185321853318534185351853618537185381853918540185411854218543185441854518546185471854818549185501855118552185531855418555185561855718558185591856018561185621856318564185651856618567185681856918570185711857218573185741857518576185771857818579185801858118582185831858418585185861858718588185891859018591185921859318594185951859618597185981859918600186011860218603186041860518606186071860818609186101861118612186131861418615186161861718618186191862018621186221862318624186251862618627186281862918630186311863218633186341863518636186371863818639186401864118642186431864418645186461864718648186491865018651186521865318654186551865618657186581865918660186611866218663186641866518666186671866818669186701867118672186731867418675186761867718678186791868018681186821868318684186851868618687186881868918690186911869218693186941869518696186971869818699187001870118702187031870418705187061870718708187091871018711187121871318714187151871618717187181871918720187211872218723187241872518726187271872818729187301873118732187331873418735187361873718738187391874018741187421874318744187451874618747187481874918750187511875218753187541875518756187571875818759187601876118762187631876418765187661876718768187691877018771187721877318774187751877618777187781877918780187811878218783187841878518786187871878818789187901879118792187931879418795187961879718798187991880018801188021880318804188051880618807188081880918810188111881218813188141881518816188171881818819188201882118822188231882418825188261882718828188291883018831188321883318834188351883618837188381883918840188411884218843188441884518846188471884818849188501885118852188531885418855188561885718858188591886018861188621886318864188651886618867188681886918870188711887218873188741887518876188771887818879188801888118882188831888418885188861888718888188891889018891188921889318894188951889618897188981889918900189011890218903189041890518906189071890818909189101891118912189131891418915189161891718918189191892018921189221892318924189251892618927189281892918930189311893218933189341893518936189371893818939189401894118942189431894418945189461894718948189491895018951189521895318954189551895618957189581895918960189611896218963189641896518966189671896818969189701897118972189731897418975189761897718978189791898018981189821898318984189851898618987189881898918990189911899218993189941899518996189971899818999190001900119002190031900419005190061900719008190091901019011190121901319014190151901619017190181901919020190211902219023190241902519026190271902819029190301903119032190331903419035190361903719038190391904019041190421904319044190451904619047190481904919050190511905219053190541905519056190571905819059190601906119062190631906419065190661906719068190691907019071190721907319074190751907619077190781907919080190811908219083190841908519086190871908819089190901909119092190931909419095190961909719098190991910019101191021910319104191051910619107191081910919110191111911219113191141911519116191171911819119191201912119122191231912419125191261912719128191291913019131191321913319134191351913619137191381913919140191411914219143191441914519146191471914819149191501915119152191531915419155191561915719158191591916019161191621916319164191651916619167191681916919170191711917219173191741917519176191771917819179191801918119182191831918419185191861918719188191891919019191191921919319194191951919619197191981919919200192011920219203192041920519206192071920819209192101921119212192131921419215192161921719218192191922019221192221922319224192251922619227192281922919230192311923219233192341923519236192371923819239192401924119242192431924419245192461924719248192491925019251192521925319254192551925619257192581925919260192611926219263192641926519266192671926819269192701927119272192731927419275192761927719278192791928019281192821928319284192851928619287192881928919290192911929219293192941929519296192971929819299193001930119302193031930419305193061930719308193091931019311193121931319314193151931619317193181931919320193211932219323193241932519326193271932819329193301933119332193331933419335193361933719338193391934019341193421934319344193451934619347193481934919350193511935219353193541935519356193571935819359193601936119362193631936419365193661936719368193691937019371193721937319374193751937619377193781937919380193811938219383193841938519386193871938819389193901939119392193931939419395193961939719398193991940019401194021940319404194051940619407194081940919410194111941219413194141941519416194171941819419194201942119422194231942419425194261942719428194291943019431194321943319434194351943619437194381943919440194411944219443194441944519446194471944819449194501945119452194531945419455194561945719458194591946019461194621946319464194651946619467194681946919470194711947219473194741947519476194771947819479194801948119482194831948419485194861948719488194891949019491194921949319494194951949619497194981949919500195011950219503195041950519506195071950819509195101951119512195131951419515195161951719518195191952019521195221952319524195251952619527195281952919530195311953219533195341953519536195371953819539195401954119542195431954419545195461954719548195491955019551195521955319554195551955619557195581955919560195611956219563195641956519566195671956819569195701957119572195731957419575195761957719578195791958019581195821958319584195851958619587195881958919590195911959219593195941959519596195971959819599196001960119602196031960419605196061960719608196091961019611196121961319614196151961619617196181961919620196211962219623196241962519626196271962819629196301963119632196331963419635196361963719638196391964019641196421964319644196451964619647196481964919650196511965219653196541965519656196571965819659196601966119662196631966419665196661966719668196691967019671196721967319674196751967619677196781967919680196811968219683196841968519686196871968819689196901969119692196931969419695196961969719698196991970019701197021970319704197051970619707197081970919710197111971219713197141971519716197171971819719197201972119722197231972419725197261972719728197291973019731197321973319734197351973619737197381973919740197411974219743197441974519746197471974819749197501975119752197531975419755197561975719758197591976019761197621976319764197651976619767197681976919770197711977219773197741977519776197771977819779197801978119782197831978419785197861978719788197891979019791197921979319794197951979619797197981979919800198011980219803198041980519806198071980819809198101981119812198131981419815198161981719818198191982019821198221982319824198251982619827198281982919830198311983219833198341983519836198371983819839198401984119842198431984419845198461984719848198491985019851198521985319854198551985619857198581985919860198611986219863198641986519866198671986819869198701987119872198731987419875198761987719878198791988019881198821988319884198851988619887198881988919890198911989219893198941989519896198971989819899199001990119902199031990419905199061990719908199091991019911199121991319914199151991619917199181991919920199211992219923199241992519926199271992819929199301993119932199331993419935199361993719938199391994019941199421994319944199451994619947199481994919950199511995219953199541995519956199571995819959199601996119962199631996419965199661996719968199691997019971199721997319974199751997619977199781997919980199811998219983199841998519986199871998819989199901999119992199931999419995199961999719998199992000020001200022000320004200052000620007200082000920010200112001220013200142001520016200172001820019200202002120022200232002420025200262002720028200292003020031200322003320034200352003620037200382003920040200412004220043200442004520046200472004820049200502005120052200532005420055200562005720058200592006020061200622006320064200652006620067200682006920070200712007220073200742007520076200772007820079200802008120082200832008420085200862008720088200892009020091200922009320094200952009620097200982009920100201012010220103201042010520106201072010820109201102011120112201132011420115201162011720118201192012020121201222012320124201252012620127201282012920130201312013220133201342013520136201372013820139201402014120142201432014420145201462014720148201492015020151201522015320154201552015620157201582015920160201612016220163201642016520166201672016820169201702017120172201732017420175201762017720178201792018020181201822018320184201852018620187201882018920190201912019220193201942019520196201972019820199202002020120202202032020420205202062020720208202092021020211202122021320214202152021620217202182021920220202212022220223202242022520226202272022820229202302023120232202332023420235202362023720238202392024020241202422024320244202452024620247202482024920250202512025220253202542025520256202572025820259202602026120262202632026420265202662026720268202692027020271202722027320274202752027620277202782027920280202812028220283202842028520286202872028820289202902029120292202932029420295202962029720298202992030020301203022030320304203052030620307203082030920310203112031220313203142031520316203172031820319203202032120322203232032420325203262032720328203292033020331203322033320334203352033620337203382033920340203412034220343203442034520346203472034820349203502035120352203532035420355203562035720358203592036020361203622036320364203652036620367203682036920370203712037220373203742037520376203772037820379203802038120382203832038420385203862038720388203892039020391203922039320394203952039620397203982039920400204012040220403204042040520406204072040820409204102041120412204132041420415204162041720418204192042020421204222042320424204252042620427204282042920430204312043220433204342043520436204372043820439204402044120442204432044420445204462044720448204492045020451204522045320454204552045620457204582045920460204612046220463204642046520466204672046820469204702047120472204732047420475204762047720478204792048020481204822048320484204852048620487204882048920490204912049220493204942049520496204972049820499205002050120502205032050420505205062050720508205092051020511205122051320514205152051620517205182051920520205212052220523205242052520526205272052820529205302053120532205332053420535205362053720538205392054020541205422054320544205452054620547205482054920550205512055220553205542055520556205572055820559205602056120562205632056420565205662056720568205692057020571205722057320574205752057620577205782057920580205812058220583205842058520586205872058820589205902059120592205932059420595205962059720598205992060020601206022060320604206052060620607206082060920610206112061220613206142061520616206172061820619206202062120622206232062420625206262062720628206292063020631206322063320634206352063620637206382063920640206412064220643206442064520646206472064820649206502065120652206532065420655206562065720658206592066020661206622066320664206652066620667206682066920670206712067220673206742067520676206772067820679206802068120682206832068420685206862068720688206892069020691206922069320694206952069620697206982069920700207012070220703207042070520706207072070820709207102071120712207132071420715207162071720718207192072020721207222072320724207252072620727207282072920730207312073220733207342073520736207372073820739207402074120742207432074420745207462074720748207492075020751207522075320754207552075620757207582075920760207612076220763207642076520766207672076820769207702077120772207732077420775207762077720778207792078020781207822078320784207852078620787207882078920790207912079220793207942079520796207972079820799208002080120802208032080420805208062080720808208092081020811208122081320814208152081620817208182081920820208212082220823208242082520826208272082820829208302083120832208332083420835208362083720838208392084020841208422084320844208452084620847208482084920850208512085220853208542085520856208572085820859208602086120862208632086420865208662086720868208692087020871208722087320874208752087620877208782087920880208812088220883208842088520886208872088820889208902089120892208932089420895208962089720898208992090020901209022090320904209052090620907209082090920910209112091220913209142091520916209172091820919209202092120922209232092420925209262092720928209292093020931209322093320934209352093620937209382093920940209412094220943209442094520946209472094820949209502095120952209532095420955209562095720958209592096020961209622096320964209652096620967209682096920970209712097220973209742097520976209772097820979209802098120982209832098420985209862098720988209892099020991209922099320994209952099620997209982099921000210012100221003210042100521006210072100821009210102101121012210132101421015210162101721018210192102021021210222102321024210252102621027210282102921030210312103221033210342103521036210372103821039210402104121042210432104421045210462104721048210492105021051210522105321054210552105621057210582105921060210612106221063210642106521066210672106821069210702107121072210732107421075210762107721078210792108021081210822108321084210852108621087210882108921090210912109221093210942109521096210972109821099211002110121102211032110421105211062110721108211092111021111211122111321114211152111621117211182111921120211212112221123211242112521126211272112821129211302113121132211332113421135211362113721138211392114021141211422114321144211452114621147211482114921150211512115221153211542115521156211572115821159211602116121162211632116421165211662116721168211692117021171211722117321174211752117621177211782117921180211812118221183211842118521186211872118821189211902119121192211932119421195211962119721198211992120021201212022120321204212052120621207212082120921210212112121221213212142121521216212172121821219212202122121222212232122421225212262122721228212292123021231212322123321234212352123621237212382123921240212412124221243212442124521246212472124821249212502125121252212532125421255212562125721258212592126021261212622126321264212652126621267212682126921270212712127221273212742127521276212772127821279212802128121282212832128421285212862128721288212892129021291212922129321294212952129621297212982129921300213012130221303213042130521306213072130821309213102131121312213132131421315213162131721318213192132021321213222132321324213252132621327213282132921330213312133221333213342133521336213372133821339213402134121342213432134421345213462134721348213492135021351213522135321354213552135621357213582135921360213612136221363213642136521366213672136821369213702137121372213732137421375213762137721378213792138021381213822138321384213852138621387213882138921390213912139221393213942139521396213972139821399214002140121402214032140421405214062140721408214092141021411214122141321414214152141621417214182141921420214212142221423214242142521426214272142821429214302143121432214332143421435214362143721438214392144021441214422144321444214452144621447214482144921450214512145221453214542145521456214572145821459214602146121462214632146421465214662146721468214692147021471214722147321474214752147621477214782147921480214812148221483214842148521486214872148821489214902149121492214932149421495214962149721498214992150021501215022150321504215052150621507215082150921510215112151221513215142151521516215172151821519215202152121522215232152421525215262152721528215292153021531215322153321534215352153621537215382153921540215412154221543215442154521546215472154821549215502155121552215532155421555215562155721558215592156021561215622156321564215652156621567215682156921570215712157221573215742157521576215772157821579215802158121582215832158421585215862158721588215892159021591215922159321594215952159621597215982159921600216012160221603216042160521606216072160821609216102161121612216132161421615216162161721618216192162021621216222162321624216252162621627216282162921630216312163221633216342163521636216372163821639216402164121642216432164421645216462164721648216492165021651216522165321654216552165621657216582165921660216612166221663216642166521666216672166821669216702167121672216732167421675216762167721678216792168021681216822168321684216852168621687216882168921690216912169221693216942169521696216972169821699217002170121702217032170421705217062170721708217092171021711217122171321714217152171621717217182171921720217212172221723217242172521726217272172821729217302173121732217332173421735217362173721738217392174021741217422174321744217452174621747217482174921750217512175221753217542175521756217572175821759217602176121762217632176421765217662176721768217692177021771217722177321774217752177621777217782177921780217812178221783217842178521786217872178821789217902179121792217932179421795217962179721798217992180021801218022180321804218052180621807218082180921810218112181221813218142181521816218172181821819218202182121822218232182421825218262182721828218292183021831218322183321834218352183621837218382183921840218412184221843218442184521846218472184821849218502185121852218532185421855218562185721858218592186021861218622186321864218652186621867218682186921870218712187221873218742187521876218772187821879218802188121882218832188421885218862188721888218892189021891218922189321894218952189621897218982189921900219012190221903219042190521906219072190821909219102191121912219132191421915219162191721918219192192021921219222192321924219252192621927219282192921930219312193221933219342193521936219372193821939219402194121942219432194421945219462194721948219492195021951219522195321954219552195621957219582195921960219612196221963219642196521966219672196821969219702197121972219732197421975219762197721978219792198021981219822198321984219852198621987219882198921990219912199221993219942199521996219972199821999220002200122002220032200422005220062200722008220092201022011220122201322014220152201622017220182201922020220212202222023220242202522026220272202822029220302203122032220332203422035220362203722038220392204022041220422204322044220452204622047220482204922050220512205222053220542205522056220572205822059220602206122062220632206422065220662206722068220692207022071220722207322074220752207622077220782207922080220812208222083220842208522086220872208822089220902209122092220932209422095220962209722098220992210022101221022210322104221052210622107221082210922110221112211222113221142211522116221172211822119221202212122122221232212422125221262212722128221292213022131221322213322134221352213622137221382213922140221412214222143221442214522146221472214822149221502215122152221532215422155221562215722158221592216022161221622216322164221652216622167221682216922170221712217222173221742217522176221772217822179221802218122182221832218422185221862218722188221892219022191221922219322194221952219622197221982219922200222012220222203222042220522206222072220822209222102221122212222132221422215222162221722218222192222022221222222222322224222252222622227222282222922230222312223222233222342223522236222372223822239222402224122242222432224422245222462224722248222492225022251222522225322254222552225622257222582225922260222612226222263222642226522266222672226822269222702227122272222732227422275222762227722278222792228022281222822228322284222852228622287222882228922290222912229222293222942229522296222972229822299223002230122302223032230422305223062230722308223092231022311223122231322314223152231622317223182231922320223212232222323223242232522326223272232822329223302233122332223332233422335223362233722338223392234022341223422234322344223452234622347223482234922350223512235222353223542235522356223572235822359223602236122362223632236422365223662236722368223692237022371223722237322374223752237622377223782237922380223812238222383223842238522386223872238822389223902239122392223932239422395223962239722398223992240022401224022240322404224052240622407224082240922410224112241222413224142241522416224172241822419224202242122422224232242422425224262242722428224292243022431224322243322434224352243622437224382243922440224412244222443224442244522446224472244822449224502245122452224532245422455224562245722458224592246022461224622246322464224652246622467224682246922470224712247222473224742247522476224772247822479224802248122482224832248422485224862248722488224892249022491224922249322494224952249622497224982249922500225012250222503225042250522506225072250822509225102251122512225132251422515225162251722518225192252022521225222252322524225252252622527225282252922530225312253222533225342253522536225372253822539225402254122542225432254422545225462254722548225492255022551225522255322554225552255622557225582255922560225612256222563225642256522566225672256822569225702257122572225732257422575225762257722578225792258022581225822258322584225852258622587225882258922590225912259222593225942259522596225972259822599226002260122602226032260422605226062260722608226092261022611226122261322614226152261622617226182261922620226212262222623226242262522626226272262822629226302263122632226332263422635226362263722638226392264022641226422264322644226452264622647226482264922650226512265222653226542265522656226572265822659226602266122662226632266422665226662266722668226692267022671226722267322674226752267622677226782267922680226812268222683226842268522686226872268822689226902269122692226932269422695226962269722698226992270022701227022270322704227052270622707227082270922710227112271222713227142271522716227172271822719227202272122722227232272422725227262272722728227292273022731227322273322734227352273622737227382273922740227412274222743227442274522746227472274822749227502275122752227532275422755227562275722758227592276022761227622276322764227652276622767227682276922770227712277222773227742277522776227772277822779227802278122782227832278422785227862278722788227892279022791227922279322794227952279622797227982279922800228012280222803228042280522806228072280822809228102281122812228132281422815228162281722818228192282022821228222282322824228252282622827228282282922830228312283222833228342283522836228372283822839228402284122842228432284422845228462284722848228492285022851228522285322854228552285622857228582285922860228612286222863228642286522866228672286822869228702287122872228732287422875228762287722878228792288022881228822288322884228852288622887228882288922890228912289222893228942289522896228972289822899229002290122902229032290422905229062290722908229092291022911229122291322914229152291622917229182291922920229212292222923229242292522926229272292822929229302293122932229332293422935229362293722938229392294022941229422294322944229452294622947229482294922950229512295222953229542295522956229572295822959229602296122962229632296422965229662296722968229692297022971229722297322974229752297622977229782297922980229812298222983229842298522986229872298822989229902299122992229932299422995229962299722998229992300023001230022300323004230052300623007230082300923010230112301223013230142301523016230172301823019230202302123022230232302423025230262302723028230292303023031230322303323034230352303623037230382303923040230412304223043230442304523046230472304823049230502305123052230532305423055230562305723058230592306023061230622306323064230652306623067230682306923070230712307223073230742307523076230772307823079230802308123082230832308423085230862308723088230892309023091230922309323094230952309623097230982309923100231012310223103231042310523106231072310823109231102311123112231132311423115231162311723118231192312023121231222312323124231252312623127231282312923130231312313223133231342313523136231372313823139231402314123142231432314423145231462314723148231492315023151231522315323154231552315623157231582315923160231612316223163231642316523166231672316823169231702317123172231732317423175231762317723178231792318023181231822318323184231852318623187231882318923190231912319223193231942319523196231972319823199232002320123202232032320423205232062320723208232092321023211232122321323214232152321623217232182321923220232212322223223232242322523226232272322823229232302323123232232332323423235232362323723238232392324023241232422324323244232452324623247232482324923250232512325223253232542325523256232572325823259232602326123262232632326423265232662326723268232692327023271232722327323274232752327623277232782327923280232812328223283232842328523286232872328823289232902329123292232932329423295232962329723298232992330023301233022330323304233052330623307233082330923310233112331223313233142331523316233172331823319233202332123322233232332423325233262332723328233292333023331233322333323334233352333623337233382333923340233412334223343233442334523346233472334823349233502335123352233532335423355233562335723358233592336023361233622336323364233652336623367233682336923370233712337223373233742337523376233772337823379233802338123382233832338423385233862338723388233892339023391233922339323394233952339623397233982339923400234012340223403234042340523406234072340823409234102341123412234132341423415234162341723418234192342023421234222342323424234252342623427234282342923430234312343223433234342343523436234372343823439234402344123442234432344423445234462344723448234492345023451234522345323454234552345623457234582345923460234612346223463234642346523466234672346823469234702347123472234732347423475234762347723478234792348023481234822348323484234852348623487234882348923490234912349223493234942349523496234972349823499235002350123502235032350423505235062350723508235092351023511235122351323514235152351623517235182351923520235212352223523235242352523526235272352823529235302353123532235332353423535235362353723538235392354023541235422354323544235452354623547235482354923550235512355223553235542355523556235572355823559235602356123562235632356423565235662356723568235692357023571235722357323574235752357623577235782357923580235812358223583235842358523586235872358823589235902359123592235932359423595235962359723598235992360023601236022360323604236052360623607236082360923610236112361223613236142361523616236172361823619236202362123622236232362423625236262362723628236292363023631236322363323634236352363623637236382363923640236412364223643236442364523646236472364823649236502365123652236532365423655236562365723658236592366023661236622366323664236652366623667236682366923670236712367223673236742367523676236772367823679236802368123682236832368423685236862368723688236892369023691236922369323694236952369623697236982369923700237012370223703237042370523706237072370823709237102371123712237132371423715237162371723718237192372023721237222372323724237252372623727237282372923730237312373223733237342373523736237372373823739237402374123742237432374423745237462374723748237492375023751237522375323754237552375623757237582375923760237612376223763237642376523766237672376823769237702377123772237732377423775237762377723778237792378023781237822378323784237852378623787237882378923790237912379223793237942379523796237972379823799238002380123802238032380423805238062380723808238092381023811238122381323814238152381623817238182381923820238212382223823238242382523826238272382823829238302383123832238332383423835238362383723838238392384023841238422384323844238452384623847238482384923850238512385223853238542385523856238572385823859238602386123862238632386423865238662386723868238692387023871238722387323874238752387623877238782387923880238812388223883238842388523886238872388823889238902389123892238932389423895238962389723898238992390023901239022390323904239052390623907239082390923910239112391223913239142391523916239172391823919239202392123922239232392423925239262392723928239292393023931239322393323934239352393623937239382393923940239412394223943239442394523946239472394823949239502395123952239532395423955239562395723958239592396023961239622396323964239652396623967239682396923970239712397223973239742397523976239772397823979239802398123982239832398423985239862398723988239892399023991239922399323994239952399623997239982399924000240012400224003240042400524006240072400824009240102401124012240132401424015240162401724018240192402024021240222402324024240252402624027240282402924030240312403224033240342403524036240372403824039240402404124042240432404424045240462404724048240492405024051240522405324054240552405624057240582405924060240612406224063240642406524066240672406824069240702407124072240732407424075240762407724078240792408024081240822408324084240852408624087240882408924090240912409224093240942409524096240972409824099241002410124102241032410424105241062410724108241092411024111241122411324114241152411624117241182411924120241212412224123241242412524126241272412824129241302413124132241332413424135241362413724138241392414024141241422414324144241452414624147241482414924150241512415224153241542415524156241572415824159241602416124162241632416424165241662416724168241692417024171241722417324174241752417624177241782417924180241812418224183241842418524186241872418824189241902419124192241932419424195241962419724198241992420024201242022420324204242052420624207242082420924210242112421224213242142421524216242172421824219242202422124222242232422424225242262422724228242292423024231242322423324234242352423624237242382423924240242412424224243242442424524246242472424824249242502425124252242532425424255242562425724258242592426024261242622426324264242652426624267242682426924270242712427224273242742427524276242772427824279242802428124282242832428424285242862428724288242892429024291242922429324294242952429624297242982429924300243012430224303243042430524306243072430824309243102431124312243132431424315243162431724318243192432024321243222432324324243252432624327243282432924330243312433224333243342433524336243372433824339243402434124342243432434424345243462434724348243492435024351243522435324354243552435624357243582435924360243612436224363243642436524366243672436824369243702437124372243732437424375243762437724378243792438024381243822438324384243852438624387243882438924390243912439224393243942439524396243972439824399244002440124402244032440424405244062440724408244092441024411244122441324414244152441624417244182441924420244212442224423244242442524426244272442824429244302443124432244332443424435244362443724438244392444024441244422444324444244452444624447244482444924450244512445224453244542445524456244572445824459244602446124462244632446424465244662446724468244692447024471244722447324474244752447624477244782447924480244812448224483244842448524486244872448824489244902449124492244932449424495244962449724498244992450024501245022450324504245052450624507245082450924510245112451224513245142451524516245172451824519245202452124522245232452424525245262452724528245292453024531245322453324534245352453624537245382453924540245412454224543245442454524546245472454824549245502455124552245532455424555245562455724558245592456024561245622456324564245652456624567245682456924570245712457224573245742457524576245772457824579245802458124582245832458424585245862458724588245892459024591245922459324594245952459624597245982459924600246012460224603246042460524606246072460824609246102461124612246132461424615246162461724618246192462024621246222462324624246252462624627246282462924630246312463224633246342463524636246372463824639246402464124642246432464424645246462464724648246492465024651246522465324654246552465624657246582465924660246612466224663246642466524666246672466824669246702467124672246732467424675246762467724678246792468024681246822468324684246852468624687246882468924690246912469224693246942469524696246972469824699247002470124702247032470424705247062470724708247092471024711247122471324714247152471624717247182471924720247212472224723247242472524726247272472824729247302473124732247332473424735247362473724738247392474024741247422474324744247452474624747247482474924750247512475224753247542475524756247572475824759247602476124762247632476424765247662476724768247692477024771247722477324774247752477624777247782477924780247812478224783247842478524786247872478824789247902479124792247932479424795247962479724798247992480024801248022480324804248052480624807248082480924810248112481224813248142481524816248172481824819248202482124822248232482424825248262482724828248292483024831248322483324834248352483624837248382483924840248412484224843248442484524846248472484824849248502485124852248532485424855248562485724858248592486024861248622486324864248652486624867248682486924870248712487224873248742487524876248772487824879248802488124882248832488424885248862488724888248892489024891248922489324894248952489624897248982489924900249012490224903249042490524906249072490824909249102491124912249132491424915249162491724918249192492024921249222492324924249252492624927249282492924930249312493224933249342493524936249372493824939249402494124942249432494424945249462494724948249492495024951249522495324954249552495624957249582495924960249612496224963249642496524966249672496824969249702497124972249732497424975249762497724978249792498024981249822498324984249852498624987249882498924990249912499224993249942499524996249972499824999250002500125002250032500425005250062500725008250092501025011250122501325014250152501625017250182501925020250212502225023250242502525026250272502825029250302503125032250332503425035250362503725038250392504025041250422504325044250452504625047250482504925050250512505225053250542505525056250572505825059250602506125062250632506425065250662506725068250692507025071250722507325074250752507625077250782507925080250812508225083250842508525086250872508825089250902509125092250932509425095250962509725098250992510025101251022510325104251052510625107251082510925110251112511225113251142511525116251172511825119251202512125122251232512425125251262512725128251292513025131251322513325134251352513625137251382513925140251412514225143251442514525146251472514825149251502515125152251532515425155251562515725158251592516025161251622516325164251652516625167251682516925170251712517225173251742517525176251772517825179251802518125182251832518425185251862518725188251892519025191251922519325194251952519625197251982519925200252012520225203252042520525206252072520825209252102521125212252132521425215252162521725218252192522025221252222522325224252252522625227252282522925230252312523225233252342523525236252372523825239252402524125242252432524425245252462524725248252492525025251252522525325254252552525625257252582525925260252612526225263252642526525266252672526825269252702527125272252732527425275252762527725278252792528025281252822528325284252852528625287252882528925290252912529225293252942529525296252972529825299253002530125302253032530425305253062530725308253092531025311253122531325314253152531625317253182531925320253212532225323253242532525326253272532825329253302533125332253332533425335253362533725338253392534025341253422534325344253452534625347253482534925350253512535225353253542535525356253572535825359253602536125362253632536425365253662536725368253692537025371253722537325374253752537625377253782537925380253812538225383253842538525386253872538825389253902539125392253932539425395253962539725398253992540025401254022540325404254052540625407254082540925410254112541225413254142541525416254172541825419254202542125422254232542425425254262542725428254292543025431254322543325434254352543625437254382543925440254412544225443254442544525446254472544825449254502545125452254532545425455254562545725458254592546025461254622546325464254652546625467254682546925470254712547225473254742547525476254772547825479254802548125482254832548425485254862548725488254892549025491254922549325494254952549625497254982549925500255012550225503255042550525506255072550825509255102551125512255132551425515255162551725518255192552025521255222552325524255252552625527255282552925530255312553225533255342553525536255372553825539255402554125542255432554425545255462554725548255492555025551255522555325554255552555625557255582555925560255612556225563255642556525566255672556825569255702557125572255732557425575255762557725578255792558025581255822558325584255852558625587255882558925590255912559225593255942559525596255972559825599256002560125602256032560425605256062560725608256092561025611256122561325614256152561625617256182561925620256212562225623256242562525626256272562825629256302563125632256332563425635256362563725638256392564025641256422564325644256452564625647256482564925650256512565225653256542565525656256572565825659256602566125662256632566425665256662566725668256692567025671256722567325674256752567625677256782567925680256812568225683256842568525686256872568825689256902569125692256932569425695256962569725698256992570025701257022570325704257052570625707257082570925710257112571225713257142571525716257172571825719257202572125722257232572425725257262572725728257292573025731257322573325734257352573625737257382573925740257412574225743257442574525746257472574825749257502575125752257532575425755257562575725758257592576025761257622576325764257652576625767257682576925770257712577225773257742577525776257772577825779257802578125782257832578425785257862578725788257892579025791257922579325794257952579625797257982579925800258012580225803258042580525806258072580825809258102581125812258132581425815258162581725818258192582025821258222582325824258252582625827258282582925830258312583225833258342583525836258372583825839258402584125842258432584425845258462584725848258492585025851258522585325854258552585625857258582585925860258612586225863258642586525866258672586825869258702587125872258732587425875258762587725878258792588025881258822588325884258852588625887258882588925890258912589225893258942589525896258972589825899259002590125902259032590425905259062590725908259092591025911259122591325914259152591625917259182591925920259212592225923259242592525926259272592825929 |
- {
- "meta": {
- "source": "远景4MW.rar (龙源如东试验场SC扩建, 2014-15 调机资料)",
- "built": "2026-09-02",
- "sensitivity": "internal — OEM机密; windcms 公开模式输出须掩数值门槛/特征频率 (client-deliverable-hide-core-parameters)",
- "iron_rules": [
- "包内参数=下装模板≠单台活值",
- "2014-15快照, 现役数值必有演化",
- "调机期跳机多为降阈值人造",
- "备份台号归属须四重对齐",
- "录波首样本未初始化为0",
- "通道存在≠信号活"
- ],
- "note": "字典表 1049 条(触发条件级) ∪ 2015 SCADA 语言表新增 246 条; brake_state_design=设计列13(88%为BrakeMode目标状态号{0,210,200,198,100,51,50}, 少数混用阶梯值; 0=不触发停机); bp_runtime_2015=交付版StatusCode.cfg的BP程序阶梯值(权威交付态)",
- "naming_conventions": {
- "provenance": "九宫口(EN15)提出, 本侧 SC-1 wbp 二进制 data-first 验证全部成立 ⇒ 跨 EN15/EN136 两代通用",
- "prefix": "SC_=告警类 / OC_=运行状态类 (SC-1 码表实测 SC_882 : OC_167)",
- "triple_derivation": "PLC符号层每码派生 _BEDISABLED(已被屏蔽) / _TODISABLE(待屏蔽) 布尔量 — SC-1 wbp 实测各 1190 条, 基码 2392; 派生量仅在 PLC 符号层, 不在状态码表层",
- "dual_case": "全大写编译版 + 驼峰源码版并存 (SC-1 wbp 实测 3584 : 1188)",
- "use": "分析'某码为何不报'时先查其 _BEDISABLED 态 — 屏蔽机制是 OEM 内建, 非现场改码"
- },
- "transferability_measured_2026_09_02": {
- "benchmark": "王家湾(远景EN87 1.5MW陆上DFIG) 490个实际码 × 714万事件",
- "sc1_coverage": "223/490=45.5% 码 / 61.8% 事件量",
- "en15_coverage": "411/490=83.9% / 77.1% (EN15包才是1.5-2.2MW陆上场的对口参照)",
- "marginal_gain": "SC-1 相对 EN15 的边际增量仅 3 码(04_16_001/002/010), 逐条核对**全是同号异义 false friend**(现场'叶片气动性能警告'被SC-1解成'自检1超时')",
- "shared_subset": "共有220码中208个变量名逐字一致(94.5%) ⇒ '同族'成立, 但**号段占用跨代会被重新分配**",
- "**rule**": "SC-1 字典只能用于与 EN15 交叉一致的码; **只在 SC-1 里出现的码一律判 INSUFFICIENT, 禁直接采信**"
- },
- "wind_sensor_family_crosscheck_2026_09_02": {
- "method": "与EN15(九宫口)风传感码族双向对拍, data-first 实读双方字典",
- "en15_has_sc1_lacks": [
- "02_11_022 SC_PwrCrvAbnormalbyFrozenWindSensor (**风速仪冻结致功率曲线异常的OEM原生归因码** — 欠发归因线直接闸门)",
- "02_11_114 SC_WindSpeedSensorSuspicious",
- "02_11_130 SC_ConstantSignalVaneRecoveryTimeout(自恢复超时,手动复位)",
- "02_11_131 SC_RepeatFaultConstantSignalVane(重复出现升级)"
- ],
- "en15_escalation_chain": "瞬时001(自复位) → 自恢复超时130(手动) → 重复出现131(手动) 三级链; SC-1 侧无 130/131 ⇒ **EN15 该族更成熟**",
- "sc1_has_en15_likely_lacks": [
- "04_09_035 SC_WindIrisData_NotValid + 036 OC_WindIrisForControl (**激光雷达测风**, 4MW海上专属)",
- "04_09_060 切换至备用风速仪 (**冗余风速仪自动切换**)",
- "04_09_005/006 风向标与风速仪**各自独立**的加热器MCB码"
- ],
- "severity_calibration_agrees": "双方一致: 风向标冻结=BP51停机级(rt170); 风速仪异常=提示级(rt40/BP0)",
- "reusable_discriminator": "**OEM原生检测器零命中 = 强负证据**, 但成立前提须先核两条: ①监测窗口时长占比(低风免监测闸门 OC_NoMonitoringWindSensors 不能吃掉大部分时间) ②屏蔽位状态(_BEDISABLED/_TODISABLE)。两条都核过后, 若仍在10min面判'风向标冻结', 必须解释为何OEM的100ms级判据从未命中。 [王家湾W08 2023全年实证: 冻结族零命中, 免监测仅占25.6%⇒窗口74.4%开着, (b)分支已排除]",
- "sc1_trigger_reference": "02_11_009 触发条件原文含 100ms 前后风向比对 (gbDetectNew100ms=1 AND iLastDirVane1Relative_100ms = iCurrDirVane1Relative_100ms) AND OC_NoMonitoringWindSensors=False"
- },
- "known_defects": [
- "**04_09_033 变量名与中文标签不符**: name=SC_FaultAI_Nacelle**WindSpeed**(风速) 但 cn='Thies**风向标**故障'(风向) — 同 param_dict InterDE/InterNDE 一类的标签错乱, 引用前须按物理归属核实 (本包已知第3例)"
- ],
- "water_cooling_reference_frame_rosetta": {
- "problem": "同一物理测点存在**三套命名参照系**, 跨代混用会把'换热器堵塞'与'泵性能衰减'结论对调",
- "three_frames": {
- "变量名(两代一致)": "部件视角 — Inlet=冷却液进入部件, Outlet=离开部件",
- "SC-1中文": "供水/回水 (与变量名一致; 另有 入口/出口 亦为部件视角)",
- "EN15中文(九宫口实测29条)": "**泵视角** — CoolInletTemp↔'水冷泵出口温度', CoolOutletTemp↔'水冷泵入口温度', 100%成对反向"
- },
- "rosetta": "**泵出口 ≡ 供水 ≡ 部件Inlet ≡ 冷侧**; **泵入口 ≡ 回水 ≡ 部件Outlet ≡ 热侧** — 三套说法描述同一点, EN15中文非缺陷而是泵视角, 但与变量名反向",
- "physical_anchor_sc1": "⚠ **原锚已撤回** (GenCooling 90/125 五列全同=模板默认, 与EN15相同系同源模板非独立验证, 用作跨代锚构成循环论证)",
- "sc1_scan_result": "SC-1 侧 75 条含 Inlet/Outlet 的码: **反向 0 / 一致 43 / 中文无进出口词 32**(水冷族用供水/回水或'压力侧/吸入侧') ⇒ SC-1 无 EN15 那种反向, 可作参照系基准",
- "cross_gen_warning": "02_08_118~131 与 03_05_043~058 两族**码号与变量名跨代完全相同**, 仅中文参照系不同 ⇒ 看起来最安全的交叉引用恰恰最危险",
- "anchor_v2_water_circuit": {
- "caveat": "空冷(GenCooling 90/125℃)与水冷(WCSGEN 45/50℃)是**两条独立回路**, 量级差一倍, 锚不可混用 [九宫口指出]",
- "structural_anchor": "**结构不对称, 不依赖数值**: SC-1 水冷 Inlet 侧配 High阈(3.5/4 bar)+Low阈(0.8/0.5), Outlet 侧**只有 Low阈**(0.4/0.2) ⇒ 设计者只给 Inlet 配过压保护 = Inlet 为高压侧 = 泵出口/供水 【此条仍成立: 结构不对称是编码约定层面的证据, 不依赖数值 provenance】",
- "tuned_evidence": "⚠ **降级**: 原称 PAR_rWCSCVTInletPreHigh1/2 '被实调过(3.5/4→4.5/5)可作实机证据' — 经复核该差异同属 default↔golden_kk 跨18个月版本差, **不足以证明现场调整**, 降为'跨版本差异'。**本条不再作实机锚**",
- "temp_corroboration": "WCSGEN InletTempHigh1/2=45/50 vs OutletTempHigh=50 ⇒ Inlet 阈更低=冷侧; 与压力侧独立同指",
- "cross_gen_agreement": "EN15 侧 Inlet PreLow 2/0.5 vs Outlet PreLow 1/0.2 同向 [九宫口]",
- "hardware_caveat": "⚠ 九宫口实测其场 `发电机/变频器冷却方式=空冷`, 其 WCS 46条水冷参数为**硬件不存在的空置模板** ⇒ 水冷锚在无水冷硬件的场一律禁引; SC-1(4MW海上)是否真有水冷硬件, repo内无配置特征字段可证, 原包在BIG(TCC锁) ⇒ **待验**"
- },
- "reference_frame_free_criterion": {
- "params": "PAR_rGenWaterCoolInOutPressureDiffLow=0.4 / High=3 (bar); CVT 侧同值",
- "value": "**压差是标量差, 与 Inlet/Outlet 谁是谁无关** ⇒ 做水冷诊断优先用压差, 直接绕开参照系陷阱。Δp>3=回路阻力过大(堵塞/滤网脏); Δp<0.4=泵性能不足/旁路短路",
- "provenance": "五列全同=模板默认值, **数值需现场校准**; 但'压差是正确判据'这个方法论信息不受影响 [九宫口提出]"
- },
- "sc1_two_vendors": "SC-1 侧水冷有**两家供应商**: 高澜(GL/WCS前缀, GEN阈45/50℃) 与 众业达(WCSOf前缀, 阈55℃) — 阈值不同, 分析前须先判该台是哪家"
- },
- "provenance": {
- "kind": "OEM 调试包解析产物 (生成器/模板层), **非整机回读**",
- "evidence_grade": "**模板值** — 按三级标签, 本包**无一条够得上'实机回读'**",
- "not": "不是任何一台机的实际设定; '一致/闭环/自洽'指模板与模板 或 模板与实测数据 之间的一致",
- "usage": "证据强度=模板值 × 用途: 作分组依据/设计意图合格; 作**阈值锚不合格**",
- "see": "README '证据规矩' 节",
- "stamped": "2026-09-02 结构污染审计补标",
- "extra": "状态码语义为设计定义; 对陆上1.5MW场实测可迁性仅45.5%, SC-1独有码判INSUFFICIENT"
- }
- },
- "codes": {
- "03_05_001": {
- "subsystem": "ConverterContainer",
- "name": "SC_NoSignalForReadyToOperate",
- "en": "Converter is not ready to operate",
- "cn": "变频器没有做好运行准备",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "3",
- "repeat_period": "T#1h",
- "trigger_en": "The current value for generator speed exceeds the value 1100.0 RPM and there is no signal from the converter (via serial communication) for \"ReadyToOperate\".(grGenSpeedForProcess_1sec > 1100.0 AND diConverter_ReadyToOperate=0)",
- "trigger_cn": "发电机转速高于1100转/分,且有变频器没有做好运行准备的信号。(grGenSpeedForProcess_1sec > 1100.0 AND diConverter_ReadyToOperate=0)",
- "set_delay": "PAR_tTimeOutReadyToOperateOK",
- "yp": "0",
- "reset_en": "The current value for generator falls below the value 1100.0 RPM or there is a signal from the converter (via serial communication) for \"ReadyToOperate\".(grGenSpeedForProcess_1sec <= 1100.0 OR diConverter_ReadyToOperate=1)",
- "reset_cn": "发电机转速不高于1100转/分,或收到变频器做好运行准备的信号。(grGenSpeedForProcess_1sec <= 1100.0 OR diConverter_ReadyToOperate=1)",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "03_05_002": {
- "subsystem": "ConverterContainer",
- "name": "SC_RepFaultNoSignalReadyToOperate",
- "en": "The fault, converter is not ready to operate, has repeated",
- "cn": "变频器没有做好运行准备的故障重复出现",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The statuscode \" SC_NoSignalForReadyToOperate\" in a given time periode becomes more times TRUE than maximum allowed.(gbRepeat_03_05_001=1)",
- "trigger_cn": "变频器没有做好运行准备的故障重复出现。(gbRepeat_03_05_001=1)",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "The statuscode \" SC_NoSignalForReadyToOperate\" in a given time periode becomes less times TRUE than maximum allowed.(gbRepeat_03_05_001=0)",
- "reset_cn": "变频器没有做好运行准备的故障没有重复出现。(gbRepeat_03_05_001=0)",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "03_05_003": {
- "subsystem": "ConverterContainer",
- "name": "SC_NoSignalForParallelOperation",
- "en": "The time for converter for cut-in is too long",
- "cn": "变频器接入电网时间过长",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "3",
- "repeat_period": "T#1h",
- "trigger_en": "The command for \"LoadRequirement\" is TRUE, but there is no signal from the converter (via serial communication) for \"GridConnected \".(dqConverter_LoadRequirement=1 AND diConverter_GridConnected=0)",
- "trigger_cn": "LoadRequirement命令为真,变频器没有信号过来。(dqConverter_LoadRequirement=1 AND diConverter_GridConnected=0)",
- "set_delay": "PAR_tTimeOutParallelOperationOK",
- "yp": "0",
- "reset_en": "The command for \"LoadRequirement\" is FALSE, or there is a signal from the converter (via serial communication) for \"GridConnected \".(dqConverter_LoadRequirement=0 OR diConverter_GridConnected=1)",
- "reset_cn": "LoadRequirement命令为假,或变频器有信号过来。(dqConverter_LoadRequirement=0 OR diConverter_GridConnected=1)",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "03_05_004": {
- "subsystem": "ConverterContainer",
- "name": "SC_RepFaultNoSignalParallelOperation",
- "en": "The fault of converter long time cutin has repeated",
- "cn": "变频器接入电网时间过长故障重复出现",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The statuscode \" SC_NoSignalForParallelOperation\" in a given time periode becomes more times TRUE than maximum allowed.(gbRepeat_03_05_003=1)",
- "trigger_cn": "变频器接入电网时间过长故障重复出现高于最大值。(gbRepeat_03_05_003=1)",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "The statuscode \" SC_NoSignalForParallelOperation\" in a given time periode becomes less times TRUE than maximum allowed.(gbRepeat_03_05_003=0)",
- "reset_cn": "变频器接入电网时间过长故障重复出现在最大值内。(gbRepeat_03_05_003=0)",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "03_05_005": {
- "subsystem": "ConverterContainer",
- "name": "SC_FaultInverter_CollectiveInformation",
- "en": "Converter has collective alarm",
- "cn": "变频器多种警告",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "3",
- "repeat_period": "T#1h",
- "trigger_en": "The signal from the converter (via serial communication) for \"SumInfoAlarm\" becomes TRUE.(diConverter_SumInfoAlarm=1 AND diConverter_HeatingMode=0 AND gbDI_TowerConverterHeatingActive=0 AND TP_Block.Q=0) TP_Block.Q rises to True when CB check start and lasst for PAR_tCBCheckBlockConverterError.",
- "trigger_cn": "变频器不处于暖机模式,且从变频器过来的\"SumInfoAlarm\"信号变true。当变频器CB开始闭合时,TP_Block.Q变为1,持续PAR_tCBCheckBlockConverterError后变为0.(diConverter_SumInfoAlarm=1 AND diConverter_HeatingMode=0 AND gbDI_TowerConverterHeatingActive=0 AND TP_Block.Q=0)",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "The signal from the converter (via serial communication) for \"SumInfoAlarm\" becomes FALSE.(diConverter_SumInfoAlarm=0 OR diConverter_HeatingMode=1 OR gbDI_TowerConverterHeatingActive=1 OR TP_Block.Q=1) TP_Block.Q rises to True when CB check start and lasst for PAR_tCBCheckBlockConverterError.",
- "reset_cn": "变频器进入暖机模式或从变频器过来的\"SumInfoAlarm\"信号是FALSE。当变频器CB开始闭合时,TP_Block.Q变为1,持续PAR_tCBCheckBlockConverterError后变为0.。(diConverter_SumInfoAlarm=0 OR diConverter_HeatingMode=1 OR gbDI_TowerConverterHeatingActive=1 OR TP_Block.Q=1)",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "100"
- },
- "03_05_027": {
- "subsystem": "ConverterContainer",
- "name": "SC_ConverterCircuitBrakerTripped",
- "en": "Circuit breaker has tripped",
- "cn": "断路器断开",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The corresponding signal from the converter (via serial communication) for \"CircuitBrakerTripped\" becomes TRUE or the corresponding digital inputs is FALSE.(diConverter_CircuitBrakerTripped=1 OR gbDI_TowerConverterMCBTripped=0)",
- "trigger_cn": "来自于变频器的\"CircuitBrakerTripped\"信号变为TRUE或相关的数字输入变为FALSE。(diConverter_CircuitBrakerTripped=1 OR gbDI_TowerConverterMCBTripped=0)",
- "set_delay": "T#50ms",
- "yp": "0",
- "reset_en": "The corresponding signal from the converter (via serial communication) for \"CircuitBrakerTripped\" becomes FALSE and the corresponding digital inputs is TRUE.(diConverter_CircuitBrakerTripped=0 AND gbDI_TowerConverterMCBTripped=1)",
- "reset_cn": "来自于变频器的\"CircuitBrakerTripped\"信号变为FALSE且相关的数字输入变为TRUE。(diConverter_CircuitBrakerTripped=0 AND gbDI_TowerConverterMCBTripped=1)",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "100"
- },
- "03_05_050": {
- "subsystem": "ConverterContainer",
- "name": "SC_CutInTooFrequently_20m_5",
- "en": "Cut-in action occurs too frequently",
- "cn": "接入电网动作过于频繁",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "When cut-in action occurs too frequently more than or eaque to 5 times cut-in within 20 minutes.(ABS(guiCutInCounter - uiStartCounter) >= CON_uiCounter)",
- "trigger_cn": "切入动作过于频繁,在20分钟内大于或等于5次。_x000D_ (ABS(guiCutInCounter - uiStartCounter) >= CON_uiCounter)",
- "set_delay": "T#60s",
- "yp": "0",
- "reset_en": "When cut-in action occurs less than 5 times cut-in within 20 minutes.(ABS(guiCutInCounter - uiStartCounter) < CON_uiCounter)",
- "reset_cn": "切入动作过于频繁,在20分钟内小于5次。(ABS(guiCutInCounter - uiStartCounter) < CON_uiCounter)",
- "reset_mode": "M",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "03_05_081": {
- "subsystem": "ConverterContainer",
- "name": "SC_GridFailureByConverter",
- "en": "Grid has failure from converter",
- "cn": "变频器报告电网故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Grid voltage is within range in LVRT, but Grid has failure from converter.(diConverter_GridFailure=1 AND diConverter_LowVoltageForRideThrough=0)",
- "trigger_cn": "LVRT模式下电网电压没有超限,但变频器报告电网故障。(diConverter_GridFailure=1 AND diConverter_LowVoltageForRideThrough=0)",
- "set_delay": "T#0s",
- "yp": "100",
- "reset_en": "Grid voltage is out of range in LVRT, or Grid has no failure from converter.(diConverter_GridFailure=0 OR diConverter_LowVoltageForRideThrough=1)",
- "reset_cn": "LVRT模式下电网电压超限,或变频器没有报告电网故障。(diConverter_GridFailure=0 OR diConverter_LowVoltageForRideThrough=1)",
- "reset_mode": "M",
- "type": "A",
- "alarm": "True",
- "level": "180-电网故障",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "180",
- "brake_state_design": "100"
- },
- "03_05_101": {
- "subsystem": "ConverterContainer",
- "name": "OC_ConverterReadyToOperate",
- "en": "Converter is ready to operate",
- "cn": "变频器做好运行准备",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Converter is ready to operate(the corresponding signal from the converter becomes TRUE).(diConverter_ReadyToOperate=1)",
- "trigger_cn": "变频器做好运行准备(相应的信号为true)。(diConverter_ReadyToOperate=1)",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "Converter is not ready to operate(the corresponding signal from the converter becomes FALSE).(diConverter_ReadyToOperate=0)",
- "reset_cn": "变频器没有做好运行准备(相应的信号为FALSE)。(diConverter_ReadyToOperate=0)",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "03_05_102": {
- "subsystem": "ConverterContainer",
- "name": "OC_ConverterGridConnected",
- "en": "Grid is connected from converter",
- "cn": "变频器报告电网已接入",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Grid is connected from converter(the corresponding signal from the converter becomes TRUE).(diConverter_GridConnected=1)",
- "trigger_cn": "变频器报告电网已接入(相应的信号为true)。(diConverter_GridConnected=1)",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "Grid is not connected from converter(the corresponding signal from the converter becomes FALSE).(diConverter_GridConnected=0)",
- "reset_cn": "变频器报告电网未接入(相应的信号为FALSE)。(diConverter_GridConnected=0)",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "79-无限制发电",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "79",
- "brake_state_design": "0"
- },
- "03_05_103": {
- "subsystem": "ConverterContainer",
- "name": "OC_ConverterReadyToSwitchON",
- "en": "Converter is ready to cut in",
- "cn": "变频器做好并网准备",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Converter is ready to cut in(the corresponding signal from the converter becomes TRUE).(diConverter_ReadyToCutIn=1)",
- "trigger_cn": "变频器做好并网准备(相应的信号为true)。(diConverter_ReadyToCutIn=1)",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "Converter is not ready to cut in(the corresponding signal from the converter becomes FALSE).(diConverter_ReadyToCutIn=0)",
- "reset_cn": "变频器没有做好并网准备(相应的信号为FALSE)。(diConverter_ReadyToCutIn=0)",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "03_05_104": {
- "subsystem": "ConverterContainer",
- "name": "OC_ConverterCircuitBrakerActive",
- "en": "Circuit breaker is active from converter",
- "cn": "变频器报告断路器断开",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Circuit breaker is active from converter(the corresponding signal from the converter becomes TRUE).(diConverter_CircuitBrakerActive=1)",
- "trigger_cn": "变频器报告断路器断开(相应的信号为true)。(diConverter_CircuitBrakerActive=1)",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "Circuit breaker is not active from converter(the corresponding signal from the converter becomes TRUE).(diConverter_CircuitBrakerActive=0)",
- "reset_cn": "变频器报告断路器没有断开(相应的信号为FALSE)。(diConverter_CircuitBrakerActive=0)",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "03_06_014": {
- "subsystem": "ConverterContainer",
- "name": "SC_InterruptionCANbusConverter",
- "en": "CAN communication with converter has fault",
- "cn": "与变频器CAN通讯故障",
- "powerup_delay": "T#10s",
- "disable_level": "100",
- "repeat_n": "3",
- "repeat_period": "T#60s",
- "trigger_en": "The CANbus communication fault was detected because of heartbeat signal lost. TP_Block.Q rises to True when CB check start and lasts for PAR_tCBCheckBlockConverterError. (gbCANConverterDisturbed=1) AND diConverter_HeatingMode=0 AND gbDI_TowerConverterHeatingActive=0 AND TP_Block.Q=0",
- "trigger_cn": "当变频器CB开始闭合时,TP_Block.Q变为1,持续PAR_tCBCheckBlockConverterError后变为0.变频器不处于暖机模式,且与变频器CAN通讯心跳信号丢失。(gbCANConverterDisturbed=1) AND diConverter_HeatingMode=0 AND gbDI_TowerConverterHeatingActive=0 AND TP_Block.Q=0",
- "set_delay": "T#15ms",
- "yp": "0",
- "reset_en": "The CANbus heartbeat signal comes back. TP_Block.Q rises to True when CB check start and lasts for PAR_tCBCheckBlockConverterError. (gbCANConverterDisturbed=0) AND diConverter_HeatingMode=1 OR gbDI_TowerConverterHeatingActive=1 OR TP_Block.Q=1",
- "reset_cn": "当变频器CB开始闭合时,TP_Block.Q变为1,持续PAR_tCBCheckBlockConverterError后变为0.变频器进入暖机模式,或变频器CAN通讯无故障。(gbCANConverterDisturbed=0) AND diConverter_HeatingMode=1 OR gbDI_TowerConverterHeatingActive=1 OR TP_Block.Q=1",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "100"
- },
- "04_08_001": {
- "subsystem": "CoolingSystem",
- "name": "OC_CS_Pump1LowON",
- "en": "The cooling water circulation pump 1 low speed generator is switched on",
- "cn": "冷却系统循环泵1低速电机启动",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "gbDQ_CS_Pump1Low",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_08_002": {
- "subsystem": "CoolingSystem",
- "name": "OC_CS_Pump2LowON",
- "en": "The cooling water circulation pump 2 low speed generator is switched on",
- "cn": "冷却系统循环泵2低速电机启动",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "gbDQ_CS_Pump2Low",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_08_003": {
- "subsystem": "CoolingSystem",
- "name": "OC_CS_Pump1HighON",
- "en": "The cooling water circulation pump 1 high speed generator is switched on",
- "cn": "冷却系统循环泵1高速电机启动",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "gbDQ_CS_Pump1High",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_08_004": {
- "subsystem": "CoolingSystem",
- "name": "OC_CS_Pump2HighON",
- "en": "The cooling water circulation pump 2 high speed generator is switched on",
- "cn": "冷却系统循环泵2高速电机启动",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "gbDQ_CS_Pump2High",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_08_005": {
- "subsystem": "CoolingSystem",
- "name": "SC_CS_Pump1LowControlManualMode",
- "en": "Manual control of cooling water circulation pump1 low speed generator is enabled",
- "cn": "冷却系统循环泵1低速电机手动模式开启",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "RemCmdACK_bEnableCS_Pump1LowManualControlMode",
- "trigger_cn": "",
- "set_delay": "T#50ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_08_006": {
- "subsystem": "CoolingSystem",
- "name": "SC_CS_Pump2LowControlManualMode",
- "en": "Manual control of cooling water circulation pump2 low speed generator is enabled",
- "cn": "冷却系统循环泵2低速电机手动模式开启",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "RemCmdACK_bEnableCS_Pump2LowManualControlMode",
- "trigger_cn": "",
- "set_delay": "T#50ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_08_007": {
- "subsystem": "CoolingSystem",
- "name": "SC_CS_Pump1LowControlForcelMode",
- "en": "Force control of cooling water circulation pump1 Low speed generator is enabled",
- "cn": "冷却系统循环泵1低速电机强制模式开启",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "RemCmdACK_bEnableCS_Pump1LowForceControlMode",
- "trigger_cn": "",
- "set_delay": "T#50ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_08_008": {
- "subsystem": "CoolingSystem",
- "name": "SC_CS_Pump2LowControlForcelMode",
- "en": "Force control of cooling water circulation pump2 Low speed generator is enabled",
- "cn": "冷却系统循环泵2低速电机强制模式开启",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "RemCmdACK_bEnableCS_Pump2LowForceControlMode",
- "trigger_cn": "",
- "set_delay": "T#50ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_08_009": {
- "subsystem": "CoolingSystem",
- "name": "SC_CS_Pump1HighControlManualMode",
- "en": "Manual control of cooling water circulation pump1 High speed generator is enabled",
- "cn": "冷却系统循环泵1高速电机手动模式开启",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "RemCmdACK_bEnableCS_Pump1HighManualControlMode",
- "trigger_cn": "",
- "set_delay": "T#50ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_08_010": {
- "subsystem": "CoolingSystem",
- "name": "SC_CS_Pump2HighControlManualMode",
- "en": "Manual control of cooling water circulation pump2 High speed generator is enabled",
- "cn": "冷却系统循环泵2高速电机手动模式开启",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "RemCmdACK_bEnableCS_Pump2HighManualControlMode",
- "trigger_cn": "",
- "set_delay": "T#50ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_08_011": {
- "subsystem": "CoolingSystem",
- "name": "SC_CS_Pump1HighControlForcelMode",
- "en": "Force control of cooling water circulation pump1 High speed generator is enabled",
- "cn": "冷却系统循环泵1高速电机强制模式开启",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "RemCmdACK_bEnableCS_Pump1HighForceControlMode",
- "trigger_cn": "",
- "set_delay": "T#50ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_08_012": {
- "subsystem": "CoolingSystem",
- "name": "SC_CS_Pump2HighControlForcelMode",
- "en": "Force control of cooling water circulation pump2 High speed generator is enabled",
- "cn": "冷却系统循环泵2高速电机强制模式开启",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "RemCmdACK_bEnableCS_Pump2HighForceControlMode",
- "trigger_cn": "",
- "set_delay": "T#50ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_08_013": {
- "subsystem": "CoolingSystem",
- "name": "SC_CS_GENOutletTempHighWarining",
- "en": "The generator outlet temperature is high",
- "cn": "冷却系统发电机出口温度过高",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "grCS_GENOutletTemp>PAR_rTemp_CS_GENOutletHigh",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_08_014": {
- "subsystem": "CoolingSystem",
- "name": "SC_CS_PreLowWaringing",
- "en": "The cooling water pressure is low",
- "cn": "冷却系统(入口或出口)压力低报警",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "grCS_PumpInletPressure<PAR_rPre_CS_LowWarning OR grCS_PumpOutletPressure<PAR_rPre_CS_LowWarning",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_08_015": {
- "subsystem": "CoolingSystem",
- "name": "SC_CS_PreLowError",
- "en": "The cooling water pressure is too low",
- "cn": "冷却系统(入口或出口)压力低故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "grCS_PumpInletPressure<PAR_rPre_CS_LowError OR grCS_PumpOutletPressure<PAR_rPre_CS_LowError",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_08_016": {
- "subsystem": "CoolingSystem",
- "name": "SC_CS_PumpOutputTempSensorFault",
- "en": "The PT100 of water pump outlet has fault",
- "cn": "冷却系统泵出口PT100故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "gbStateAI_CS_PumpOutletTemp",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_08_017": {
- "subsystem": "CoolingSystem",
- "name": "SC_CS_GENOutletTempSensorFault",
- "en": "The PT100 of water generator outlet has fault",
- "cn": "冷却系统发电机出口PT100故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "gbStateAI_CS_GENOutletTemp",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_08_018": {
- "subsystem": "CoolingSystem",
- "name": "SC_CS_GBXOutletTempSensorFault",
- "en": "The PT100 of water gearbox outlet has fault",
- "cn": "冷却系统齿轮箱出口PT100故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "gbStateAI_CS_GBXOutletTemp",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "brake_state_design": "0"
- },
- "04_08_019": {
- "subsystem": "CoolingSystem",
- "name": "SC_CS_PumpOutletPreSensorFault",
- "en": "The pressure sensor of cooling water circulation pump pressure side has fault",
- "cn": "冷却系统循环泵压力侧压力传感器故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "gbStateAI_CS_PumpInletPressure",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_08_020": {
- "subsystem": "CoolingSystem",
- "name": "SC_CS_PumpInletPreSensorFault",
- "en": "The pressure sensor of cooling water circulation pump suction side has fault",
- "cn": "冷却系统循环泵吸入侧压力传感器故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "gbStateAI_CS_PumpOutletPressure",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_08_021": {
- "subsystem": "CoolingSystem",
- "name": "SC_CS_Pump1LowOverload",
- "en": "The cooling circulation pump 1 low overload has been activated",
- "cn": "水冷循环泵1低速热继触发",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "gbDI_CS_Pump1Low_OverloadOK=0",
- "trigger_cn": "",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_08_022": {
- "subsystem": "CoolingSystem",
- "name": "SC_CS_Pump2LowOverload",
- "en": "The cooling circulation pump 2 low overload has been activated",
- "cn": "水冷循环泵2低速热继触发",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "gbDI_CS_Pump2Low_OverloadOK=0",
- "trigger_cn": "",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_08_023": {
- "subsystem": "CoolingSystem",
- "name": "SC_CS_Pump1HighOverload",
- "en": "The cooling circulation pump 1 high overload has been activated",
- "cn": "水冷循环泵1高速热继触发",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "gbDI_CS_Pump1High_OverloadOK=0",
- "trigger_cn": "",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_08_024": {
- "subsystem": "CoolingSystem",
- "name": "SC_CS_Pump2HighOverload",
- "en": "The cooling circulation pump 2 high overload has been activated",
- "cn": "水冷循环泵2高速热继触发",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "gbDI_CS_Pump2High_OverloadOK=0",
- "trigger_cn": "",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_08_025": {
- "subsystem": "CoolingSystem",
- "name": "SC_CS_Pump1MCB",
- "en": "The cooling circulation pump 1 MCB has been activated",
- "cn": "水冷循环泵1空开跳开",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "gbDI_CS_Pump1MCBOK=0",
- "trigger_cn": "",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_08_026": {
- "subsystem": "CoolingSystem",
- "name": "SC_CS_Pump2MCB",
- "en": "The cooling circulation pump 2 MCB has been activated",
- "cn": "水冷循环泵2空开跳开",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "gbDI_CS_Pump2MCBOK=0",
- "trigger_cn": "",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_08_027": {
- "subsystem": "CoolingSystem",
- "name": "SC_CS_GBXOutletTempHighWarining",
- "en": "The gear box outlet temperature is high",
- "cn": "冷却系统齿轮箱出口温度过高",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_13_003": {
- "subsystem": "CoreController",
- "name": "OC_AsymProxOffsetCalcRequired",
- "en": "sensors of individual Pitch Control need auto-caculation.",
- "cn": "独立变桨需要自动校准",
- "powerup_delay": "T#30s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "A",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_13_004": {
- "subsystem": "CoreController",
- "name": "SC_AsymSensorError",
- "en": "Individual pitch system faults",
- "cn": "独立变桨控制系统故障",
- "powerup_delay": "T#30s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "A",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_13_005": {
- "subsystem": "CoreController",
- "name": "OC_AsymScaleDeltaFault",
- "en": "scale fualts of individual pitch control sensors",
- "cn": "独立变桨控制系统标定故障",
- "powerup_delay": "T#30s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "A",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "03_06_032": {
- "subsystem": "CoreController",
- "name": "SC_NoCOM_C_Task",
- "en": "communication faults with core controller",
- "cn": "与核心控制器通讯失败",
- "powerup_delay": "T#30s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "When the communication with the referred external C-Task is interrupted or seems to be disturbed (only monitored when using Envision CoreController).(giENVin_HeartBeat = iENVin_HeartBeat_old AND PAR_bActivatePitchAndTorqueExternal)",
- "trigger_cn": "与外部软件控制器通讯失败(当使用核心控制器时)。giENVin_HeartBeat =iENVin_HeartBeat_old)AND PAR_bActivatePitchAndTorqueExternal",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "When the communication with the referred external C-Task is OK or the external controller is not activated).(giENVin_HeartBeat ≠ iENVin_HeartBeat_old OR SC_External_C_ControllerAktivated=0)",
- "reset_cn": "与外部软件控制器通讯正常或外部监测控制器没有被激活。(giENVin_HeartBeat ≠ iENVin_HeartBeat_old OR SC_External_C_ControllerAktivated=0)",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "200"
- },
- "03_06_118": {
- "subsystem": "DataFlow",
- "name": "SC_PoweringUp",
- "en": "turbine is powering up",
- "cn": "主控制器上电初始化",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "230-上电初始化",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "230",
- "brake_state_design": "0"
- },
- "03_06_132": {
- "subsystem": "DataFlow",
- "name": "SC_Init_Done",
- "en": "All initialization is finished",
- "cn": "初始化全部完成",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "gbINIT_MAIN_InitializationFinished",
- "trigger_cn": "初始化全部完成",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "All initialization is not finished.(gbINIT_MAIN_InitializationFinished=0)",
- "reset_cn": "初始化没有全部完成。(gbINIT_MAIN_InitializationFinished=0)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "20-无原因待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "20",
- "brake_state_design": "0"
- },
- "03_09_104": {
- "subsystem": "DataFlow",
- "name": "OC_PLCPowerUpDelayElapsed",
- "en": "The first cycle of PLC main task is done",
- "cn": "PLC主任务重启后第一个执行周期完成",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The first cycle of PLC main task is done.(gbPLC_FirstCycleDone=1)",
- "trigger_cn": "PLC主任务重启后第一个执行周期完成。(gbPLC_FirstCycleDone=1)",
- "set_delay": "T#10s",
- "yp": "0",
- "reset_en": "The first cycle of PLC main task is not done.(gbPLC_FirstCycleDone=0)",
- "reset_cn": "PLC主任务重启后第一个执行周期没有完成。(gbPLC_FirstCycleDone=0)",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "02_02_060": {
- "subsystem": "Drivetrain",
- "name": "SC_FaultInputPT100_RotorBearingA",
- "en": "PT100 for rotor A bearing has fault",
- "cn": "主轴承温度测量PT100传感器故障",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Bit 6 from the status byte from the rotor A bearing PT100 input becomes TRUE.(giStatePT100_TempRotorBearingA.6=1)",
- "trigger_cn": "主轴承PT100传感器输入的状态字节第6位是TRUE或主轴承1min平均温度不在[-100,500]范围内。(giStatePT100_TempRotorBearingA.6=1 OR (grTempRotorBearingA_1min >500 OR grTempRotorBearingA_1min<-100))",
- "set_delay": "T#5s",
- "yp": "0",
- "reset_en": "Bit 6 from the status byte from the rotor A bearing PT100 input becomes FALSE.(giStatePT100_TempRotorBearingA.6=0)",
- "reset_cn": "主轴承PT100传感器输入的状态字节第6位是FALSE且主轴承1min平均温度在[-100,500]范围内。(giStatePT100_TempRotorBearingA.6=0 AND (grTempRotorBearingA_1min <500 AND grTempRotorBearingA_1min>-100))",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_04_001": {
- "subsystem": "Drivetrain",
- "name": "SC_RotorOverSpeedLevel1",
- "en": "Rotor speed exceeds the level1 overspeed limit",
- "cn": "低速端转速高于1级超速门限值",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "3",
- "repeat_period": "T#1h",
- "trigger_en": "The current value for rotor speed exceeds the limit given by parameter.(grRotorSpeedPDM_100ms > PAR_rGenOverSpeedLevel1 / PAR_rGearboxRatio)",
- "trigger_cn": "风机100ms平均转速高于1级超速门限值(值由参数计算得出)。(grRotorSpeedPDM_100ms > PAR_rGenOverSpeedLevel1 / PAR_rGearboxRatio)",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "The current value for rotor speed falls below the limit given by parameter and less than 10.(grRotorSpeedPDM <= rRotorOverSpeedLevel1 AND grRotorSpeedPDM < 10.0)",
- "reset_cn": "风机转速不高于1级超速门限值,并且风机转速小于10。(grRotorSpeedPDM <= rRotorOverSpeedLevel1 AND grRotorSpeedPDM < 10.0)",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_04_003": {
- "subsystem": "Drivetrain",
- "name": "SC_GeneratorOverSpeedLevel1",
- "en": "Generator speed exceeds the level1 overspeed limit",
- "cn": "发电机转速高于1级超速门限值",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "3",
- "repeat_period": "T#1h",
- "trigger_en": "The current value for generator speed exceeds the level1 overspeed limit given by parameter.(grGenSpeedForProcess > PAR_rGenOverSpeedLevel1)",
- "trigger_cn": "发电机转速大于发电机1级超速门限值。(grGenSpeedForProcess > PAR_rGenOverSpeedLevel1)",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "The current value for generator speed falls below the level1 overspeed limit given by parameter and is less than 500.(grGenSpeedForProcess <= PAR_rGenOverSpeedLevel1 AND grGenSpeedForProcess < 500.0)",
- "reset_cn": "发电机转速不大于发电机1级超速门限值,且速度低于500。(grGenSpeedForProcess <= PAR_rGenOverSpeedLevel1 AND grGenSpeedForProcess < 500.0)",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_04_005": {
- "subsystem": "Drivetrain",
- "name": "SC_RepFaultOverspeedLevel1",
- "en": "Level1 overspeed faults have repeated",
- "cn": "风机低速端或发电机转速高于1级超速门限值故障重复出现",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The statuscode for \"rotor overspeed level 1\" or that one for \"rotor overspeed level 1\" in a given time periode becomes more times TRUE than allowed maximum number.(gbRepeat_02_04_001=1 OR gbRepeat_02_04_003=1)",
- "trigger_cn": "风机低速端转速高于1级超速门限值或发电机转速高于1级超速门限值。(gbRepeat_02_04_001=1 OR gbRepeat_02_04_003=1)",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "The statuscode for \"rotor overspeed level 1\" and that one for \"rotor overspeed level 1\" in a given time periode becomes less times TRUE than allowed maximum number.(gbRepeat_02_04_001=0 AND gbRepeat_02_04_003=0 AND SC_RotorOverSpeedLevel1=0 AND SC_GeneratorOverSpeedLevel1=0)",
- "reset_cn": "风机低速端转速不高于1级超速门限值且发电机转速不高于1级超速门限值。(gbRepeat_02_04_001=0 AND gbRepeat_02_04_003=0 AND SC_RotorOverSpeedLevel1=0 AND SC_GeneratorOverSpeedLevel1=0)",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "100"
- },
- "02_04_006": {
- "subsystem": "Drivetrain",
- "name": "SC_RotorSpeedUnequalGeneratorSpeed",
- "en": "Rotor speed is NOT compatible with generator speed",
- "cn": "低速端转速与发电机转速不匹配",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Following conditions are fullfiled: _x000D_ 1.the generator speed or the rotor speed is higher than parameter value 2.no brake program active 3.speed unequal error is monitored 4.generator speed calculated from converter and rotor speed differ more than a value given (in percent) by parameter._x000D_ (giBPLevel = 0 AND grGenSpeedForProcess_1sec > PAR_rGenSpeedStartCompareRotGen AND ABS (rRotorSpeedPDM_TransferedToGenSpeed - grGenSpeedForProcess_1sec)> rMaxDiffSpeed_RPM) AND NOT OC_IgnoreSpeedUnequalError _x000D_ IF grGenSpeedForProcess_1sec > PAR_rGenSpeedUnequalDefectingHighSpeed,rMaxDiffSpeed_RPM := grGenSpeedForProcess_1sec * PAR_rGenSpeedDiffCompareRotGen_RPM_HIGH / 100.0; ELSE,rMaxDiffSpeed_RPM := grGenSpeedForProcess_1sec * PAR_rGenSpeedDiffCompareRotGen_RPM / 100.0;",
- "trigger_cn": "风机满足如下所有条件:_x000D_ 1.没有刹车程序被激活 2.发电机转速高于设定值3.OC_IgnoreSpeedUnequalError为false 4.变频器计算得到的发电机转速和从发电机转子计算得到的转速差大于给定值。_x000D_ (giBPLevel = 0 AND grGenSpeedForProcess_1sec > PAR_rGenSpeedStartCompareRotGen AND NOT OC_IgnoreSpeedUnequalError AND ABS (rRotorSpeedPDM_TransferedToGenSpeed - grGenSpeedForProcess_1sec)> rMaxDiffSpeed_RPM)。 当grGenSpeedForProcess_1sec > PAR_rGenSpeedUnequalDefectingHighSpeed时,rMaxDiffSpeed_RPM := grGenSpeedForProcess_1sec * PAR_rGenSpeedDiffCompareRotGen_RPM_HIGH / 100.0;否则,rMaxDiffSpeed_RPM := grGenSpeedForProcess_1sec * PAR_rGenSpeedDiffCompareRotGen_RPM / 100.0;",
- "set_delay": "T#1500ms",
- "yp": "0",
- "reset_en": "At least one Following conditions is not fullfiled: _x000D_ 1.the generator speed or the rotor speed is higher than parameter value 2.no brake program active 3.speed unequal error is monitored 4.generator speed calculated from converter and rotor speed differ more than a value given (in percent) by parameter._x000D_ (giBPLevel = 0 AND grGenSpeedForProcess_1sec > PAR_rGenSpeedStartCompareRotGen AND ABS (rRotorSpeedPDM_TransferedToGenSpeed - grGenSpeedForProcess_1sec)> rMaxDiffSpeed_RPM) AND NOT OC_IgnoreSpeedUnequalError _x000D_ IF grGenSpeedForProcess_1sec > PAR_rGenSpeedUnequalDefectingHighSpeed,rMaxDiffSpeed_RPM := grGenSpeedForProcess_1sec * PAR_rGenSpeedDiffCompareRotGen_RPM_HIGH / 100.0; ELSE,rMaxDiffSpeed_RPM := grGenSpeedForProcess_1sec * PAR_rGenSpeedDiffCompareRotGen_RPM / 100.0;",
- "reset_cn": "至少一个如下条件风机不满足:_x000D_ 1.没有刹车程序被激活 2.发电机转速高于设定值3.OC_IgnoreSpeedUnequalError为false 4.变频器计算得到的发电机转速和从发电机转子计算得到的转速差大于给定值_x000D_ (giBPLevel = 0 AND grGenSpeedForProcess_1sec > PAR_rGenSpeedStartCompareRotGen AND NOT OC_IgnoreSpeedUnequalError AND ABS (rRotorSpeedPDM_TransferedToGenSpeed - grGenSpeedForProcess_1sec)> rMaxDiffSpeed_RPM)。 当grGenSpeedForProcess_1sec > PAR_rGenSpeedUnequalDefectingHighSpeed时,rMaxDiffSpeed_RPM := grGenSpeedForProcess_1sec * PAR_rGenSpeedDiffCompareRotGen_RPM_HIGH / 100.0;否则,rMaxDiffSpeed_RPM := grGenSpeedForProcess_1sec * PAR_rGenSpeedDiffCompareRotGen_RPM / 100.0;",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "50",
- "brake_state_design": "100"
- },
- "02_04_007": {
- "subsystem": "Drivetrain",
- "name": "SC_RotorDirectionWrong",
- "en": "Rotor rotating direction is wrong",
- "cn": "低速端旋转方向错误",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "When generator speed is in a given range(a small speed)AND grConverter_GeneratorSpeed < -0.1.(grGenSpeedForProcess_100ms > PAR_rGenSpeedStartDetectDirection) AND (grGenSpeedForProcess_100ms < PAR_rGenSpeedStopDetectDirection) AND (grConverter_GeneratorSpeed < -0.1)",
- "trigger_cn": "当发电机转速处于一个小窗口速度区,且速度小于负的0.1。(grGenSpeedForProcess_100ms > PAR_rGenSpeedStartDetectDirection) AND (grGenSpeedForProcess_100ms < PAR_rGenSpeedStopDetectDirection) AND (grConverter_GeneratorSpeed < -0.1)",
- "set_delay": "T#2s",
- "yp": "0",
- "reset_en": "When generator speed is not in a given range(a small speed)or grConverter_GeneratorSpeed >= -0.1.(grGenSpeedForProcess_100ms <= PAR_rGenSpeedStartDetectDirection) OR (grGenSpeedForProcess_100ms >= PAR_rGenSpeedStopDetectDirection) OR (grConverter_GeneratorSpeed >= -0.1)",
- "reset_cn": "发电机转速不处于一个小窗口速度区或速度不小于负的0.1。(grGenSpeedForProcess_100ms <= PAR_rGenSpeedStartDetectDirection) OR (grGenSpeedForProcess_100ms >= PAR_rGenSpeedStopDetectDirection) OR (grConverter_GeneratorSpeed >= -0.1)",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_04_026": {
- "subsystem": "Drivetrain",
- "name": "SC_TempRotorBearingA_high",
- "en": "Temperature of rotor bearing A is too high",
- "cn": "主轴的轴承座温度过高警告",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The 10min-mean-value of the temperature exceeds the value given by parameter.(grTempRotorBearingA_10min > PAR_rTempHigh_RotorBearingA)",
- "trigger_cn": "主轴承10分钟平均温度高于设定值。(grTempRotorBearingA_10min > PAR_rTempHigh_RotorBearingA)",
- "set_delay": "T#1m",
- "yp": "0",
- "reset_en": "The 10min-mean-value of temperature falls below the value given by parameter minus a hysteresis value OR get reset signal of status code coming from Nacelle, Tower or Remote Command.(grTempRotorBearingA_10min < (PAR_rTempHigh_RotorBearingA - PAR_rTempHysteresisUpperTemp) OR gbMAIN_ResetStatusCodes)",
- "reset_cn": "主轴承温度(10分钟平均值)小于设定值减去一个滞后值或收到reset信号。(grTempRotorBearingA_10min < (PAR_rTempHigh_RotorBearingA - PAR_rTempHysteresisUpperTemp) OR gbMAIN_ResetStatusCodes)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_04_028": {
- "subsystem": "Drivetrain",
- "name": "SC_TempRotorBearingA_MAX",
- "en": "Temperature of rotor bearing A exceeds maximum limit",
- "cn": "主轴的轴承座温度过高故障",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "3",
- "repeat_period": "T#24h",
- "trigger_en": "The 10min-mean-value of the temperature exceeds the maximum limit.(grTempRotorBearingA_10min > PAR_rTempMAX_RotorBearingA)",
- "trigger_cn": "主轴承10分钟平均温度高于最大值。(grTempRotorBearingA_10min > PAR_rTempMAX_RotorBearingA)",
- "set_delay": "T#1m",
- "yp": "0",
- "reset_en": "The 10min-mean-value of temperature falls below the value given by parameter minus a hysteresis value OR get reset signal of status code coming from Nacelle, Tower or Remote Command.(grTempRotorBearingA_10min < (PAR_rTempMAX_RotorBearingA - PAR_rTempHysteresisUpperTemp) OR gbMAIN_ResetStatusCodes)",
- "reset_cn": "主轴承温度(10分钟平均值)小于最大值减去一个滞后值或收到reset信号。(grTempRotorBearingA_10min < (PAR_rTempMAX_RotorBearingA - PAR_rTempHysteresisUpperTemp) OR gbMAIN_ResetStatusCodes)",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_04_030": {
- "subsystem": "Drivetrain",
- "name": "SC_RepFaultTempRotorBearingA",
- "en": "The faults, rotor bearing A temperature exceeds maximum or minimum limit, have repeated",
- "cn": "主轴的轴承座温度过高警告重复出现",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The faults, rotor bearing A temperature exceeds maximum or minimum limit, have repeated.(gbRepeat_02_04_028=1 OR gbRepeat_02_04_029=1)",
- "trigger_cn": "主轴承温度高于最大、最小值故障重复出现。(gbRepeat_02_04_028=1 OR gbRepeat_02_04_029=1)",
- "set_delay": "T#1m",
- "yp": "0",
- "reset_en": "The faults, rotor bearing A temperature does not exceed maximum or minimum limit, have repeated.(gbRepeat_02_04_028=0 AND gbRepeat_02_04_029=0)",
- "reset_cn": "主轴承温度高于最大、最小值故障没有重复出现。(gbRepeat_02_04_028=0 AND gbRepeat_02_04_029=0)",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_04_039": {
- "subsystem": "Drivetrain",
- "name": "SC_GeneratorSpeedUnequalConverter",
- "en": "Generator speed from sensor is different from generator speed from converter",
- "cn": "主控系统测得的发电机转速与从变频器读得的不匹配",
- "powerup_delay": "T#0s",
- "disable_level": "50",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Following conditions are fullfiled: _x000D_ 1.the generator speed or the rotor speed is higher than parameter value 2.no brake program active 3.speed unequal error is monitored 4.measured generator speed and speed calculated from converter differ more than a value given (in percent) by parameter._x000D_ (giBPLevel = 0 AND grGenSpeedForProcess_1sec > PAR_rGenSpeedStartCompareRotGen AND ABS(grGenSpeedPDM - grConverter_GeneratorSpeed) > rMaxDiffSpeed_RPM。 IF grGenSpeedForProcess_1sec > PAR_rGenSpeedUnequalDefectingHighSpeed,rMaxDiffSpeed_RPM := grGenSpeedForProcess_1sec * PAR_rGenSpeedDiffCompareRotGen_RPM_HIGH / 100.0; ELSE,rMaxDiffSpeed_RPM := grGenSpeedForProcess_1sec * PAR_rGenSpeedDiffCompareRotGen_RPM / 100.0;",
- "trigger_cn": "风机满足如下所有条件:_x000D_ 1.没有刹车程序被激活 2.发电机转速高于设定值3.OC_IgnoreSpeedUnequalError为false 4.发电机转速和从变频器计算得到的转速差大于给定值。_x000D_ (giBPLevel = 0 AND grGenSpeedForProcess_1sec > PAR_rGenSpeedStartCompareRotGen AND NOT OC_IgnoreSpeedUnequalError AND ABS(grGenSpeedPDM - grConverter_GeneratorSpeed) > rMaxDiffSpeed_RPM。 IF grGenSpeedForProcess_1sec > PAR_rGenSpeedUnequalDefectingHighSpeed,rMaxDiffSpeed_RPM := grGenSpeedForProcess_1sec * PAR_rGenSpeedDiffCompareRotGen_RPM_HIGH / 100.0; ELSE,rMaxDiffSpeed_RPM := grGenSpeedForProcess_1sec * PAR_rGenSpeedDiffCompareRotGen_RPM / 100.0;",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "At least one Following conditions is not fullfiled: _x000D_ 1.the generator speed or the rotor speed is higher than parameter value 2.no brake program active 3.speed unequal error is monitored 4.measured generator speed and speed calculated from converter differ more than a value given (in percent) by parameter._x000D_ (giBPLevel = 0 AND grGenSpeedForProcess_1sec > PAR_rGenSpeedStartCompareRotGen AND ABS(grGenSpeedPDM - grConverter_GeneratorSpeed) > rMaxDiffSpeed_RPM。 IF grGenSpeedForProcess_1sec > PAR_rGenSpeedUnequalDefectingHighSpeed,rMaxDiffSpeed_RPM := grGenSpeedForProcess_1sec * PAR_rGenSpeedDiffCompareRotGen_RPM_HIGH / 100.0; ELSE,rMaxDiffSpeed_RPM := grGenSpeedForProcess_1sec * PAR_rGenSpeedDiffCompareRotGen_RPM / 100.0;",
- "reset_cn": "风机不满足至少一个如下条件:_x000D_ 1.没有刹车程序被激活 2.发电机转速高于设定值3.OC_IgnoreSpeedUnequalError为false 4.发电机转速和从变频器计算得到的转速差大于给定值。_x000D_ (giBPLevel = 0 AND grGenSpeedForProcess_1sec > PAR_rGenSpeedStartCompareRotGen AND NOT OC_IgnoreSpeedUnequalError AND ABS(grGenSpeedPDM - grConverter_GeneratorSpeed) > rMaxDiffSpeed_RPM。 IF grGenSpeedForProcess_1sec > PAR_rGenSpeedUnequalDefectingHighSpeed,rMaxDiffSpeed_RPM := grGenSpeedForProcess_1sec * PAR_rGenSpeedDiffCompareRotGen_RPM_HIGH / 100.0; ELSE,rMaxDiffSpeed_RPM := grGenSpeedForProcess_1sec * PAR_rGenSpeedDiffCompareRotGen_RPM / 100.0;",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "50",
- "brake_state_design": "100"
- },
- "02_04_102": {
- "subsystem": "Drivetrain",
- "name": "OC_GeneratorSpeedBelowSlipLimit_MIN",
- "en": "Generator speed falls below cut-out limit",
- "cn": "发电机转速小于切出电网转速",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The 100ms mean value for generattor speed falls below the cut-out limit value.(grGenSpeedForProcess_100ms < PAR_rGenSpeedSlipLimit_MIN)",
- "trigger_cn": "发电机100ms平均转速小于切出电网转速。(grGenSpeedForProcess_100ms < PAR_rGenSpeedSlipLimit_MIN)",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "The 100ms mean value for generattor speed exceeds the cut-out limit value.(grGenSpeedForProcess_100ms >= PAR_rGenSpeedSlipLimit_MIN)",
- "reset_cn": "发电机100ms平均转速不小于切出电网转速。(grGenSpeedForProcess_100ms >= PAR_rGenSpeedSlipLimit_MIN)",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "03_09_009": {
- "subsystem": "Drivetrain",
- "name": "SC_MaxGenSpeedAtManualOP",
- "en": "In manual control of turbine, generator speed is too high",
- "cn": "手动控制模式下,发电机转速过大",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "During activated manual control of the turbine the generator speed exceeds a maximum value given by parameter.(OC_ManualTurbineControlActive=1 AND grGenSpeedForProcess_100ms > PAR_rMaxGenSpeedAtManualOperation)",
- "trigger_cn": "手动控制模式下,发电机转速大于最大值。(OC_ManualTurbineControlActive=1 AND grGenSpeedForProcess_100ms > PAR_rMaxGenSpeedAtManualOperation)",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "Not in activated manual control of the turbine, or the generator speed falls below a maximum value given by parameter.(OC_ManualTurbineControlActive=0 OR grGenSpeedForProcess_100ms <= PAR_rMaxGenSpeedAtManualOperation)",
- "reset_cn": "不处于手动控制模式下,或发电机转速低于最大值。(OC_ManualTurbineControlActive=0 OR grGenSpeedForProcess_100ms <= PAR_rMaxGenSpeedAtManualOperation)",
- "reset_mode": "M",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "51"
- },
- "04_04_001": {
- "subsystem": "DriveTrain",
- "name": "SC_MainBearingTempDeviationWarning",
- "en": "The deviation of two main bearings temperature warning",
- "cn": "前后主轴承温差异常",
- "powerup_delay": "T#30s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "gbTempDiffFrontAndRearBearing",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_04_005": {
- "subsystem": "DriveTrain",
- "name": "SC_RearMainBearingTempWarning",
- "en": "The temperature of rear main bearing is high",
- "cn": "主轴后轴承温度过高报警",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "gr_TempRearMainBearing>PAR_rTempRearBearingHighWarning",
- "trigger_cn": "",
- "set_delay": "T#10s",
- "yp": "0",
- "reset_en": "AI_Rear_Main_Bearing_Temp < PAR_rXX - 10",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_04_006": {
- "subsystem": "DriveTrain",
- "name": "SC_RearMainBearingTempError",
- "en": "The temperature of rear main bearing is too high",
- "cn": "主轴后轴承温度过高故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "gr_TempRearMainBearing>PAR_rTempRearBearingHighError",
- "trigger_cn": "",
- "set_delay": "T#10s",
- "yp": "0",
- "reset_en": "AI_Rear_Main_Bearing_Temp < PAR_rXX - 10",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_04_007": {
- "subsystem": "DriveTrain",
- "name": "SC_FaultPT100_RearMainRotorBearing",
- "en": "PT100 for Rear Main Rotor Bearing has fault",
- "cn": "主轴后轴承PT100故障",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#5s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_04_008": {
- "subsystem": "DriveTrain",
- "name": "SC_CouplingSlip",
- "en": "The coupling slips",
- "cn": "传动链联轴器打滑",
- "powerup_delay": "T#30s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "gbCouplingSlipSlightly OR gbCouplingSlipCritically",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_04_009": {
- "subsystem": "DriveTrain",
- "name": "SC_MainBearingsLubLevelLow",
- "en": "The level of main bearings lubrication system is low",
- "cn": "主轴承润滑系统油位过低",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "NOT gbDI_MainBearingLubLowLevelOK",
- "trigger_cn": "",
- "set_delay": "T#5s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_04_010": {
- "subsystem": "DriveTrain",
- "name": "SC_MainBearingsLubPreHigh",
- "en": "The pressure of main bearings lubrication system is high",
- "cn": "主轴承润滑系统油压过高",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "NOT gbDI_MainBearingLubPreHighOK",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_04_011": {
- "subsystem": "DriveTrain",
- "name": "SC_MainBearingsLubPistonNotMove",
- "en": "The piston of main bearing lubrication system is not moving",
- "cn": "主轴承润滑系统油脂分配器故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#5s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_04_012": {
- "subsystem": "DriveTrain",
- "name": "SC_Sensor1GeneratorImpulsesDefect",
- "en": "The No.1 inductive sensor of generator has defect",
- "cn": "发电机#1接近开关失效",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "A",
- "alarm": "True",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_04_013": {
- "subsystem": "DriveTrain",
- "name": "SC_Sensor2GeneratorImpulsesDefect",
- "en": "The No.2 inductive sensor of generator has defect",
- "cn": "发电机#2接近开关失效",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "A",
- "alarm": "True",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_02_027": {
- "subsystem": "GearBox",
- "name": "SC_MotorProtection_GearOilPump",
- "en": "The motor protection for gearbox oil pump has tripped.",
- "cn": "机舱柜中齿轮箱的油泵电机保护空开跳开",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The motor protection for gearbox oil pump has tripped.(gbDI_NacelleMotorProtGearOilPump=0)",
- "trigger_cn": "齿轮箱油泵的电机保护系统发生故障。(gbDI_NacelleMotorProtGearOilPump=0)",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "The motor protection for gearbox oil pump is OK.(gbDI_NacelleMotorProtGearOilPump=1 )",
- "reset_cn": "齿轮箱油泵的电机保护系统故障解除。(gbDI_NacelleMotorProtGearOilPump=1 )",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_02_029": {
- "subsystem": "GearBox",
- "name": "SC_MotorProtection_GearFan",
- "en": "The motor protection system for gearbox cooling fan has tripped.",
- "cn": "机舱柜中齿轮箱冷却风扇保护空开跳开",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The motor protection for gearbox cooling fan has tripped.(gbDI_NacelleMotorProtGearFan=0)",
- "trigger_cn": "齿轮箱冷却风扇断路器状态断开。(gbDI_NacelleMotorProtGearFan=0)",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "The motor protection for gearbox cooling fan is OK.(gbDI_NacelleMotorProtGearFan=1)",
- "reset_cn": "齿轮箱冷却风扇电机保护系统故障解除。(gbDI_NacelleMotorProtGearFan=1)",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_02_031": {
- "subsystem": "Gearbox",
- "name": "SC_NacelleFuseGearboxHeater",
- "en": "The fuse for gearbox heater has tripped.",
- "cn": "机舱柜中齿轮箱油池加热器保护空开跳开",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The fuse for gearbox heater has tripped.(gbDI_NacelleMotorProtGearHeater=0)",
- "trigger_cn": "齿轮箱加热器保险丝发生故障。(gbDI_NacelleMotorProtGearHeater=0)",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "The fuse for gearbox heater is OK.(gbDI_NacelleMotorProtGearHeater=1)",
- "reset_cn": "齿轮箱加热器保险丝故障解除。(gbDI_NacelleMotorProtGearHeater=1)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_02_042": {
- "subsystem": "GearBox",
- "name": "SC_NacelleFuseMotorHeater_GearFanAndOilPump",
- "en": "The fuse for power supply for gearbox heater, fan and oil pump has tripped.",
- "cn": "机舱柜中齿轮箱冷却风扇电机加热器或齿轮箱油泵电机加热器保护空开跳开",
- "powerup_delay": "T#0s",
- "disable_level": "99",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The fuse for power supply for gearbox heater, fan and oil pump has tripped.(gbDI_NacelleFuseHeaterGearFanAndOilPump=0)",
- "trigger_cn": "齿轮箱加热器,风扇和油泵的电源保险丝发生故障。(gbDI_NacelleFuseHeaterGearFanAndOilPump=0)",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "The fuse for power supply for gearbox heater, fan and oil pump is OK.(gbDI_NacelleFuseHeaterGearFanAndOilPump=1)",
- "reset_cn": "齿轮箱加热器,风扇和油泵的电源保险丝故障解除。(gbDI_NacelleFuseHeaterGearFanAndOilPump=1)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_02_043": {
- "subsystem": "Gearbox",
- "name": "SC_NacelleFuseHeater_GearOilPipe",
- "en": "SC_NacelleFuseHeater_GearOilPipe",
- "cn": "机舱柜中齿轮箱油管加热器保护开关跳开",
- "powerup_delay": "T#0s",
- "disable_level": "99",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_02_054": {
- "subsystem": "GearBox",
- "name": "SC_FaultInputPT100_GearOilSump",
- "en": "PT100 for gearbox oil sump has fault",
- "cn": "齿轮箱油池油温测量PT100传感器故障",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Bit 6 from the status byte from the gearbox oil sump PT100 input becomes TRUE.(giStatePT100_TempGearOilSump.6=1)",
- "trigger_cn": "齿轮箱油箱PT100传感器输入的状态字节第6位是TRUE或油箱1min平均温度不在[-100,500]范围内。(giStatePT100_TempGearOilSump.6=1 OR (grTempGearOilSump_1min>500 OR grTempGearOilSump_1min<-100))",
- "set_delay": "T#5s",
- "yp": "0",
- "reset_en": "Bit 6 from the status byte from the gearbox oil sump PT100 input becomes FALSE.(giStatePT100_TempGearOilSump.6=0)",
- "reset_cn": "齿轮箱油箱PT100传感器输入的状态字节第6位是FALSE且油箱1min平均温度在[-100,500]范围内。(giStatePT100_TempGearOilSump.6=0 AND (grTempGearOilSump_1min<500 AND grTempGearOilSump_1min>-100))",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_02_055": {
- "subsystem": "GearBox",
- "name": "SC_FaultInputPT100_GearOilInlet",
- "en": "PT100 for gearbox oil inlet has fault",
- "cn": "齿轮箱入口油温测量PT100传感器故障",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Bit 6 from the status byte from the gearbox oil inlet PT100 input becomes TRUE.(giStatePT100_TempGearOilInlet.6=1)",
- "trigger_cn": "齿轮箱进油口PT100传感器输入的状态字节第6位是TRUE或进油口1min平均温度不在[-100,500]范围内。(giStatePT100_TempGearOilInlet.6=1 OR grTempGearOilInlet_1min >500 OR grTempGearOilInlet_1min <-100)",
- "set_delay": "T#5s",
- "yp": "0",
- "reset_en": "Bit 6 from the status byte from the gearbox oil inlet PT100 input becomes FALSE.(giStatePT100_TempGearOilInlet.6=0)",
- "reset_cn": "齿轮箱进油口PT100传感器输入的状态字节第6位是FALSE且进油口1min平均温度在[-100,500]范围内。(giStatePT100_TempGearOilInlet.6=0 AND (grTempGearOilInlet_1min <500 AND grTempGearOilInlet_1min >-100))",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_02_058": {
- "subsystem": "GearBox",
- "name": "SC_FaultInputPT100_GearBearingDE",
- "en": "PT100 for gearbox DE bearing has fault",
- "cn": "驱动端轴承温度测量PT100传感器故障",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Bit 6 from the status byte from the gearbox DE bearing PT100 input becomes TRUE.(giStatePT100_TempGearBearingDE.6=1)",
- "trigger_cn": "齿轮箱驱动端轴承PT100传感器输入的状态字节第6位是TRUE或齿轮箱驱动端轴承1min平均温度不在[-100,500]范围内。(giStatePT100_TempGearBearingDE.6=1 OR (grTempGearBearingDE_1min >500 OR grTempGearBearingDE_1min <-100))",
- "set_delay": "T#5s",
- "yp": "0",
- "reset_en": "Bit 6 from the status byte from the gearbox DE bearing PT100 input becomes FALSE.(giStatePT100_TempGearBearingDE.6=0)",
- "reset_cn": "齿轮箱驱动端轴承PT100传感器输入的状态字节第6位是FALSE且齿轮箱驱动端轴承1min平均温度在[-100,500]范围内。(giStatePT100_TempGearBearingDE.6=0 NAD(grTempGearBearingDE_1min <500 AND grTempGearBearingDE_1min >-100))",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_02_059": {
- "subsystem": "GearBox",
- "name": "SC_FaultInputPT100_GearBearingNDE",
- "en": "PT100 for gearbox NDE bearing has fault",
- "cn": "非驱动端轴承温度测量PT100传感器故障",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Bit 6 from the status byte from the gearbox NDE bearing PT100 input becomes TRUE.(giStatePT100_TempGearBearingNDE.6=1)",
- "trigger_cn": "齿轮箱非驱动端轴承PT100传感器输入的状态字节第6位是TRUE或齿轮箱非驱动端轴承1min平均温度不在[-100,500]范围内。(giStatePT100_TempGearBearingNDE.6=1 OR (grTempGearBearingNDE_1min >500 OR grTempGearBearingNDE_1min <-100)",
- "set_delay": "T#5s",
- "yp": "0",
- "reset_en": "Bit 6 from the status byte from the gearbox NDE bearing PT100 input becomes FALSE.(giStatePT100_TempGearBearingNDE.6=0)",
- "reset_cn": "齿轮箱非驱动端轴承PT100传感器输入的状态字节第6位是FALSE且齿轮箱非驱动端轴承1min平均温度在[-100,500]范围内。(giStatePT100_TempGearBearingNDE.6=0 AND(grTempGearBearingNDE_1min <500 AND grTempGearBearingNDE_1min >-100)",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_02_061": {
- "subsystem": "Gearbox",
- "name": "SC_FaultInputPT100_GearBearingInterDE",
- "en": "SC_FaultInputPT101_GearBearingInterDE",
- "cn": "齿轮箱驱动端的中间轴温度测量PT100传感器故障",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "齿轮箱中间轴驱动端轴承PT100传感器输入的状态字节第6位是TRUE或齿轮箱中间轴驱动端轴承1min平均温度不在[-100,500]范围内。(ggiStatePT100_TempGearBearingInterDE.6=1 OR (grTempGearBearingInterDE_1min >500 OR grTempGearBearingInterDE_1min<-100))",
- "set_delay": "T#5s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "齿轮箱中间轴驱动端轴承PT100传感器输入的状态字节第6位是FALSE且齿轮箱中间轴驱动端轴承1min平均温度在[-100,500]范围内。(ggiStatePT100_TempGearBearingInterDE.6=0 AND(grTempGearBearingInterDE_1min <500 AND grTempGearBearingInterDE_1min>-100))",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_02_062": {
- "subsystem": "Gearbox",
- "name": "SC_FaultInputPT100_GearBearingInterNDE",
- "en": "SC_FaultInputPT101_GearBearingInterNDE",
- "cn": "齿轮箱非驱动端中间轴温度测量PT100传感器故障",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "齿轮箱中间轴非驱动端轴承PT100传感器输入的状态字节第6位是TRUE或齿轮箱中间轴非驱动端轴承1min平均温度不在[-100,500]范围内。(ggiStatePT100_TempGearBearingInterNDE.6=1 OR (grTempGearBearingInterNDE_1min >500 OR grTempGearBearingInterNDE_1min<-100))",
- "set_delay": "T#5s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "齿轮箱中间轴非驱动端轴承PT100传感器输入的状态字节第6位是FALSE且齿轮箱中间轴非驱动端轴承1min平均温度在[-100,500]范围内。(giStatePT100_TempGearBearingInterNDE.6=0 AND(grTempGearBearingInterNDE_1min <500 AND grTempGearBearingInterNDE_1min>-100))",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_02_064": {
- "subsystem": "GearBox",
- "name": "SC_FaultAI_GearOilPressureFilterInlet",
- "en": "Gearbox filter inlet oil pressure input has fault",
- "cn": "齿轮箱过滤器入口压力传感器故障",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Bit 6 from the status byte from the Gearbox filter inlet oil pressure input becomes TRUE.(giStateAIGearOilPressureFilterInlet.6=1)",
- "trigger_cn": "齿轮箱滤网进油端压力传感器输入的状态字节第6位是TRUE。(giStateAIGearOilPressureFilterInlet.6=1)",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "Bit 6 from the status byte from the Gearbox filter inlet oil pressure input becomes FALSE.(giStateAIGearOilPressureFilterInlet.6=0)",
- "reset_cn": "齿轮箱滤网进油端压力传感器输入的状态字节第6位是FALSE。(giStateAIGearOilPressureFilterInlet.6=0)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_02_065": {
- "subsystem": "GearBox",
- "name": "SC_FaultAI_GearOilPressureGBXInlet",
- "en": "Gearbox inlet oil pressure sensor has fault",
- "cn": "齿轮箱入口压力传感器故障",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Bit 6 from the status byte from the Gearbox inlet oil pressure input becomes TRUE.(giStateAIGearOilPressureGBXInlet.6=1)",
- "trigger_cn": "齿轮箱入口油压传感器输入的状态字节第6位是TRUE。(giStateAIGearOilPressureGBXInlet.6=1)",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "Bit 6 from the status byte from the Gearbox inlet oil pressure input becomes FALSE.(giStateAIGearOilPressureGBXInlet.6=0)",
- "reset_cn": "齿轮箱入口油压传感器输入的状态字节第6位是FALSE。(giStateAIGearOilPressureGBXInlet.6=0)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_02_104": {
- "subsystem": "GearBox",
- "name": "OC_HeaterGearOilPump_ON",
- "en": "Heater of gearbox oil pump is set to on",
- "cn": "齿轮箱油泵加热器运行",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "PLC output for controlling the gearbox oil pump heater becomes TRUE.(DQ_NacelleGearHeaterOilPump=1)",
- "trigger_cn": "PLC控制发电机加热器的输出为TRUE。(DQ_NacelleGearHeaterOilPump=1)",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "PLC output for controlling the gearbox oil pump heater becomes FALSE.(DQ_NacelleGearHeaterOilPump=0)",
- "reset_cn": "PLC控制发电机加热器的输出为FALSE。(DQ_NacelleGearHeaterOilPump=0)",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "02_02_105": {
- "subsystem": "GearBox",
- "name": "OC_GearFanLS_ON",
- "en": "Gearbox low speed fan is set to on",
- "cn": "齿轮箱低速冷却风扇运行",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "PLC output for controlling the gearbox low speed fan becomes TRUE.(DQ_NacelleGearFanLS=1)",
- "trigger_cn": "PLC控制齿轮箱低速风扇的输出为TRUE。(DQ_NacelleGearFanLS=1)",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "PLC output for controlling the gearbox low speed fan becomes FALSE.(DQ_NacelleGearFanLS=0)",
- "reset_cn": "PLC控制齿轮箱低速风扇的输出为FALSE。(DQ_NacelleGearFanLS=0)",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "02_02_106": {
- "subsystem": "GearBox",
- "name": "OC_GearOilPumpLS_ON",
- "en": "Gearbox low speed oil pump is set to on",
- "cn": "齿轮箱低速油泵运行",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "PLC output for controlling the gearbox low speed oil pump becomes TRUE.(DQ_NacelleGearOilPumpLS=1)",
- "trigger_cn": "PLC控制齿轮箱低速油泵的输出为TRUE。(DQ_NacelleGearOilPumpLS=1)",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "PLC output for controlling the gearbox low speed oil pump becomes FALSE.(DQ_NacelleGearOilPumpLS=0)",
- "reset_cn": "PLC控制齿轮箱低速油泵的输出为FALSE。(DQ_NacelleGearOilPumpLS=0)",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "02_02_107": {
- "subsystem": "GearBox",
- "name": "OC_GearOilPumpHS_ON",
- "en": "Gearbox high speed oil pump is set to on",
- "cn": "齿轮箱高速油泵运行",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "PLC output for controlling the gearbox high speed oil pump becomes TRUE.(DQ_NacelleGearOilPumpHS=1)",
- "trigger_cn": "PLC控制齿轮箱高速油泵的输出为TRUE。(DQ_NacelleGearOilPumpHS=1)",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "PLC output for controlling the gearbox high speed oil pump becomes FALSE.(DQ_NacelleGearOilPumpHS=0)",
- "reset_cn": "PLC控制齿轮箱高速油泵的输出为FALSE。(DQ_NacelleGearOilPumpHS=0)",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "02_02_108": {
- "subsystem": "GearBox",
- "name": "OC_GearOilHeater_ON",
- "en": "Gearbox oil heater is set to on",
- "cn": "齿轮箱油池加热器运行",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "PLC output for controlling the gearbox oil heater becomes TRUE.(DQ_NacelleGearHeaterGearOil=1)",
- "trigger_cn": "PLC控制齿轮箱润滑油加热器的输出为TRUE。(DQ_NacelleGearHeaterGearOil=1)",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "PLC output for controlling the gearbox oil heater becomes FALSE.(DQ_NacelleGearHeaterGearOil=0)",
- "reset_cn": "PLC控制齿轮箱润滑油加热器的输出为FALSE。(DQ_NacelleGearHeaterGearOil=0)",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "02_02_112": {
- "subsystem": "GearBox",
- "name": "OC_GearFanHS_ON",
- "en": "Gearbox high speed fan is set to on",
- "cn": "齿轮箱高速冷却风扇高速运行",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "PLC output for controlling the gearbox high speed fan becomes TRUE.(DQ_NacelleGearFanHS=1)",
- "trigger_cn": "PLC控制齿轮箱高速风扇的输出为TRUE。(DQ_NacelleGearFanHS=1)",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "PLC output for controlling the gearbox high speed fan becomes FALSE.(DQ_NacelleGearFanHS=0)",
- "reset_cn": "PLC控制齿轮箱高速风扇的输出为FALSE。(DQ_NacelleGearFanHS=0)",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "02_02_113": {
- "subsystem": "GearBox",
- "name": "OC_HeaterGearFan_ON",
- "en": "Heater for gearbox fan is set to on",
- "cn": "齿轮箱冷却风扇加热器运行",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "PLC output for controlling the gearbox fan heater becomes TRUE.(DQ_NacelleGearHeaterFan=1)",
- "trigger_cn": "PLC控制齿轮箱风扇加热器的输出为TRUE。(DQ_NacelleGearHeaterFan=1)",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "PLC output for controlling the gearbox fan heater becomes FALSE.(DQ_NacelleGearHeaterFan=0)",
- "reset_cn": "PLC控制齿轮箱风扇加热器的输出为FALSE。(DQ_NacelleGearHeaterFan=0)",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "02_02_130": {
- "subsystem": "Gearbox",
- "name": "OC_GearOilFilter_ON",
- "en": "OC_GearOilFilter_ON",
- "cn": "齿轮箱精滤器运行",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "02_02_132": {
- "subsystem": "Gearbox",
- "name": "SC_GearOilFilter_Overload",
- "en": "SC_GearOilFilter_Overload",
- "cn": "齿轮箱精滤器保护空开跳开",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "02_05_001": {
- "subsystem": "GearBox",
- "name": "SC_GearOilFilterClogged_Warning",
- "en": "Gearbox oil filter has warning for clogging",
- "cn": "齿轮箱过滤器阻塞警告",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "3",
- "repeat_period": "T#24h",
- "trigger_en": "The gear oil pump is runnung (low speed or high speed) and the temperature of the gear oil (10 min mean value) is not lower than a value given by parameter.(DQ_NacelleGearOilPumpLS=1 OR DQ_NacelleGearOilPumpHS=1) AND (grTempGearOilSump_10min >= PAR_rTempGearOilBelowMonitoringFilter)",
- "trigger_cn": "齿轮油泵处于运行状态,但齿轮油的温度不低于设定值。(DQ_NacelleGearOilPumpLS=1 OR DQ_NacelleGearOilPumpHS=1) AND (grTempGearOilSump_10min >= PAR_rTempGearOilBelowMonitoringFilter)",
- "set_delay": "T#5s",
- "yp": "0",
- "reset_en": "The gear oil pump is runnung (low speed or high speed) and the temperature of the gear oil (10 min mean value) is lower than a value given by parameter.(DQ_NacelleGearOilPumpLS=1 OR DQ_NacelleGearOilPumpHS=1) AND (grTempGearOilSump_10min < PAR_rTempGearOilBelowMonitoringFilter)",
- "reset_cn": "齿轮油泵处于运行状态,但齿轮油的温度低于设定值。(DQ_NacelleGearOilPumpLS=1 OR DQ_NacelleGearOilPumpHS=1) AND (grTempGearOilSump_10min < PAR_rTempGearOilBelowMonitoringFilter)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_05_002": {
- "subsystem": "GearBox",
- "name": "SC_RepFaultGearOilFilterClogged",
- "en": "Gearbox oil filter is clogged.(The warning has repeated)",
- "cn": "齿轮箱过滤器堵塞故障",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The statuscode for \"SC_GearOilFilterClogged_Warning\" in a given time periode becomes more times TRUE than maximum allowed.(gbRepeat_02_05_001=1)",
- "trigger_cn": "齿轮箱滤网阻塞警告不断出现。(gbRepeat_02_05_001=1)",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "The statuscode for \"SC_GearOilFilterClogged_Warning\" in a given time periode becomes less times TRUE than maximum allowed.(gbRepeat_02_05_001=0)",
- "reset_cn": "齿轮箱滤网阻塞警告消除。(gbRepeat_02_05_001=0)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_05_003": {
- "subsystem": "GearBox",
- "name": "SC_GearOilFilterClogged_STOP",
- "en": "Gearbox oil filter is clogged for stop",
- "cn": "齿轮箱过滤器阻塞故障,要求停机",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Gearbox oil filter is clogged.(SC_RepFaultGearOilFilterClogged=1)",
- "trigger_cn": "齿轮箱滤网阻塞故障不断。(SC_RepFaultGearOilFilterClogged=1)",
- "set_delay": "PAR_tDelayGearOilFilterClogged_STOP",
- "yp": "0",
- "reset_en": "Gearbox oil filter is OK.(SC_RepFaultGearOilFilterClogged=0)",
- "reset_cn": "齿轮箱滤网阻塞故障消除。(SC_RepFaultGearOilFilterClogged=0)",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_05_004": {
- "subsystem": "GearBox",
- "name": "SC_GearOilLevel_Warning",
- "en": "Gearbox oil level has warning",
- "cn": "齿轮箱油池油位警告",
- "powerup_delay": "T#0s",
- "disable_level": "50",
- "repeat_n": "3",
- "repeat_period": "T#24h",
- "trigger_en": "Gearbox oil level(the corresponding digital input) is not ok.(gbDI_NacelleGearOilLevelOK=0)",
- "trigger_cn": "齿轮箱油位(相应的的数字输入)有警告。(gbDI_NacelleGearOilLevelOK=0)",
- "set_delay": "PAR_tDelayGearOilLevel_Warning",
- "yp": "0",
- "reset_en": "Gearbox oil level(the corresponding digital input) is ok.(gbDI_NacelleGearOilLevelOK=1)",
- "reset_cn": "齿轮箱油位(相应的的数字输入)OK了。(gbDI_NacelleGearOilLevelOK=1)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_05_005": {
- "subsystem": "GearBox",
- "name": "SC_GearOilLevel_STOP",
- "en": "Gearbox oil level is not ok for stop",
- "cn": "齿轮箱油池油位故障",
- "powerup_delay": "T#0s",
- "disable_level": "50",
- "repeat_n": "3",
- "repeat_period": "T#1h",
- "trigger_en": "Gearbox oil level(the corresponding digital input) is not ok.(gbDI_NacelleGearOilLevelOK=0)",
- "trigger_cn": "齿轮箱油位(相应的数字输入)有警告。(gbDI_NacelleGearOilLevelOK=0)",
- "set_delay": "PAR_tDelayGearOilLevel_STOP",
- "yp": "0",
- "reset_en": "Gearbox oil level(the corresponding digital input) is ok.(gbDI_NacelleGearOilLevelOK=0)",
- "reset_cn": "齿轮箱油位(相应的的数字输入)OK。(gbDI_NacelleGearOilLevelOK=1)",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_05_006": {
- "subsystem": "GearBox",
- "name": "SC_RepFaultGearOilLevel",
- "en": "The warning of gearbox oil level has repeated",
- "cn": "齿轮箱油池油位警告重复出现",
- "powerup_delay": "T#0s",
- "disable_level": "50",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The statuscode for \"SC_GearOilLevel_Warning\" in a given time periode becomes more times TRUE than maximum allowed.(gbRepeat_02_05_004=1)",
- "trigger_cn": "齿轮箱油位警告(SC_GearOilLevel_Warning)重复出现。(gbRepeat_02_05_004=1)",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "The statuscode for \"SC_GearOilLevel_Warning\" in a given time periode becomes less times TRUE than maximum allowed.",
- "reset_cn": "齿轮箱油位警告消除。(gbRepeat_02_05_004=0)",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_05_008": {
- "subsystem": "GearBox",
- "name": "SC_GBXFilterOilPressure_MAX_STOP",
- "en": "Gearbox oil pressure exceeds the maximum limit",
- "cn": "齿轮箱油压高于上限值",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "3",
- "repeat_period": "T#24h",
- "trigger_en": "The gear oil pump is runnung (low speed or high speed) and the 1 minute mean value for \"GearOilPressureFilterInlet\" or \"GearOilPressureGBXInle\" will be higher than the maximum limit.(DQ_NacelleGearOilPumpLS=1 OR DQ_NacelleGearOilPumpHS=1) AND (grGearOilPressureFilterInlet_1sec > PAR_rGearOilPressure_MAX) OR (grGearOilPressureGBXInlet_1sec > PAR_rGearOilPressure_MAX)",
- "trigger_cn": "齿轮油泵处于运行状态,滤网或齿轮箱入口油压1分钟平均值高于最大限值。(DQ_NacelleGearOilPumpLS=1 OR DQ_NacelleGearOilPumpHS=1) AND (grGearOilPressureFilterInlet_1sec > PAR_rGearOilPressure_MAX) OR (grGearOilPressureGBXInlet_1sec > PAR_rGearOilPressure_MAX)",
- "set_delay": "T#60s",
- "yp": "0",
- "reset_en": "The gear oil pump is runnung (low speed or high speed) and the 1 minute mean value for \"GearOilPressureFilterInlet\" and \"GearOilPressureGBXInle\" will be lower than the maximum limit.(DQ_NacelleGearOilPumpLS=1 OR DQ_NacelleGearOilPumpHS=1) AND (grGearOilPressureFilterInlet_1sec <= PAR_rGearOilPressure_MAX) AND (grGearOilPressureGBXInlet_1sec <= PAR_rGearOilPressure_MAX)",
- "reset_cn": "齿轮油泵处于运行状态,滤网和齿轮箱入口油压1分钟平均值不高于最大限值。(DQ_NacelleGearOilPumpLS=1 OR DQ_NacelleGearOilPumpHS=1) AND (grGearOilPressureFilterInlet_1sec <= PAR_rGearOilPressure_MAX) AND (grGearOilPressureGBXInlet_1sec <= PAR_rGearOilPressure_MAX)",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_05_015": {
- "subsystem": "GearBox",
- "name": "SC_TempGearOilSump_high",
- "en": "Temperature of gearbox oil sump is too high",
- "cn": "齿轮箱油池温度过高警告",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "3",
- "repeat_period": "T#24h",
- "trigger_en": "The 1min-mean-value of the temperature exceeds the value given by parameter.(grTempGearOilSump_1min > PAR_rTempHigh_GearOilSump)",
- "trigger_cn": "齿轮箱油箱1分钟平均温度高于设定值。(grTempGearOilSump_1min > PAR_rTempHigh_GearOilSump)",
- "set_delay": "T#1m",
- "yp": "0",
- "reset_en": "The 1min-mean-value of temperature falls below the value given by parameter minus a hysteresis value OR get reset signal of status code coming from Nacelle, Tower or Remote Command.((grTempGearOilSump_1min < (PAR_rTempHigh_GearOilSump - PAR_rTempHysteresisUpperTemp)) OR gbMAIN_ResetStatusCodes=1)",
- "reset_cn": "齿轮箱油箱温度(1分钟平均值)小于设定值减去一个滞后值或收到reset信号。((grTempGearOilSump_1min < (PAR_rTempHigh_GearOilSump - PAR_rTempHysteresisUpperTemp)) OR gbMAIN_ResetStatusCodes=1)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "165",
- "brake_state_design": "0"
- },
- "02_05_016": {
- "subsystem": "GearBox",
- "name": "SC_TempGearOilSump_low",
- "en": "Temperature of gearbox oil sump is too low",
- "cn": "齿轮箱油池温度过低警告",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "3",
- "repeat_period": "T#24h",
- "trigger_en": "The 10min-mean-value of the temperature falls below the value given by parameter.(grTempGearOilSump_10min < PAR_rTempLow_GearOilSump)",
- "trigger_cn": "齿轮箱油箱10分钟平均温度低于设定值。(grTempGearOilSump_10min < PAR_rTempLow_GearOilSump)",
- "set_delay": "T#1m",
- "yp": "0",
- "reset_en": "The 10min-mean-value of temperature increases above the value given by parameter plus a hysteresis value OR get reset signal of status code coming from Nacelle, Tower or Remote Command. ((grTempGearOilSump_10min > (PAR_rTempLow_GearOilSump + PAR_rTempHysteresisLowerTemp) OR gbMAIN_ResetStatusCodes=1)",
- "reset_cn": "齿轮箱油箱温度(10分钟平均值)大于设定值加上一个滞后值或收到reset信号。((grTempGearOilSump_10min > (PAR_rTempLow_GearOilSump + PAR_rTempHysteresisLowerTemp) OR gbMAIN_ResetStatusCodes=1)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "50"
- },
- "02_05_017": {
- "subsystem": "GearBox",
- "name": "SC_TempGearOilSump_MAX",
- "en": "Temperature of gearbox oil sump exceeds maximum limit",
- "cn": "齿轮箱油池温度过高故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The 1min-mean-value of the temperature exceeds the maximum limit OR The 10min-mean-value of the temperature exceeds the value given by parameter for 30m._x000D_ (grTempGearOilSump_10min > PAR_rTempHigh_GearOilSump) last for 30 min OR (grTempGearOilSump_1min >_x000D_ PAR_rTempMAX_GearOilSump)",
- "trigger_cn": "齿轮箱油箱1分钟平均温度高于最高值或齿轮箱油温10分钟平均温度超过高温值达30分钟以上。(grTempGearOilSump_10min > PAR_rTempHigh_GearOilSump) last for 30 min OR (grTempGearOilSump_1min >_x000D_ PAR_rTempMAX_GearOilSump)",
- "set_delay": "T#1m",
- "yp": "0",
- "reset_en": "The 1min-mean-value of temperature falls below the maximum limit value given by parameter minus a hysteresis value OR get reset signal of status code coming from Nacelle, Tower or Remote Command.(grTempGearOilSump_10min < (PAR_rTempMAX_GearOilSump - PAR_rTempHysteresisUpperTemp) OR gbMAIN_ResetStatusCodes=1)",
- "reset_cn": "齿轮箱油箱温度(1分钟平均值)小于最大值减去一个滞后值或收到reset信号。(grTempGearOilSump_10min < (PAR_rTempMAX_GearOilSump - PAR_rTempHysteresisUpperTemp) OR gbMAIN_ResetStatusCodes=1)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_05_018": {
- "subsystem": "GearBox",
- "name": "SC_TempGearOilSump_MIN",
- "en": "Temperature of gearbox oil sump exceeds minimum limit",
- "cn": "齿轮箱油池温度过低故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The 10min-mean-value of the temperature falls below the minimum limit.(grTempGearOilSump_10min < PAR_rTempMIN_GearOilSump)",
- "trigger_cn": "齿轮箱油箱10分钟平均温度高于最低限值。grTempGearOilSump_10min < PAR_rTempMIN_GearOilSump)",
- "set_delay": "T#1m",
- "yp": "0",
- "reset_en": "The 10min-mean-value of temperature increases above the value given by parameter plus a hysteresis value OR get reset signal of status code coming from Nacelle, Tower or Remote Command. (grTempGearOilSump_10min > (PAR_rTempMIN_GearOilSump + PAR_rTempHysteresisLowerTemp) OR gbMAIN_ResetStatusCodes=1)",
- "reset_cn": "齿轮箱油箱温度(10分钟平均值)大于最小值加上一个滞后值或收到reset信号。(grTempGearOilSump_10min > (PAR_rTempMIN_GearOilSump + PAR_rTempHysteresisLowerTemp) OR gbMAIN_ResetStatusCodes=1)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_05_019": {
- "subsystem": "GearBox",
- "name": "SC_TempGearOilInlet_high",
- "en": "Temperature of gearbox oil inlet is too high",
- "cn": "齿轮箱入口油温过高警告",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The 10min-mean-value of the temperature exceeds the value given by parameter.(grTempGearOilInlet_10min > PAR_rTempHigh_GearOilInlet)",
- "trigger_cn": "齿轮箱入口10分钟平均油温高于设定值。(grTempGearOilInlet_10min > PAR_rTempHigh_GearOilInlet)",
- "set_delay": "T#1m",
- "yp": "0",
- "reset_en": "The 10min-mean-value of temperature falls below the value given by parameter minus a hysteresis value OR get reset signal of status code coming from Nacelle, Tower or Remote Command.(grTempGearOilInlet_10min < (PAR_rTempHigh_GearOilInlet - PAR_rTempHysteresisUpperTemp) OR gbMAIN_ResetStatusCodes=1)",
- "reset_cn": "齿轮箱入口油温(10分钟平均值)小于设定值减去一个滞后值或收到reset信号。(grTempGearOilInlet_10min < (PAR_rTempHigh_GearOilInlet - PAR_rTempHysteresisUpperTemp) OR gbMAIN_ResetStatusCodes=1)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_05_020": {
- "subsystem": "GearBox",
- "name": "SC_TempGearOilInlet_low",
- "en": "Temperature of gearbox oil inlet is too low",
- "cn": "齿轮箱入口油温过低警告",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The 10min-mean-value of the temperature falls below the value given by parameter.(grTempGearOilInlet_10min < PAR_rTempLow_GearOilInlet)",
- "trigger_cn": "齿轮箱入口10分钟平均油温低于设定值。(grTempGearOilInlet_10min < PAR_rTempLow_GearOilInlet)",
- "set_delay": "T#1m",
- "yp": "0",
- "reset_en": "The 10min-mean-value of temperature increases above the value given by parameter plus a hysteresis value OR get reset signal of status code coming from Nacelle, Tower or Remote Command. (grTempGearOilInlet_10min > (PAR_rTempLow_GearOilInlet + PAR_rTempHysteresisLowerTemp) OR gbMAIN_ResetStatusCodes=1)",
- "reset_cn": "齿轮箱油箱入口温度(10分钟平均值)大于设定值加上一个滞后值或收到reset信号。(grTempGearOilInlet_10min > (PAR_rTempLow_GearOilInlet + PAR_rTempHysteresisLowerTemp) OR gbMAIN_ResetStatusCodes=1)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "50"
- },
- "02_05_021": {
- "subsystem": "GearBox",
- "name": "SC_TempGearOilInlet_MAX",
- "en": "Temperature of gearbox oil inlet exceeds maximum limit",
- "cn": "齿轮箱入口油温过高故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The 10min-mean-value of the temperature exceeds the maximum limit OR the 10min-mean-value of the temperature exceeds the value given by parameter for 30m.(grTempGearOilInlet_10min > PAR_rTempMAX_GearOilInlet OR bSTOP_DelayWarningElapsed=1)",
- "trigger_cn": "齿轮箱入口10分钟平均油温高于最高限值或高于设定值达30分钟之久。(grTempGearOilInlet_10min > PAR_rTempMAX_GearOilInlet OR bSTOP_DelayWarningElapsed=1)",
- "set_delay": "T#1m",
- "yp": "0",
- "reset_en": "The 10min-mean-value of temperature falls below the value given by parameter minus a hysteresis value OR get reset signal of status code coming from Nacelle, Tower or Remote Command.(grTempGearOilInlet_10min < (PAR_rTempMAX_GearOilInlet - PAR_rTempHysteresisUpperTemp) OR gbMAIN_ResetStatusCodes=1)",
- "reset_cn": "齿轮箱入口油温(10分钟平均值)小于最大值减去一个滞后值或收到reset信号。(grTempGearOilInlet_10min < (PAR_rTempMAX_GearOilInlet - PAR_rTempHysteresisUpperTemp) OR gbMAIN_ResetStatusCodes=1)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_05_022": {
- "subsystem": "GearBox",
- "name": "SC_TempGearOilInlet_MIN",
- "en": "Temperature of gearbox oil inlet exceeds minimum limit",
- "cn": "齿轮箱入口油温过低故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The 10min-mean-value of the temperature falls below the minimum limit.(grTempGearOilInlet_10min < PAR_rTempMIN_GearOilInlet)",
- "trigger_cn": "齿轮箱入口10分钟平均油温低于最低限值。(grTempGearOilInlet_10min < PAR_rTempMIN_GearOilInlet)",
- "set_delay": "T#1m",
- "yp": "0",
- "reset_en": "The 10min-mean-value of temperature increases above the value given by parameter plus a hysteresis value OR get reset signal of status code coming from Nacelle, Tower or Remote Command. (grTempGearOilInlet_10min > (PAR_rTempMIN_GearOilInlet + PAR_rTempHysteresisLowerTemp) OR gbMAIN_ResetStatusCodes=1)",
- "reset_cn": "齿轮箱油箱入口温度(10分钟平均值)大于最小值加上一个滞后值或收到reset信号。(grTempGearOilInlet_10min > (PAR_rTempMIN_GearOilInlet + PAR_rTempHysteresisLowerTemp) OR gbMAIN_ResetStatusCodes=1)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_05_027": {
- "subsystem": "GearBox",
- "name": "SC_RepFaultTempGearOilSump",
- "en": "The faults, gearbox oil sump temperature is too high or too low, have repeated",
- "cn": "齿轮箱油池温度高于过高设定值或低于过低设定值故障重复出现",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The faults, gearbox oil sump temperature is too high or too low, have repeated.(gbRepeat_02_05_015=1 OR gbRepeat_02_05_016=1)",
- "trigger_cn": "齿轮箱油箱温度过高或过低的故障重复出现。(gbRepeat_02_05_015=1 OR gbRepeat_02_05_016=1)",
- "set_delay": "T#1m",
- "yp": "0",
- "reset_en": "The faults, gearbox oil sump temperature is too high or too low, have not repeated.(gbRepeat_02_05_015=0 AND gbRepeat_02_05_016=0)",
- "reset_cn": "齿轮箱油箱温度过高和过低的故障均无。(gbRepeat_02_05_015=0 AND gbRepeat_02_05_016=0)",
- "reset_mode": "M",
- "type": "A",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_05_028": {
- "subsystem": "GearBox",
- "name": "SC_TempGearBearingDE_high",
- "en": "Temperature of gearbox drive-end bearing is too high",
- "cn": "齿轮箱驱动端轴承温度过高警告",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "3",
- "repeat_period": "T#24h",
- "trigger_en": "The 1min-mean-value of the temperature exceeds the value given by parameter.(grTempGearBearingDE_1min > PAR_rTempHigh_GearBearingDE)",
- "trigger_cn": "齿轮箱驱动端轴承1分钟温度过高。(grTempGearBearingDE_1min > PAR_rTempHigh_GearBearingDE)",
- "set_delay": "T#1m",
- "yp": "0",
- "reset_en": "The 1min-mean-value of temperature falls below the value given by parameter minus a hysteresis value OR get reset signal of status code coming from Nacelle, Tower or Remote Command.(grTempGearBearingDE_1min < (PAR_rTempHigh_GearBearingDE - PAR_rTempHysteresisUpperTemp) OR gbMAIN_ResetStatusCodes=1)",
- "reset_cn": "齿轮箱驱动端轴承温度(1分钟平均值)小于设定值减去一个滞后值或收到reset信号。(grTempGearBearingDE_1min < (PAR_rTempHigh_GearBearingDE - PAR_rTempHysteresisUpperTemp) OR gbMAIN_ResetStatusCodes=1)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_05_030": {
- "subsystem": "GearBox",
- "name": "SC_TempGearBearingDE_MAX",
- "en": "Temperature of gearbox drive-end bearing exceeds maximum limit",
- "cn": "齿轮箱驱动端轴承温度过高故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The 1min-mean-value of the temperature exceeds the maximum limit value or the value given by parameter for 30m.(grTempGearBearingDE_1min > PAR_rTempMAX_GearBearingDE OR bSTOP_DelayWarningElapsed=1)",
- "trigger_cn": "齿轮箱驱动端轴承1分钟平均温度高于最高限值或高于设定值达30分钟之久。(grTempGearBearingDE_1min > PAR_rTempMAX_GearBearingDE OR bSTOP_DelayWarningElapsed=1)",
- "set_delay": "T#1m",
- "yp": "0",
- "reset_en": "The 1min-mean-value of temperature falls below the value given by parameter minus a hysteresis value OR get reset signal of status code coming from Nacelle, Tower or Remote Command.(grTempGearBearingDE_1min < (PAR_rTempMAX_GearBearingDE - PAR_rTempHysteresisUpperTemp) OR gbMAIN_ResetStatusCodes=1)_x000D_",
- "reset_cn": "齿轮箱驱动端轴承温度(1分钟平均值)小于最大值减去一个滞后值或收到reset信号。(grTempGearBearingDE_1min < (PAR_rTempMAX_GearBearingDE - PAR_rTempHysteresisUpperTemp) OR gbMAIN_ResetStatusCodes=1)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_05_032": {
- "subsystem": "GearBox",
- "name": "SC_RepFaultTempGearBearingDE",
- "en": "The faults, gearbox drive-end bearing temperature is too high or low, have repeated",
- "cn": "齿轮箱驱动端轴承温度过于过高设定值或低于过低设定值故障重复出现",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The faults, gearbox DE bearing temperature is too high or too low, have repeated.(gbRepeat_02_05_028=1 OR gbRepeat_02_05_029=1)",
- "trigger_cn": "齿轮箱驱动端轴承温度过高或过低的故障重复出现。(gbRepeat_02_05_028=1 OR gbRepeat_02_05_029=1)",
- "set_delay": "T#1m",
- "yp": "0",
- "reset_en": "The faults, gearbox DE bearing temperature is too high or too low, have not repeated.(gbRepeat_02_05_028=0 AND gbRepeat_02_05_029=0)",
- "reset_cn": "齿轮箱驱动端轴承温度过高和过低的故障均无。(gbRepeat_02_05_028=0 AND gbRepeat_02_05_029=0)",
- "reset_mode": "M",
- "type": "A",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_05_033": {
- "subsystem": "GearBox",
- "name": "SC_TempGearBearingNDE_high",
- "en": "Temperature of gearbox non-drive-end bearing is too high",
- "cn": "齿轮箱非驱动端轴承温度过高警告",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "3",
- "repeat_period": "T#24h",
- "trigger_en": "The 10min-mean-value of the temperature exceeds the value given by parameter.(grTempGearBearingNDE_10min > PAR_rTempHigh_GearBearingNDE)",
- "trigger_cn": "齿轮箱非驱动端轴承10分钟平均温度高于设定值。(grTempGearBearingNDE_10min > PAR_rTempHigh_GearBearingNDE)",
- "set_delay": "T#1m",
- "yp": "0",
- "reset_en": "The 10min-mean-value of temperature increases above the value given by parameter plus a hysteresis value OR get reset signal of status code coming from Nacelle, Tower or Remote Command.(grTempGearBearingNDE_10min > (PAR_rTempMIN_GearBearingDE + PAR_rTempHysteresisLowerTemp) OR gbMAIN_ResetStatusCodes=1)",
- "reset_cn": "齿轮箱非驱动端轴承温度(10分钟平均值)大于设定值加上一个滞后值或收到reset信号。(grTempGearBearingDE_10min > (PAR_rTempLow_GearBearingNDE + PAR_rTempHysteresisLowerTemp) OR gbMAIN_ResetStatusCodes=1)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_05_035": {
- "subsystem": "GearBox",
- "name": "SC_TempGearBearingNDE_MAX",
- "en": "Temperature of gearbox non-drive-end bearing exceeds maximum limit",
- "cn": "齿轮箱非驱动端轴承温度过高故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The 1min-mean-value of the temperature exceeds the maximum limit OR The 10min-mean-value of the temperature exceeds the value given by parameter for 30m.(grTempGearBearingNDE_1min > PAR_rTempMAX_GearBearingNDE) OR (grTempGearBearingNDE_10min > PAR_rTempHigh_GearBearingNDE) last for 30 min_x000D_",
- "trigger_cn": "齿轮箱非驱动端轴承1分钟平均油温高于上限值或10min平均油温高于设定值达30分钟之久。(grTempGearBearingNDE_1min > PAR_rTempMAX_GearBearingNDE) OR (grTempGearBearingNDE_10min > PAR_rTempHigh_GearBearingNDE) last for 30 min",
- "set_delay": "T#1m",
- "yp": "0",
- "reset_en": "The 1min-mean-value of temperature falls below the maximum limit value given by parameter minus a hysteresis value OR get reset signal of status code coming from Nacelle, Tower or Remote Command.(grTempGearBearingNDE_10min < (PAR_rTempMAX_GearBearingNDE - PAR_rTempHysteresisUpperTemp) OR gbMAIN_ResetStatusCodes=1)_x000D_ _x000D_",
- "reset_cn": "齿轮箱非驱动端轴承温度(1分钟平均值)小于最大值减去一个滞后值或收到reset信号。(grTempGearBearingNDE_10min < (PAR_rTempMAX_GearBearingNDE - PAR_rTempHysteresisUpperTemp) OR gbMAIN_ResetStatusCodes=1)",
- "reset_mode": "M",
- "type": "A",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_05_037": {
- "subsystem": "GearBox",
- "name": "SC_RepFaultTempGearBearingNDE",
- "en": "The faults, gearbox non-drive-end bearing temperature is too high or low, have repeated",
- "cn": "齿轮箱非驱动端轴承温度高于过高设定值或低于过低设定值故障重复出现",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The faults, gearbox NDE bearing temperature is too high or too low, have repeated.(gbRepeat_02_05_033=1 OR gbRepeat_02_05_034=1)",
- "trigger_cn": "齿轮箱非驱动端轴承温度过高或过低的故障重复出现。(gbRepeat_02_05_033=1 OR gbRepeat_02_05_034=1)",
- "set_delay": "T#1m",
- "yp": "0",
- "reset_en": "The faults, gearbox NDE bearing temperature is too high or too low, have not repeated.(gbRepeat_02_05_033=0 AND gbRepeat_02_05_034=0)",
- "reset_cn": "齿轮箱非驱动端轴承温度过高和过低的故障均无。(gbRepeat_02_05_033=0 AND gbRepeat_02_05_034=0)",
- "reset_mode": "M",
- "type": "A",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_05_038": {
- "subsystem": "Gearbox",
- "name": "SC_TempGearBearingInterDE_high",
- "en": "Overtemperature, bearing inlet at drive end of gearbox",
- "cn": "齿轮箱驱动端轴承入口温度过高警告",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "3",
- "repeat_period": "T#24h",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#1m",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_05_039": {
- "subsystem": "Gearbox",
- "name": "SC_TempGearBearingInterDE_MAX",
- "en": "Too low temperature, bearing inlet at drive end of gearbox",
- "cn": "齿轮箱驱动端轴承入口温度过高故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#1m",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_05_041": {
- "subsystem": "Gearbox",
- "name": "SC_TempGearBearingInterNDE_high",
- "en": "Temperature of bearing inlet at drive end of gearbox higher than upper limit",
- "cn": "齿轮箱驱动端轴承入口温度过高警告",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "3",
- "repeat_period": "T#24h",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#1m",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_05_042": {
- "subsystem": "Gearbox",
- "name": "SC_TempGearBearingInterNDE_MAX",
- "en": "Temperature of bearing inlet at drive end of gearbox lower than lower limit",
- "cn": "齿轮箱驱动端轴承入口温度过高故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#1m",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_05_043": {
- "subsystem": "Gearbox",
- "name": "SC_GearOilFilter_TempHigh",
- "en": "SC_GearOilFilter_TempHigh",
- "cn": "齿轮箱过滤器的油温过高",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "02_05_044": {
- "subsystem": "Gearbox",
- "name": "SC_GearOilFilter_PressureHigh",
- "en": "SC_GearOilFilter_PresureHigh",
- "cn": "齿轮箱过滤器压力过大",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "02_05_045": {
- "subsystem": "GearBox",
- "name": "SC_GearOilFilterOffLine_Blocking",
- "en": "SC_GearOilFilterOffLine_Blocking",
- "cn": "齿轮箱精滤器堵塞",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0S",
- "trigger_en": "",
- "trigger_cn": "每隔20分钟检测,连续三次压力过大,则报精滤器堵塞",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "I",
- "alarm": "True",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_05_100": {
- "subsystem": "GearBox",
- "name": "OC_NoMonitoringOfGearOilFilter",
- "en": "No monitoring of gearbox oil filter",
- "cn": "齿轮箱过滤器不监测阻塞情况",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "No monitoring of gearbox oil filter.(gbNoMonitoringOfGearOilFilter=1)",
- "trigger_cn": "齿轮箱滤网不监测。(gbNoMonitoringOfGearOilFilter=1)",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "Monitoring of gearbox oil filter.(gbNoMonitoringOfGearOilFilter=0)",
- "reset_cn": "齿轮箱滤网恢复监测。(gbNoMonitoringOfGearOilFilter=0)",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "02_05_110": {
- "subsystem": "Gearbox",
- "name": "SC_GearboxHeatingModeTimeout",
- "en": "Gearbox heating mode time out",
- "cn": "齿轮箱暖机超时",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "OC_GearboxHeatingMode is TRUE",
- "trigger_cn": "齿轮箱暖机模式持续时间过长",
- "set_delay": "PAR_tGearboxHeatingModeTimeout",
- "yp": "0",
- "reset_en": "OC_GearboxHeatingMode is FALSE",
- "reset_cn": "退出齿轮箱暖机模式",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_05_001": {
- "subsystem": "Gearbox",
- "name": "OC_GearFanLSForceMode",
- "en": "Gearbox Low-Speed Fan enter in ForceMode",
- "cn": "齿轮箱低速风扇强制模式开启",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "RemCmdACK_bEnableGearboxFanLSForceCtrl = TRUE",
- "trigger_cn": "",
- "set_delay": "T#50ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_05_002": {
- "subsystem": "Gearbox",
- "name": "OC_GearFanLSManualMode",
- "en": "Gearbox Low-Speed Fan enter in ManualMode",
- "cn": "齿轮箱低速风扇手动模式开启",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "RemCmdACK_bEnableGearboxFanLSManualCtrl = TRUE",
- "trigger_cn": "",
- "set_delay": "T#50ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_05_003": {
- "subsystem": "Gearbox",
- "name": "OC_GearFanHSForceMode",
- "en": "Gearbox High-Speed Fan enter in ForceMode",
- "cn": "齿轮箱高速风扇强制模式开启",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "RemCmdACK_bEnableGearboxFanHSForceCtrl = TRUE",
- "trigger_cn": "",
- "set_delay": "T#50ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_05_004": {
- "subsystem": "Gearbox",
- "name": "OC_GearFanHSManualMode",
- "en": "Gearbox High-Speed Fan enter in ManualMode",
- "cn": "齿轮箱高速风扇手动模式开启",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "RemCmdACK_bEnableGearboxFanHSManualCtrl = TRUE",
- "trigger_cn": "",
- "set_delay": "T#50ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_05_005": {
- "subsystem": "Gearbox",
- "name": "OC_GearOilHeaterForceMode",
- "en": "Gearbox OilSump Heater Enter in ForceMode",
- "cn": "齿轮箱油池加热器强制模式开启",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "RemCmdACK_bEnableGearboxHeaterForceCtrl = TRUE",
- "trigger_cn": "",
- "set_delay": "T#50ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_05_006": {
- "subsystem": "Gearbox",
- "name": "OC_GearOilHeaterManualMode",
- "en": "Gearbox OilSump Heater Enter in ManualMode",
- "cn": "齿轮箱油池加热器手动模式开启",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "RemCmdACK_bEnableGearboxHeaterManualCtrl = TRUE",
- "trigger_cn": "",
- "set_delay": "T#50ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_05_007": {
- "subsystem": "Gearbox",
- "name": "OC_GearOilFilterForceMode",
- "en": "Gearbox Offline Oil Filter Enter in ForceMode",
- "cn": "齿轮箱精滤器强制模式开启",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "RemCmdACK_bEnableGearOilFilterForceCtrl = TRUE",
- "trigger_cn": "",
- "set_delay": "T#50ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_05_008": {
- "subsystem": "Gearbox",
- "name": "OC_GearOilFilterManualMode",
- "en": "Gearbox Offline Oil Filter Enter in ManualMode",
- "cn": "齿轮箱精滤器手动模式开启",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "RemCmdACK_bEnableGearOilFilterManualCtrl = TRUE",
- "trigger_cn": "",
- "set_delay": "T#50ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_05_009": {
- "subsystem": "Gearbox",
- "name": "OC_GearOilPumpLSForceMode",
- "en": "Gearbox Low-Speed Pump enter in ForceMode",
- "cn": "齿轮箱低速泵强制模式开启",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "RemCmdACK_bEnableGearOilPumpLSForceCtrl = TRUE",
- "trigger_cn": "",
- "set_delay": "T#50ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_05_010": {
- "subsystem": "Gearbox",
- "name": "OC_GearOilPumpLSManualMode",
- "en": "Gearbox Low-Speed Pump enter in ManualMode",
- "cn": "齿轮箱低速泵手动模式开启",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "RemCmdACK_bEnableGearOilPumpLSManualCtrl = TRUE",
- "trigger_cn": "",
- "set_delay": "T#50ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_05_011": {
- "subsystem": "Gearbox",
- "name": "OC_GearOilPumpHSForceMode",
- "en": "Gearbox High-Speed Pump enter in ForceMode",
- "cn": "齿轮箱高速泵强制模式开启",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "RemCmdACK_bEnableGearOilPumpHSForceCtrl = TRUE",
- "trigger_cn": "",
- "set_delay": "T#50ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_05_012": {
- "subsystem": "Gearbox",
- "name": "OC_GearOilPumpHSManualMode",
- "en": "Gearbox High-Speed Pump enter in ManualMode",
- "cn": "齿轮箱高速泵手动模式开启",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "RemCmdACK_bEnableGearOilPumpHSManualCtrl = TRUE",
- "trigger_cn": "",
- "set_delay": "T#50ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_05_013": {
- "subsystem": "Gearbox",
- "name": "OC_GearboxFanHeaterForceMode",
- "en": "Gearbox Fan Heater Enter in ForceMode",
- "cn": "齿轮箱风扇加热器强制模式开启",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "RemCmdACK_bEnableGearFanHeaterForceCtrl = TRUE",
- "trigger_cn": "",
- "set_delay": "T#50ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_05_014": {
- "subsystem": "Gearbox",
- "name": "OC_GearboxFanHeaterManualMode",
- "en": "Gearbox Fan Heater Enter in ManualMode",
- "cn": "齿轮箱风扇加热器手动模式开启",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "RemCmdACK_bEnableGearFanHeaterManualCtrl = TRUE",
- "trigger_cn": "",
- "set_delay": "T#50ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_05_015": {
- "subsystem": "Gearbox",
- "name": "OC_GearboxOilPumpHeaterForceMode",
- "en": "Gearbox Pump Heater Enter in ForceMode",
- "cn": "齿轮箱油泵加热器强制模式开启",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "RemCmdACK_bEnableGearOilPumpHeaterForceCtrl = TRUE",
- "trigger_cn": "",
- "set_delay": "T#50ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_05_016": {
- "subsystem": "Gearbox",
- "name": "OC_GearboxOilPumpHeaterManualMode",
- "en": "Gearbox Pump Heater Enter in ManualMode",
- "cn": "齿轮箱油泵加热器手动模式开启",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "RemCmdACK_bEnableGearOilPumpHeaterManualCtrl = TRUE",
- "trigger_cn": "",
- "set_delay": "T#50ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_05_017": {
- "subsystem": "Gearbox",
- "name": "SC_GBXOilPumpMotorLS_Overload",
- "en": "Gearbox Low-Speed Pump overload",
- "cn": "齿轮箱低速泵热继跳开",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_05_018": {
- "subsystem": "Gearbox",
- "name": "SC_GBXOilPumpMotorHS_Overload",
- "en": "Gearbox High-Speed Pump overload",
- "cn": "齿轮箱高速泵热继跳开",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_05_020": {
- "subsystem": "Gearbox",
- "name": "SC_GBXOilInletPressureTooLow",
- "en": "Gearbox Oil Inlet Pressure Too Low",
- "cn": "齿轮箱油入口压力过低故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#5s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_05_021": {
- "subsystem": "Gearbox",
- "name": "SC_GBXBearingIMS_GSGS_TempHigh",
- "en": "",
- "cn": "齿轮箱中速轴(GSGS)温度高警告",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "165",
- "brake_state_design": "0"
- },
- "04_05_022": {
- "subsystem": "Gearbox",
- "name": "SC_GBXBearingIMS_GSGS_TempMax",
- "en": "",
- "cn": "齿轮箱中速轴(GSGS)温度高故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_05_023": {
- "subsystem": "Gearbox",
- "name": "SC_GBXBearingIMS_GSRS_TempHigh",
- "en": "",
- "cn": "齿轮箱中速轴(GSRS)温度高警告",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "165",
- "brake_state_design": "0"
- },
- "04_05_024": {
- "subsystem": "Gearbox",
- "name": "SC_GBXBearingIMS_GSRS_TempMax",
- "en": "",
- "cn": "齿轮箱中速轴(GSRS)温度高故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_05_025": {
- "subsystem": "Gearbox",
- "name": "SC_GBXBearingIMS_RS_TempHigh",
- "en": "",
- "cn": "齿轮箱中速轴(RS)温度高警告",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "165",
- "brake_state_design": "0"
- },
- "04_05_026": {
- "subsystem": "Gearbox",
- "name": "SC_GBXBearingIMS_RS_TempMax",
- "en": "",
- "cn": "齿轮箱中速轴(RS)温度高故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_05_027": {
- "subsystem": "Gearbox",
- "name": "SC_GBXBearingHSS_GSGS_TempHigh",
- "en": "",
- "cn": "齿轮箱高速轴(GSGS)温度高警告",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "165",
- "brake_state_design": "0"
- },
- "04_05_028": {
- "subsystem": "Gearbox",
- "name": "SC_GBXBearingHSS_GSGS_TempMax",
- "en": "",
- "cn": "齿轮箱高速轴(GSGS)温度高故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_05_029": {
- "subsystem": "Gearbox",
- "name": "SC_GBXBearingHSS_GSRS_TempHigh",
- "en": "",
- "cn": "齿轮箱高速轴(GSRS)温度高警告",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "165",
- "brake_state_design": "0"
- },
- "04_05_030": {
- "subsystem": "Gearbox",
- "name": "SC_GBXBearingHSS_GSRS_TempMax",
- "en": "",
- "cn": "齿轮箱高速轴(GSRS)温度高故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_05_031": {
- "subsystem": "Gearbox",
- "name": "SC_FaultAIAI_Gearbox_Bearing_IMS_GSGS_Temp",
- "en": "",
- "cn": "齿轮箱中速轴(GSGS)PT100传感器故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_05_032": {
- "subsystem": "Gearbox",
- "name": "SC_FaultAIAI_Gearbox_Bearing_IMS_GSRS_Temp",
- "en": "",
- "cn": "齿轮箱中速轴(GSRS)PT100传感器故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_05_033": {
- "subsystem": "Gearbox",
- "name": "SC_FaultAIAI_Gearbox_Bearing_IMS_RS_Temp",
- "en": "",
- "cn": "齿轮箱中速轴(RS)PT100传感器故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_05_034": {
- "subsystem": "Gearbox",
- "name": "SC_FaultAIAI_Gearbox_Bearing_HSS_GSGS_Temp",
- "en": "",
- "cn": "齿轮箱高速轴(GSGS)PT100传感器故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_05_035": {
- "subsystem": "Gearbox",
- "name": "SC_FaultAIAI_Gearbox_Bearing_HSS_GSRS_Temp",
- "en": "",
- "cn": "齿轮箱高速轴(GSRS)PT100传感器故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_05_036": {
- "subsystem": "Gearbox",
- "name": "SC_FaultAIAI_Gearbox_Bearing_HSS_RS_Temp",
- "en": "",
- "cn": "齿轮箱高速轴(RS)PT100传感器故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_05_037": {
- "subsystem": "Gearbox",
- "name": "SC_GBXBearingHSS_RS_TempHigh",
- "en": "",
- "cn": "齿轮箱高速轴(RS)温度高警告",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "165",
- "brake_state_design": "0"
- },
- "04_05_038": {
- "subsystem": "Gearbox",
- "name": "SC_GBXBearingHSS_RS_TempMax",
- "en": "",
- "cn": "齿轮箱高速轴(RS)温度高故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_05_039": {
- "subsystem": "Gearbox",
- "name": "SC_GBXOfflineFitrationSystemMCB",
- "en": "Gearbox Offline Filter MCB",
- "cn": "齿轮箱离线精滤器空开跳开",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_05_040": {
- "subsystem": "GearBox",
- "name": "SC_GearOilPumpMotorPreheaterMCB",
- "en": "",
- "cn": "齿轮箱油泵加热器空开跳开",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_05_041": {
- "subsystem": "GearBox",
- "name": "SC_GearFilterPumpClogging",
- "en": "",
- "cn": "齿轮箱油泵滤网堵塞",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "False",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_05_042": {
- "subsystem": "GearBox",
- "name": "OC_GearOilPumpValve_ON",
- "en": "",
- "cn": "齿轮箱两位三通阀开启",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_05_043": {
- "subsystem": "GearBox",
- "name": "OC_GearOilPumpValveForceMode",
- "en": "",
- "cn": "齿轮箱两位三通阀强制模式开启",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "RemCmdACK_bEnableGearOilValveForceCtrl = TRUE",
- "trigger_cn": "",
- "set_delay": "T#50ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_05_044": {
- "subsystem": "GearBox",
- "name": "OC_GearOilPumpValveManualMode",
- "en": "",
- "cn": "齿轮箱两位三通阀手动模式开启",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "RemCmdACK_bEnableGearOilValveManualCtrl = TRUE",
- "trigger_cn": "",
- "set_delay": "T#50ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "02_02_036": {
- "subsystem": "Generator",
- "name": "SC_MotorProtection_GenFanExternal",
- "en": "The motor protection system for generator fan has tripped.",
- "cn": "机舱柜中发电机冷却风扇保护空开跳开",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The motor protection for generator fan has tripped.(gbDI_NacelleMotorProtGenFan=0)",
- "trigger_cn": "发电机冷却风扇电机保护系统发生故障。(gbDI_NacelleMotorProtGenFan=0)",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "The motor protection for generator fan is OK.(gbDI_NacelleMotorProtGenFan=1 AND bSpecResCond=1)",
- "reset_cn": "发电机冷却风扇电机保护系统故障解除。(gbDI_NacelleMotorProtGenFan=1 AND bSpecResCond=1)",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_02_038": {
- "subsystem": "Generator",
- "name": "SC_NacelleFuseGenSpaceHeater",
- "en": "The fuse for generator heater has tripped.",
- "cn": "机舱柜中发电机空间加热器保护空开跳开",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The fuse for generator heater has tripped.(gbDI_NacelleMotorProtGenSpaceHeater=0)",
- "trigger_cn": "发电机加热器保险丝发生故障。(gbDI_NacelleMotorProtGenSpaceHeater=0)",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "The fuse for generator heater is OK.(gbDI_NacelleMotorProtGenSpaceHeater=1)",
- "reset_cn": "发电机加热器保险丝故障解除。(gbDI_NacelleMotorProtGenSpaceHeater=1)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_02_067": {
- "subsystem": "Generator",
- "name": "SC_FaultInputPT100_GeneratorStatorU",
- "en": "PT100 for generator stator U coil has fault",
- "cn": "发电机定子U相绕组温度测量PT100传感器故障",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Bit 6 from the status byte from the generator stator U coil PT100 input becomes TRUE.(giStatePT100_TempGenStatorU.6=1)",
- "trigger_cn": "发电机定子U相绕组PT100传感器输入的状态字节第6位是TRUE或发电机定子U相绕组1min平均温度不在[-100,500]范围内。(giStatePT100_TempGenStatorU.6=1 OR (grTempGenStatorU_1min >500 OR grTempGenStatorU_1min<-100))",
- "set_delay": "T#5s",
- "yp": "0",
- "reset_en": "Bit 6 from the status byte from the generator stator U coil PT100 input becomes FALSE.(giStatePT100_TempGenStatorU.6=0)",
- "reset_cn": "发电机定子U相绕组PT100传感器输入的状态字节第6位是FALSE且发电机定子U相绕组1min平均温度在[-100,500]范围内。(giStatePT100_TempGenStatorU.6=0 AND (grTempGenStatorU_1min <500 AND grTempGenStatorU_1min>-100))",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_02_069": {
- "subsystem": "Generator",
- "name": "SC_FaultInputPT100_GeneratorStatorV",
- "en": "PT100 for generator stator V coil has fault",
- "cn": "发电机定子V相绕组温度测量PT100传感器故障",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Bit 6 from the status byte from the generator stator V coil PT100 input becomes TRUE.(giStatePT100_TempGenStatorV.6=1)",
- "trigger_cn": "发电机定子V相绕组PT100传感器输入的状态字节第6位是TRUE或发电机定子V相绕组1min平均温度不在[-100,500]范围内。(giStatePT100_TempGenStatorV.6=1 OR (grTempGenStatorV_1min >500 OR grTempGenStatorV_1min<-100))",
- "set_delay": "T#5s",
- "yp": "0",
- "reset_en": "Bit 6 from the status byte from the generator stator V coil PT100 input becomes FALSE.(giStatePT100_TempGenStatorV.6=0)",
- "reset_cn": "发电机定子V相绕组PT100传感器输入的状态字节第6位是FALSE且发电机定子V相绕组1min平均温度在[-100,500]范围内。(giStatePT100_TempGenStatorV.6=0 AND (grTempGenStatorV_1min <500 AND grTempGenStatorV_1min>-100))",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_02_071": {
- "subsystem": "Generator",
- "name": "SC_FaultInputPT100_GeneratorStatorW",
- "en": "PT100 for generator stator W coil has fault",
- "cn": "发电机定子W相绕组温度测量PT100传感器故障",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Bit 6 from the status byte from the generator stator W coil PT100 input becomes TRUE.(giStatePT100_TempGenStatorW.6=1)",
- "trigger_cn": "发电机定子W相绕组PT100传感器输入的状态字节第6位是TRUE或发电机定子W相绕组1min平均温度不在[-100,500]范围内。(giStatePT100_TempGenStatorW.6=1 OR (grTempGenStatorW_1min >500 OR grTempGenStatorW_1min<-100))",
- "set_delay": "T#5s",
- "yp": "0",
- "reset_en": "Bit 6 from the status byte from the generator stator W coil PT100 input becomes FALSE.(giStatePT100_TempGenStatorW.6=0)",
- "reset_cn": "发电机定子W相绕组PT100传感器输入的状态字节第6位是FALSE且发电机定子W相绕组1min平均温度在[-100,500]范围内。(giStatePT100_TempGenStatorW.6=0 AND (grTempGenStatorW_1min <500 AND grTempGenStatorW_1min>-100))",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_02_073": {
- "subsystem": "Generator",
- "name": "SC_FaultInputPT100_GeneratorBearingDE",
- "en": "PT100 for generator DE bearing has fault",
- "cn": "发电机驱动端轴承温度测量PT100传感器故障",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Bit 6 from the status byte from the generator DE bearing PT100 input becomes TRUE.(giStatePT100_TempGenBearingDE.6=1)",
- "trigger_cn": "发电机驱动端轴承PT100传感器输入的状态字节第6位是TRUE或发电机驱动端轴承1min平均温度不在[-100,500]范围内。giStatePT100_TempGenBearingDE.6=1 OR (grTempGenBearingDE_1min >500 OR grTempGenBearingDE_1min<-100)",
- "set_delay": "T#5s",
- "yp": "0",
- "reset_en": "Bit 6 from the status byte from the generator DE bearing PT100 input becomes FALSE.(giStatePT100_TempGenBearingDE.6=0)",
- "reset_cn": "发电机驱动端轴承PT100传感器输入的状态字节第6位是FALSE且发电机驱动端轴承1min平均温度在[-100,500]范围内。giStatePT100_TempGenBearingDE.6=0 AND(grTempGenBearingDE_1min <500 AND grTempGenBearingDE_1min>-100)",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_02_074": {
- "subsystem": "Generator",
- "name": "SC_FaultInputPT100_GeneratorBearingNDE",
- "en": "PT100 for generator NDE bearing has fault",
- "cn": "发电机非驱动端轴承温度测量PT100传感器故障",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Bit 6 from the status byte from the generator NDE bearing PT100 input becomes TRUE.(giStatePT100_TempGenBearingNDE.6=1)",
- "trigger_cn": "发电机非驱动端轴承PT100传感器输入的状态字节第6位是FALSE或发电机非驱动端轴承1min平均温度不在[-100,500]范围内。giStatePT100_TempGenBearingNDE.6=1 OR (grTempGenBearingNDE_1min >500 OR grTempGenBearingNDE_1min<-100)",
- "set_delay": "T#5s",
- "yp": "0",
- "reset_en": "Bit 6 from the status byte from the generator NDE bearing PT100 input becomes FALSE.(giStatePT100_TempGenBearingNDE.6=0)",
- "reset_cn": "发电机非驱动端轴承PT100传感器输入的状态字节第6位是FALSE且发电机非驱动端轴承1min平均温度在[-100,500]范围内。giStatePT100_TempGenBearingNDE.6=0 AND(grTempGenBearingNDE_1min <500 AND grTempGenBearingNDE_1min>-100)",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_02_101": {
- "subsystem": "Generator",
- "name": "OC_GenFanExternal_ON",
- "en": "Generator fan is set to on",
- "cn": "发电机冷却风扇运行",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "PLC output for controlling the generator fan becomes TRUE.(DQ_NacelleGenFan=1)",
- "trigger_cn": "PLC控制发电机风扇的输出为TRUE。(DQ_NacelleGenFan=1)",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "PLC output for controlling the generator fan becomes FALSE.(DQ_NacelleGenFan=0)",
- "reset_cn": "PLC控制发电机风扇的输出为FALSE。(DQ_NacelleGenFan=0)",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "02_02_103": {
- "subsystem": "Generator",
- "name": "OC_GenSpaceHeaterON",
- "en": "Generator heater is set to on",
- "cn": "发电机空间加热器运行",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "PLC output for controlling the generator heater becomes TRUE.(DQ_NacelleGenSpaceHeater=1)",
- "trigger_cn": "PLC控制发电机加热器的输出为TRUE。(DQ_NacelleGenSpaceHeater=1)",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "PLC output for controlling the generator heater becomes FALSE.(DQ_NacelleGenSpaceHeater=0)",
- "reset_cn": "PLC控制发电机加热器的输出为FALSE。(DQ_NacelleGenSpaceHeater=0)",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "02_02_128": {
- "subsystem": "Generator",
- "name": "SC_MotorProtection_WCSG",
- "en": "Air switch trip, water cooling system for generator, nacelle cabinet",
- "cn": "机舱柜中发电机水冷系统保护空开跳开",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_08_006": {
- "subsystem": "Generator",
- "name": "SC_GeneratorBrushesWaste_Warning",
- "en": "Generator brush is worn-out for warning",
- "cn": "发电机碳刷磨损警告",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Statuscode for \"GeneratorBrushesWaste_Warning\" will be TRUE for a time given by parameter.(SC_GeneratorBrushesWaste_Warning=1)",
- "trigger_cn": "状态字\"GeneratorBrushesWaste_Warning\"为TRUE。(SC_GeneratorBrushesWaste_Warning=1)",
- "set_delay": "T#10s",
- "yp": "0",
- "reset_en": "Statuscode for \"GeneratorBrushesWaste_Warning\" will be FALSE for a time given by parameter.(SC_GeneratorBrushesWaste_Warning=0)",
- "reset_cn": "状态字\"GeneratorBrushesWaste_Warning\"为FALSE。(SC_GeneratorBrushesWaste_Warning=0)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_08_007": {
- "subsystem": "Generator",
- "name": "SC_GeneratorBrushesWaste_STOP",
- "en": "Generator brush is worn-out for stop",
- "cn": "发电机碳刷磨损故障",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Generator brush is worn-out for stop.(SC_GeneratorBrushesWaste_Warning=1)",
- "trigger_cn": "发电机碳刷磨损故障。(SC_GeneratorBrushesWaste_Warning=1)",
- "set_delay": "PAR_tWarningToSTOP_GeneratorBrushes",
- "yp": "0",
- "reset_en": "Generator brush is not worn-out for stop.(SC_GeneratorBrushesWaste_Warning=0)",
- "reset_cn": "发电机不发生碳刷磨损故障。(SC_GeneratorBrushesWaste_Warning=0)",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_08_012": {
- "subsystem": "Generator",
- "name": "SC_GEN_StatorTempDiffExceedLimit",
- "en": "Temperature between two stators out of three exceeds certain value",
- "cn": "发电机定子两相绕组温差大于设定值",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#1m",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_08_013": {
- "subsystem": "Generator",
- "name": "SC_TempGenStatorU_high",
- "en": "Temperature of generator stator U coil is too high",
- "cn": "发电机定子U相绕组温度过高警告",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "3",
- "repeat_period": "T#24h",
- "trigger_en": "The 1min-mean-value of the temperature exceeds the value given by parameter.(grTempGenStatorU_1min > PAR_rTempHigh_GenStator)",
- "trigger_cn": "发电机定子U相绕组温度(1分钟平均值)高于设定值。(grTempGenStatorU_1min > PAR_rTempHigh_GenStator)",
- "set_delay": "T#1m",
- "yp": "0",
- "reset_en": "The 1min-mean-value of temperature falls below the value given by parameter minus a hysteresis value OR get reset signal of status code coming from Nacelle, Tower or Remote Command.(grTempGenStatorU_1min < (PAR_rTempHigh_GenStator -PAR_rTempHysteresisUpperTemp) OR gbMAIN_ResetStatusCodes=1)",
- "reset_cn": "发电机定子U相绕组温度(1分钟平均值)小于设定值减去一个滞后值或收到reset信号。(grTempGenStatorU_1min < (PAR_rTempHigh_GenStator - PAR_rTempHysteresisUpperTemp) OR gbMAIN_ResetStatusCodes=1)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_08_014": {
- "subsystem": "Generator",
- "name": "SC_TempGenStatorU_low",
- "en": "Temperature of generator stator U coil is too low",
- "cn": "发电机定子U相绕组温度过低警告",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "3",
- "repeat_period": "T#24h",
- "trigger_en": "The 1min-mean-value of the temperature falls below the value given by parameter.(grTempGenStatorU_1min < PAR_rTempLow_GenStator)",
- "trigger_cn": "发电机定子U相绕组1分钟平均温度低于设定值。(grTempGenStatorU_1min < PAR_rTempLow_GenStator)",
- "set_delay": "T#1m",
- "yp": "0",
- "reset_en": "The 1min-mean-value of temperature increases above the value given by parameter plus a hysteresis value OR get reset signal of status code coming from Nacelle, Tower or Remote Command.(grTempGenStatorU_1min > (PAR_rTempLow_GenStator + PAR_rTempHysteresisLowerTemp) OR gbMAIN_ResetStatusCodes=1)",
- "reset_cn": "发电机定子U相绕组温度(1分钟平均值)大于设定值加上一个滞后值或收到reset信号。(grTempGenStatorU_1min > (PAR_rTempLow_GenStator + PAR_rTempHysteresisLowerTemp) OR gbMAIN_ResetStatusCodes=1)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_08_015": {
- "subsystem": "Generator",
- "name": "SC_TempGenStatorU_MAX",
- "en": "Temperature of generator stator U coil exceeds maximum limit",
- "cn": "发电机定子U相绕组温度过高故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The 1min-mean-value of the temperature exceeds the maximum limit value given by parameter.(grTempGenStatorU_1min > PAR_rTempMAX_GenStator)_x000D_",
- "trigger_cn": "发电机定子U相绕组1分钟平均温度高于上限值。(grTempGenStatorU_1min > PAR_rTempMAX_GenStator)_x000D_",
- "set_delay": "T#1m",
- "yp": "0",
- "reset_en": "The 1min-mean-value of temperature falls below the value given by parameter minus a hysteresis value OR get reset signal of status code coming from Nacelle, Tower or Remote Command.(grTempGenStatorU_1min < (PAR_rTempMAX_GenStator - PAR_rTempHysteresisUpperTemp) OR gbMAIN_ResetStatusCodes=1)_x000D_",
- "reset_cn": "发电机定子U相绕组温度(1分钟平均值)小于设定值减去一个滞后值或收到reset信号。(grTempGenStatorU_1min < (PAR_rTempMAX_GenStator - PAR_rTempHysteresisUpperTemp) OR gbMAIN_ResetStatusCodes=1)_x000D_",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_08_016": {
- "subsystem": "Generator",
- "name": "SC_TempGenStatorU_min",
- "en": "Temperature of generator stator U coil exceeds minimum limit",
- "cn": "发电机定子U相绕组温度过低故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The 1min-mean-value of the temperature falls below the minimum limit value given by parameter.(grTempGenStatorU_1min < PAR_rTempMIN_GenStator)",
- "trigger_cn": "发电机定子U相绕组1分钟平均温度低于下限值。(grTempGenStatorU_1min < PAR_rTempMIN_GenStator)",
- "set_delay": "T#1m",
- "yp": "0",
- "reset_en": "The 1min-mean-value of temperature increases above the value given by parameter plus a hysteresis value OR get reset signal of status code coming from Nacelle, Tower or Remote Command.(grTempGenStatorU_1min > (PAR_rTempMIN_GenStator + PAR_rTempHysteresisLowerTemp) OR gbMAIN_ResetStatusCodes=1)",
- "reset_cn": "发电机定子U相绕组温度(1分钟平均值)大于最小值加上一个滞后值或收到reset信号。(grTempGenStatorU_1min > (PAR_rTempMIN_GenStator + PAR_rTempHysteresisLowerTemp) OR gbMAIN_ResetStatusCodes=1)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "50"
- },
- "02_08_017": {
- "subsystem": "Generator",
- "name": "SC_TempGenStatorV_high",
- "en": "Temperature of generator stator V coil is too high",
- "cn": "发电机定子V相绕组温度过高警告",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "3",
- "repeat_period": "T#24h",
- "trigger_en": "The 1min-mean-value of the temperature exceeds the value given by parameter.(grTempGenStatorV_1min > PAR_rTempHigh_GenStator)",
- "trigger_cn": "发电机定子V相绕组温度(1分钟平均值)高于设定值。(grTempGenStatorV_1min > PAR_rTempHigh_GenStator)",
- "set_delay": "T#1m",
- "yp": "0",
- "reset_en": "_x000D_ The 1min-mean-value of temperature falls below the value given by parameter minus a hysteresis value OR get reset signal of status code coming from Nacelle, Tower or Remote Command.(grTempGenStatorV_1min < (PAR_rTempHigh_GenStator -PAR_rTempHysteresisUpperTemp) OR gbMAIN_ResetStatusCodes=1)_x000D_",
- "reset_cn": "发电机定子V相绕组温度(1分钟平均值)小于设定值减去一个滞后值或收到reset信号。(grTempGenStatorV_1min < (PAR_rTempHigh_GenStator - PAR_rTempHysteresisUpperTemp) OR gbMAIN_ResetStatusCodes=1)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_08_018": {
- "subsystem": "Generator",
- "name": "SC_TempGenStatorV_low",
- "en": "Temperature of generator stator V coil is too low",
- "cn": "发电机定子V相绕组温度过低警告",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "3",
- "repeat_period": "T#24h",
- "trigger_en": "The 1min-mean-value of the temperature falls below the value given by parameter.(grTempGenStatorV_1min < PAR_rTempLow_GenStator)",
- "trigger_cn": "发电机定子V相绕组1分钟平均温度低于设定值。(grTempGenStatorV_1min < PAR_rTempLow_GenStator)",
- "set_delay": "T#1m",
- "yp": "0",
- "reset_en": "The 1min-mean-value of temperature increases above the value given by parameter plus a hysteresis value OR get reset signal of status code coming from Nacelle, Tower or Remote Command.(grTempGenStatorV_1min > (PAR_rTempLow_GenStator + PAR_rTempHysteresisLowerTemp) OR gbMAIN_ResetStatusCodes=1)",
- "reset_cn": "发电机定子V相绕组温度(1分钟平均值)大于设定值加上一个滞后值或收到reset信号。(grTempGenStatorV_1min > (PAR_rTempLow_GenStator + PAR_rTempHysteresisLowerTemp) OR gbMAIN_ResetStatusCodes=1)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_08_019": {
- "subsystem": "Generator",
- "name": "SC_TempGenStatorV_MAX",
- "en": "Temperature of generator stator V coil exceeds maximum limit",
- "cn": "发电机定子V相绕组温度过高故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The 1min-mean-value of the temperature exceeds the maximum limit value given by parameter.(grTempGenStatorV_1min > PAR_rTempMAX_GenStator)_x000D_",
- "trigger_cn": "发电机定子V相绕组1分钟平均温度高于上限值。(grTempGenStatorV_1min > PAR_rTempMAX_GenStator)",
- "set_delay": "T#1m",
- "yp": "0",
- "reset_en": "The 1min-mean-value of temperature falls below the value given by parameter minus a hysteresis value OR get reset signal of status code coming from Nacelle, Tower or Remote Command.(grTempGenStatorV_1min < (PAR_rTempMAX_GenStator - PAR_rTempHysteresisUpperTemp) OR gbMAIN_ResetStatusCodes=1)",
- "reset_cn": "发电机定子V相绕组温度(1分钟平均值)小于设定值减去一个滞后值或收到reset信号。(grTempGenStatorV_1min < (PAR_rTempMAX_GenStator - PAR_rTempHysteresisUpperTemp) OR gbMAIN_ResetStatusCodes=1)",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_08_020": {
- "subsystem": "Generator",
- "name": "SC_TempGenStatorV_MIN",
- "en": "Temperature of generator stator V coil exceeds minimum limit",
- "cn": "发电机定子V相绕组温度过低故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The 1min-mean-value of the temperature falls below the minimum limit value given by parameter.(grTempGenStatorV_1min < PAR_rTempMIN_GenStator)",
- "trigger_cn": "发电机定子V相绕组1分钟平均温度低于下限值。(grTempGenStatorV_1min < PAR_rTempMIN_GenStator)",
- "set_delay": "T#1m",
- "yp": "0",
- "reset_en": "The 1min-mean-value of temperature increases above the value given by parameter plus a hysteresis value OR get reset signal of status code coming from Nacelle, Tower or Remote Command.(grTempGenStatorV_1min > (PAR_rTempMIN_GenStator + PAR_rTempHysteresisLowerTemp) OR gbMAIN_ResetStatusCodes=1)",
- "reset_cn": "发电机定子V相绕组温度(1分钟平均值)大于最小值加上一个滞后值或收到reset信号。(grTempGenStatorV_1min > (PAR_rTempMIN_GenStator + PAR_rTempHysteresisLowerTemp) OR gbMAIN_ResetStatusCodes=1)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "50"
- },
- "02_08_021": {
- "subsystem": "Generator",
- "name": "SC_TempGenStatorW_high",
- "en": "Temperature of generator stator W coil is too high",
- "cn": "发电机定子W相绕组温度过高警告",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "3",
- "repeat_period": "T#24h",
- "trigger_en": "The 1min-mean-value of the temperature exceeds the value given by parameter.(grTempGenStatorW_1min >PAR_rTempHigh_GenStator)",
- "trigger_cn": "发电机定子W相绕组温度(1分钟平均值)高于设定值。(grTempGenStatorW_1min >PAR_rTempHigh_GenStator)",
- "set_delay": "T#1m",
- "yp": "0",
- "reset_en": "The 1min-mean-value of temperature falls below the value given by parameter minus a hysteresis value OR get reset signal of status code coming from Nacelle, Tower or Remote Command.(grTempGenStatorW_1min < (PAR_rTempHigh_GenStator -PAR_rTempHysteresisUpperTemp) OR gbMAIN_ResetStatusCodes=1)_x000D_",
- "reset_cn": "发电机定子W相绕组温度(1分钟平均值)小于设定值减去一个滞后值或收到reset信号。(grTempGenStatorW_1min < (PAR_rTempHigh_GenStator - PAR_rTempHysteresisUpperTemp) OR gbMAIN_ResetStatusCodes=1)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_08_022": {
- "subsystem": "Generator",
- "name": "SC_TempGenStatorW_low",
- "en": "Temperature of generator stator W coil is too low",
- "cn": "发电机定子W相绕组温度过低警告",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "3",
- "repeat_period": "T#24h",
- "trigger_en": "The 1min-mean-value of the temperature falls below the value given by parameter.(grTempGenStatorW_1min < PAR_rTempLow_GenStator)",
- "trigger_cn": "发电机定子W相绕组1分钟平均温度低于设定值。(grTempGenStatorW_1min < PAR_rTempLow_GenStator)",
- "set_delay": "T#1m",
- "yp": "0",
- "reset_en": "The 1min-mean-value of temperature increases above the value given by parameter plus a hysteresis value OR get reset signal of status code coming from Nacelle, Tower or Remote Command.(grTempGenStatorW_1min > (PAR_rTempLow_GenStator + PAR_rTempHysteresisLowerTemp) OR gbMAIN_ResetStatusCodes=1)",
- "reset_cn": "发电机定子W相绕组温度(1分钟平均值)大于设定值加上一个滞后值或收到reset信号。(grTempGenStatorW_1min > (PAR_rTempLow_GenStator + PAR_rTempHysteresisLowerTemp) OR gbMAIN_ResetStatusCodes=1)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_08_023": {
- "subsystem": "Generator",
- "name": "SC_TempGenStatorW_MAX",
- "en": "Temperature of generator stator W coil exceeds maximum limit",
- "cn": "发电机定子W相绕组温度过高故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The 1min-mean-value of the temperature exceeds the maximum limit value given by parameter.(grTempGenStatorW_1min > PAR_rTempMAX_GenStator)",
- "trigger_cn": "发电机定子W相绕组1分钟平均温度高于上限值。(grTempGenStatorW_1min > PAR_rTempMAX_GenStator)",
- "set_delay": "T#1m",
- "yp": "0",
- "reset_en": "The 1min-mean-value of temperature falls below the value given by parameter minus a hysteresis value OR get reset signal of status code coming from Nacelle, Tower or Remote Command.(grTempGenStatorW_1min < (PAR_rTempMAX_GenStator - PAR_rTempHysteresisUpperTemp) OR gbMAIN_ResetStatusCodes=1)",
- "reset_cn": "发电机定子W相绕组温度(1分钟平均值)小于设定值减去一个滞后值或收到reset信号。(grTempGenStatorW_1min < (PAR_rTempMAX_GenStator - PAR_rTempHysteresisUpperTemp) OR gbMAIN_ResetStatusCodes=1)",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_08_024": {
- "subsystem": "Generator",
- "name": "SC_TempGenStatorW_MIN",
- "en": "Temperature of generator stator W coil exceeds minimum limit",
- "cn": "发电机定子W相绕组温度过低故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The 1min-mean-value of the temperature falls below the minimum limit value given by parameter.(grTempGenStatorW_1min < PAR_rTempMIN_GenStator)",
- "trigger_cn": "发电机定子W相绕组1分钟平均温度低于下限值。(grTempGenStatorW_1min < PAR_rTempMIN_GenStator)",
- "set_delay": "T#1m",
- "yp": "0",
- "reset_en": "The 1min-mean-value of temperature increases above the value given by parameter plus a hysteresis value OR get reset signal of status code coming from Nacelle, Tower or Remote Command.(grTempGenStatorW_1min > (PAR_rTempMIN_GenStator + PAR_rTempHysteresisLowerTemp) OR gbMAIN_ResetStatusCodes=1)",
- "reset_cn": "发电机定子W相绕组温度(1分钟平均值)大于最小值加上一个滞后值或收到reset信号。(grTempGenStatorW_1min > (PAR_rTempMIN_GenStator + PAR_rTempHysteresisLowerTemp) OR gbMAIN_ResetStatusCodes=1)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "50"
- },
- "02_08_025": {
- "subsystem": "Generator",
- "name": "SC_RepFaultTempGenStator",
- "en": "The faults, generator stator coils temperature is too high or too low, have repeated.",
- "cn": "发电机定子绕组温度过高或过低警告重复出现",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "One of the statuscodes for the referred temperature for \"temperature too high\" or \"temperature too low\" in a given time periode becomes more times TRUE than maximum allowed.(gbRepeat_02_08_013=1 OR gbRepeat_02_08_017=1 OR gbRepeat_02_08_021=1 OR gbRepeat_02_08_014=1 OR gbRepeat_02_08_018=1 OR gbRepeat_02_08_022=1)",
- "trigger_cn": "发电机定子线圈温度过高或过低故障重复出现。(gbRepeat_02_08_013=1 OR gbRepeat_02_08_017=1 OR gbRepeat_02_08_021=1 OR gbRepeat_02_08_014=1 OR gbRepeat_02_08_018=1 OR gbRepeat_02_08_022=1)",
- "set_delay": "T#1m",
- "yp": "0",
- "reset_en": "One of the statuscodes for the referred temperature for \"temperature too high\" or \"temperature too low\" in a given time periode becomes less times TRUE than maximum allowed.(gbRepeat_02_08_013=0 AND gbRepeat_02_08_017=0 AND gbRepeat_02_08_021=0 AND gbRepeat_02_08_014=0 AND gbRepeat_02_08_018=0 AND gbRepeat_02_08_022=0)",
- "reset_cn": "发电机定子线圈温度过高或过低故障不重复出现。(gbRepeat_02_08_013=0 AND gbRepeat_02_08_017=0 AND gbRepeat_02_08_021=0 AND gbRepeat_02_08_014=0 AND gbRepeat_02_08_018=0 AND gbRepeat_02_08_022=0)",
- "reset_mode": "M",
- "type": "A",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_08_026": {
- "subsystem": "Generator",
- "name": "SC_TempGenBearingDE_high",
- "en": "Temperature of generator drive-end bearing is too high",
- "cn": "发电机驱动端轴承温度过高警告",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "3",
- "repeat_period": "T#24h",
- "trigger_en": "The 1min-mean-value of the temperature exceeds the value given by parameter.(grTempGenBearingDE_1min >PAR_rTempHigh_GenBearDE)",
- "trigger_cn": "发电机驱动端轴承1分钟平均温度高于设定值。(grTempGenBearingDE_1min >PAR_rTempHigh_GenBearDE)",
- "set_delay": "T#1m",
- "yp": "0",
- "reset_en": "The 1min-mean-value of temperature falls below the value given by parameter minus a hysteresis value OR get reset signal of status code coming from Nacelle, Tower or Remote Command.(grTempGenBearingDE_1min < (PAR_rTempHigh_GenBearDE - PAR_rTempHysteresisUpperTemp) OR gbMAIN_ResetStatusCodes=1)_x000D_",
- "reset_cn": "发电机驱动端轴承温度(1分钟平均值)小于设定值减去一个滞后值或收到reset信号。(grTempGenBearingDE_1min < (PAR_rTempHigh_GenBearDE - PAR_rTempHysteresisUpperTemp) OR gbMAIN_ResetStatusCodes=1)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_08_027": {
- "subsystem": "Generator",
- "name": "SC_TempGenBearingDE_low",
- "en": "Temperature of generator drive-end bearing is too low",
- "cn": "发电机驱动端轴承温度过低警告",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "3",
- "repeat_period": "T#24h",
- "trigger_en": "The 1min-mean-value of the temperature falls below the value given by parameter.(grTempGenBearingDE_1min < PAR_rTempLow_GenBearDE)",
- "trigger_cn": "发电机驱动端轴承1分钟平均温度低于设定值。(grTempGenBearingDE_1min < PAR_rTempLow_GenBearDE)",
- "set_delay": "T#1m",
- "yp": "0",
- "reset_en": "The 1min-mean-value of temperature increases above the value given by parameter plus a hysteresis value OR get reset signal of status code coming from Nacelle, Tower or Remote Command.(grTempGenBearingDE_1min > (PAR_rTempLow_GenBearDE + PAR_rTempHysteresisLowerTemp) OR gbMAIN_ResetStatusCodes=1)",
- "reset_cn": "发电机驱动端轴承温度(1分钟平均值)大于设定值加上一个滞后值或收到reset信号。(grTempGenBearingDE_1min > (PAR_rTempLow_GenBearDE + PAR_rTempHysteresisLowerTemp) OR gbMAIN_ResetStatusCodes=1)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_08_028": {
- "subsystem": "Generator",
- "name": "SC_TempGenBearingDE_MAX",
- "en": "Temperature of generator drive-end bearing exceeds maximum limit",
- "cn": "发电机驱动端轴承温度过高故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The 1min-mean-value of the temperature exceeds the maximum limit.(grTempGenBearingDE_1min > PAR_rTempMAX_GenBearDE)",
- "trigger_cn": "发电机驱动端轴承1分钟平均温度高于设定值。(grTempGenBearingDE_1min > PAR_rTempMAX_GenBearDE)",
- "set_delay": "T#1m",
- "yp": "0",
- "reset_en": "The 1min-mean-value of temperature falls below the value given by parameter minus a hysteresis value OR get reset signal of status code coming from Nacelle, Tower or Remote Command.(grTempGenBearingDE_1min < (PAR_rTempMAX_GenBearDE - PAR_rTempHysteresisUpperTemp) OR gbMAIN_ResetStatusCodes=1)",
- "reset_cn": "发电机驱动端轴承温度(1分钟平均值)小于设定值减去一个滞后值或收到reset信号。(grTempGenBearingDE_1min < (PAR_rTempMAX_GenBearDE - PAR_rTempHysteresisUpperTemp) OR gbMAIN_ResetStatusCodes=1)",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_08_029": {
- "subsystem": "Generator",
- "name": "SC_TempGenBearingDE_MIN",
- "en": "Temperature of generator drive-end bearing exceeds minimum limit",
- "cn": "发电机驱动端轴承温度过低故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The 1min-mean-value of the temperature falls below the minimum limit value given by parameter.(grTempGenBearingDE_1min < PAR_rTempMIN_GenBearDE)",
- "trigger_cn": "发电机驱动端轴承1分钟平均温度低于下限值。(grTempGenBearingDE_1min < PAR_rTempMIN_GenBearDE)",
- "set_delay": "T#1m",
- "yp": "0",
- "reset_en": "The 1min-mean-value of temperature increases above the value given by parameter plus a hysteresis value OR get reset signal of status code coming from Nacelle, Tower or Remote Command.(grTempGenBearingDE_1min > (PAR_rTempMIN_GenBearDE + PAR_rTempHysteresisLowerTemp) OR gbMAIN_ResetStatusCodes=1)",
- "reset_cn": "发电机驱动端轴承温度(1分钟平均值)大于最小值加上一个滞后值或收到reset信号。(grTempGenBearingDE_1min > (PAR_rTempMIN_GenBearDE + PAR_rTempHysteresisLowerTemp) OR gbMAIN_ResetStatusCodes=1)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "50"
- },
- "02_08_030": {
- "subsystem": "Generator",
- "name": "SC_TempGenBearingNDE_high",
- "en": "Temperature of generator non-drive-end bearing is too high",
- "cn": "发电机非驱动端轴承温度过高警告",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "3",
- "repeat_period": "T#24h",
- "trigger_en": "The 1min-mean-value of the temperature exceeds the value given by parameter.(grTempGenBearingNDE_1min > PAR_rTempHigh_GenBearNDE)",
- "trigger_cn": "发电机非驱动端轴承1分钟平均温度高于设定值。(grTempGenBearingNDE_1min > PAR_rTempHigh_GenBearNDE)",
- "set_delay": "T#1m",
- "yp": "0",
- "reset_en": "The 1min-mean-value of temperature falls below the value given by parameter minus a hysteresis value OR get reset signal of status code coming from Nacelle, Tower or Remote Command.(grTempGenBearingDE_1min < (PAR_rTempHigh_GenBearNDE - PAR_rTempHysteresisUpperTemp) OR gbMAIN_ResetStatusCodes=1)",
- "reset_cn": "发电机非驱动端轴承温度(1分钟平均值)小于设定值减去一个滞后值或收到reset信号。(grTempGenBearingNDE_1min < (PAR_rTempHigh_GenBearDE - PAR_rTempHysteresisUpperTemp) OR gbMAIN_ResetStatusCodes=1)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_08_031": {
- "subsystem": "Generator",
- "name": "SC_TempGenBearingNDE_low",
- "en": "Temperature of generator non-drive-end bearing is too low",
- "cn": "发电机非驱动端轴承温度过低警告",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "3",
- "repeat_period": "T#24h",
- "trigger_en": "The 1min-mean-value of the temperature falls below the value given by parameter.(grTempGenBearingNDE_1min < PAR_rTempLow_GenBearNDE)",
- "trigger_cn": "发电机非驱动端轴承1分钟平均温度低于设定值。(grTempGenBearingNDE_1min < PAR_rTempLow_GenBearNDE)",
- "set_delay": "T#1m",
- "yp": "0",
- "reset_en": "The 1min-mean-value of temperature increases above the value given by parameter plus a hysteresis value OR get reset signal of status code coming from Nacelle, Tower or Remote Command.(grTempGenBearingNDE_1min > (PAR_rTempLow_GenBearNDE + PAR_rTempHysteresisLowerTemp) OR gbMAIN_ResetStatusCodes=1)",
- "reset_cn": "发电机非驱动端轴承温度(1分钟平均值)大于设定值加上一个滞后值或收到reset信号。(grTempGenBearingNDE_1min > (PAR_rTempLow_GenBearNDE + PAR_rTempHysteresisLowerTemp) OR gbMAIN_ResetStatusCodes=1)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_08_032": {
- "subsystem": "Generator",
- "name": "SC_TempGenBearingNDE_MAX",
- "en": "Temperature of generator non-drive-end bearing exceeds maximum limit",
- "cn": "发电机非驱动端轴承温度过高故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The 1min-mean-value of the temperature exceeds the maximum limit value given by parameter.(grTempGenBearingNDE_1min > PAR_rTempMAX_GenBearNDE)",
- "trigger_cn": "发电机非驱动端轴承1分钟平均温度高于上限值。(grTempGenBearingNDE_1min > PAR_rTempMAX_GenBearNDE)",
- "set_delay": "T#1m",
- "yp": "0",
- "reset_en": "The 1min-mean-value of temperature falls below the value given by parameter minus a hysteresis value OR get reset signal of status code coming from Nacelle, Tower or Remote Command.(grTempGenBearingNDE_1min < (PAR_rTempMAX_GenBearNDE - PAR_rTempHysteresisUpperTemp) OR gbMAIN_ResetStatusCodes)_x000D_",
- "reset_cn": "发电机非驱动端轴承温度(1分钟平均值)小于设定值减去一个滞后值或收到reset信号。(grTempGenBearingNDE_1min < (PAR_rTempMAX_GenBearNDE - PAR_rTempHysteresisUpperTemp) OR gbMAIN_ResetStatusCodes)",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_08_033": {
- "subsystem": "Generator",
- "name": "SC_TempGenBearingNDE_MIN",
- "en": "Temperature of generator non-drive-end bearing exceeds minimum limit",
- "cn": "发电机非驱动端轴承温度过低故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The 1min-mean-value of the temperature falls below the minimum limit value given by parameter.(grTempGenBearingNDE_1min < PAR_rTempMIN_GenBearNDE)",
- "trigger_cn": "发电机非驱动端轴承1分钟平均温度低于下限值。(grTempGenBearingNDE_1min < PAR_rTempMIN_GenBearNDE)",
- "set_delay": "T#1m",
- "yp": "0",
- "reset_en": "The 1min-mean-value of temperature increases above the value given by parameter plus a hysteresis value OR get reset signal of status code coming from Nacelle, Tower or Remote Command.(grTempGenBearingNDE_1min > (PAR_rTempMIN_GenBearNDE + PAR_rTempHysteresisLowerTemp) OR gbMAIN_ResetStatusCodes=1)",
- "reset_cn": "发电机非驱动端轴承温度(1分钟平均值)大于最小值加上一个滞后值或收到reset信号。(grTempGenBearingNDE_1min > (PAR_rTempMIN_GenBearNDE + PAR_rTempHysteresisLowerTemp) OR gbMAIN_ResetStatusCodes=1)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "50"
- },
- "02_08_034": {
- "subsystem": "Generator",
- "name": "SC_RepFaultTempGenBearing",
- "en": "The faults, generator bearing temperature is too high or too low, have repeated",
- "cn": "发电机轴承温度过高或过低警告重复出现",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "One of the statuscodes for the referred temperature for \"temperature too high\" or \"temperature too low\" in a given time periode becomes more times TRUE than maximum allowed.(gbRepeat_02_08_026=1 OR gbRepeat_02_08_027=1 OR gbRepeat_02_08_030=1 OR gbRepeat_02_08_031=1)",
- "trigger_cn": "发电机轴承温度过高或过低故障重复出现。(gbRepeat_02_08_026=1 OR gbRepeat_02_08_027=1 OR gbRepeat_02_08_030=1 OR gbRepeat_02_08_031=1)",
- "set_delay": "T#1m",
- "yp": "0",
- "reset_en": "One of the statuscodes for the referred temperature for \"temperature too high\" or \"temperature too low\" in a given time periode becomes less times TRUE than maximum allowed.(gbRepeat_02_08_026=0 AND gbRepeat_02_08_027=0 AND gbRepeat_02_08_030=0 AND gbRepeat_02_08_031=0)",
- "reset_cn": "发电机轴承温度过高和过低故障不重复出现。(gbRepeat_02_08_026=0 AND gbRepeat_02_08_027=0 AND gbRepeat_02_08_030=0 AND gbRepeat_02_08_031=0)",
- "reset_mode": "M",
- "type": "A",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_08_035": {
- "subsystem": "Generator",
- "name": "SC_TempGenCoolingInletOrOutlet_high",
- "en": "Temperature of generator cooling inlet or outlet is too high",
- "cn": "发电机冷却系统入口或出口温度过高警告",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "3",
- "repeat_period": "T#24h",
- "trigger_en": "1min-mean-value temperature of generator cooling inlet or outlet exceeds the value given by parameter.(grTempGenCoolingInlet_1min > PAR_rTempHigh_GenCoolingInlet OR grTempGenCoolingOutlet_1min > PAR_rTempHigh_GenCoolingOutlet)",
- "trigger_cn": "发电机冷却系统入口或出口1分钟平均温度高于设定值。(grTempGenCoolingInlet_1min > PAR_rTempHigh_GenCoolingInlet OR grTempGenCoolingOutlet_1min > PAR_rTempHigh_GenCoolingOutlet)",
- "set_delay": "T#1m",
- "yp": "0",
- "reset_en": "The 1min-mean-value of temperature falls below the value given by parameter minus a hysteresis value OR get reset signal of status code coming from Nacelle, Tower or Remote Command.(grTempGenCoolingInlet_1min < (PAR_rTempHigh_GenCoolingInlet - PAR_rTempHysteresisUpperTemp) AND grTempGenCoolingOutlet_1min < (PAR_rTempHigh_GenCoolingOutlet - PAR_rTempHysteresisUpperTemp)) OR gbMAIN_ResetStatusCodes=1",
- "reset_cn": "发电机冷却系统入口和出口温度(1分钟平均值)小于设定值减去一个滞后值或收到reset信号。(grTempGenCoolingInlet_1min < (PAR_rTempHigh_GenCoolingInlet - PAR_rTempHysteresisUpperTemp) AND grTempGenCoolingOutlet_1min < (PAR_rTempHigh_GenCoolingOutlet - PAR_rTempHysteresisUpperTemp)) OR gbMAIN_ResetStatusCodes=1",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_08_036": {
- "subsystem": "Generator",
- "name": "SC_TempGenCoolingInletOrOutlet_low",
- "en": "Temperature of generator cooling inlet or outlet is too low",
- "cn": "发电机冷却系统入口或出口温度过低警告",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "3",
- "repeat_period": "T#24h",
- "trigger_en": "1min-mean-value temperature of generator cooling inlet or outlet falls below the value given by parameter.(grTempGenCoolingInlet_1min < PAR_rTempLow_GenCoolingInlet OR grTempGenCoolingOutlet_1min < PAR_rTempLow_GenCoolingOutlet)",
- "trigger_cn": "发电机冷却系统入口或出口1分钟平均温度低于设定值。(grTempGenCoolingInlet_1min < PAR_rTempLow_GenCoolingInlet OR grTempGenCoolingOutlet_1min < PAR_rTempLow_GenCoolingOutlet)",
- "set_delay": "T#1m",
- "yp": "0",
- "reset_en": "The 1min-mean-value of temperature increases above the value given by parameter plus a hysteresis value OR get reset signal of status code coming from Nacelle, Tower or Remote Command.(grTempGenCoolingInlet_1min > (PAR_rTempLow_GenCoolingInlet + PAR_rTempHysteresisLowerTemp) AND grTempGenCoolingOutlet_1min > (PAR_rTempLow_GenCoolingOutlet + PAR_rTempHysteresisLowerTemp)) OR gbMAIN_ResetStatusCodes=1",
- "reset_cn": "发电机冷却系统入口和出口温度(1分钟平均值)大于设定值加上一个滞后值或收到reset信号。(grTempGenCoolingInlet_1min > (PAR_rTempLow_GenCoolingInlet + PAR_rTempHysteresisLowerTemp) AND grTempGenCoolingOutlet_1min > (PAR_rTempLow_GenCoolingOutlet + PAR_rTempHysteresisLowerTemp)) OR gbMAIN_ResetStatusCodes=1",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_08_037": {
- "subsystem": "Generator",
- "name": "SC_TempGenCoolingInletOrOutlet_MAX",
- "en": "Temperature of generator cooling inlet or outlet exceeds maximum limit",
- "cn": "发电机冷却系统入口或出口温度过高故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "1min-mean-value temperature of generator cooling inlet or outlet exceeds the maximum limit value given by parameter.(grTempGenCoolingInlet_1min > PAR_rTempMAX_GenCoolingInlet) OR (grTempGenCoolingOutlet_1min > PAR_rTempMAX_GenCoolingOutlet)",
- "trigger_cn": "发电机冷却系统入口或出口1分钟平均温度高于上限值。(grTempGenCoolingInlet_1min > PAR_rTempMAX_GenCoolingInlet) OR (grTempGenCoolingOutlet_1min > PAR_rTempMAX_GenCoolingOutlet)",
- "set_delay": "T#1m",
- "yp": "0",
- "reset_en": "The 1min-mean-value of temperature falls below the value given by parameter minus a hysteresis value OR get reset signal of status code coming from Nacelle, Tower or Remote Command.(grTempGenCoolingInlet_1min <(PAR_rTempMAX_GenCoolingInlet - PAR_rTempHysteresisUpperTemp) AND grTempGenCoolingOutlet_1min < (PAR_rTempMAX_GenCoolingOutlet - PAR_rTempHysteresisUpperTemp)) OR gbMAIN_ResetStatusCodes=1",
- "reset_cn": "发电机冷却系统入口和出口温度(1分钟平均值)小于上限值减去一个滞后值或收到reset信号。(grTempGenCoolingInlet_1min <(PAR_rTempMAX_GenCoolingInlet - PAR_rTempHysteresisUpperTemp) AND grTempGenCoolingOutlet_1min < (PAR_rTempMAX_GenCoolingOutlet - PAR_rTempHysteresisUpperTemp)) OR gbMAIN_=1",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_08_038": {
- "subsystem": "Generator",
- "name": "SC_TempGenCoolingInletOrOutlet_MIN",
- "en": "Temperature of generator cooling inlet or outlet exceeds minimum limit",
- "cn": "发电机冷却系统入口或出口温度过低故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "1min-mean-value temperature of generator cooling inlet or outlet falls below the minimum limit value given by parameter.(grTempGenCoolingInlet_1min < PAR_rTempMIN_GenCoolingInlet) OR (grTempGenCoolingOutlet_1min < PAR_rTempMIN_GenCoolingOutlet)",
- "trigger_cn": "发电机冷却系统入口或出口1分钟平均温度低于下限值。(grTempGenCoolingInlet_1min < PAR_rTempMIN_GenCoolingInlet) OR (grTempGenCoolingOutlet_1min < PAR_rTempMIN_GenCoolingOutlet)",
- "set_delay": "T#1m",
- "yp": "0",
- "reset_en": "The 1min-mean-value of temperature increases above the value given by parameter plus a hysteresis value OR get reset signal of status code coming from Nacelle, Tower or Remote Command.(grTempGenCoolingInlet_1min > (PAR_rTempMIN_GenCoolingInlet + PAR_rTempHysteresisLowerTemp) AND grTempGenCoolingOutlet_1min > (PAR_rTempMIN_GenCoolingOutlet + PAR_rTempHysteresisLowerTemp)) OR gbMAIN_ResetStatusCodes=1",
- "reset_cn": "发电机冷却系统入口和出口温度(1分钟平均值)大于下限值加上一个滞后值或收到reset信号。(grTempGenCoolingInlet_1min > (PAR_rTempMIN_GenCoolingInlet + PAR_rTempHysteresisLowerTemp) AND grTempGenCoolingOutlet_1min > (PAR_rTempMIN_GenCoolingOutlet + PAR_rTempHysteresisLowerTemp)) OR gbMAIN_ResetStatusCodes=1",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "50"
- },
- "02_08_039": {
- "subsystem": "Generator",
- "name": "SC_RepFaultTempGenCoolingInletOrOutlet",
- "en": "The faults, generator cooling inlet or outlet temperature is too high or too low, have repeated",
- "cn": "发电机冷却系统入口或出口温度过高或过低警告重复出现",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "One of the statuscodes for the referred temperature for \"temperature too high\" or \"temperature too low\" in a given time periode becomes more times TRUE than maximum allowed.(gbRepeat_02_08_035=1 OR gbRepeat_02_08_036=1)",
- "trigger_cn": "发电机冷却系统入口或出口温度多高过低故障重复出现。(gbRepeat_02_08_035=1 OR gbRepeat_02_08_036=1)",
- "set_delay": "T#1m",
- "yp": "0",
- "reset_en": "One of the statuscodes for the referred temperature for \"temperature too high\" or \"temperature too low\" in a given time periode becomes less times TRUE than maximum allowed.(gbRepeat_02_08_035=0 AND gbRepeat_02_08_036=0)",
- "reset_cn": "发电机冷却系统入口和出口温度多高过低故障不重复出现。(gbRepeat_02_08_035=0 AND gbRepeat_02_08_036=0)",
- "reset_mode": "M",
- "type": "A",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_08_042": {
- "subsystem": "Generator",
- "name": "SC_FaultPT100_GenCoolingInlet",
- "en": "Generator Cooling System Inlet PT100 Fault",
- "cn": "发电机冷却系统入口PT100传感器故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_08_043": {
- "subsystem": "Generator",
- "name": "SC_FaultPT100_GenCoolingOutlet",
- "en": "Generator Cooling System Outlet PT100 Fault",
- "cn": "发电机冷却系统出口PT100传感器故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_08_100": {
- "subsystem": "Generator",
- "name": "SC_TempGenStatorDewShortCircuit",
- "en": "Generator stator temperature is below dew point temperature",
- "cn": "发电机定子温度低于露点温度",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "All the following conditions are fullfilled:_x000D_ 1.(giTurbineOperationMode <> CON_iGridOperation) AND (grTempGenStatorU_1min < PAR_rTempGen_HeaterON OR grTempGenStatorV_1min < PAR_rTempGen_HeaterON OR grTempGenStatorW_1min < PAR_rTempGen_HeaterON)_x000D_ 2.(grTempGenStatorU_1min < grTempNacelle_1min + PAR_rTempHysteresisGenStatorDew) OR_x000D_ (grTempGenStatorV_1min < grTempNacelle_1min + PAR_rTempHysteresisGenStatorDew) OR_x000D_ (grTempGenStatorW_1min < grTempNacelle_1min + PAR_rTempHysteresisGenStatorDew) _x000D_",
- "trigger_cn": "满足以下所有条件:_x000D_ 1.风机未并网并且发电机定子U, V或W温度低于露点温度。(giTurbineOperationMode <> CON_iGridOperation) AND (grTempGenStatorU_1min < PAR_rTempGen_HeaterON OR grTempGenStatorV_1min < PAR_rTempGen_HeaterON OR grTempGenStatorW_1min < PAR_rTempGen_HeaterON)_x000D_ 2.发电机定子温度低于机舱温度加一个滞环温度参数_x000D_ (grTempGenStatorU_1min < grTempNacelle_1min + PAR_rTempHysteresisGenStatorDew) OR_x000D_ (grTempGenStatorV_1min < grTempNacelle_1min + PAR_rTempHysteresisGenStatorDew) OR_x000D_ (grTempGenStatorW_1min < grTempNacelle_1min + PAR_rTempHysteresisGenStatorDew)",
- "set_delay": "PAR_tGenStatorDewShortCircuit",
- "yp": "0",
- "reset_en": "condition 1 is not fullfilled or condition 1 is fullfilled and condition 3 is fullfilled. (Condition1 AND Condition3) OR (NOT Condition1)_x000D_ 1.(giTurbineOperationMode <> CON_iGridOperation) AND (grTempGenStatorU_1min < PAR_rTempGen_HeaterON OR grTempGenStatorV_1min < PAR_rTempGen_HeaterON OR grTempGenStatorW_1min < PAR_rTempGen_HeaterON)_x000D_ 2.(grTempGenStatorU_1min < grTempNacelle_1min + PAR_rTempHysteresisGenStatorDew) OR_x000D_ (grTempGenStatorV_1min < grTempNacelle_1min + PAR_rTempHysteresisGenStatorDew) OR_x000D_ (grTempGenStatorW_1min < grTempNacelle_1min + PAR_rTempHysteresisGenStatorDew) _x000D_ 3. ((grTempGenStatorU_1min > (grTempNacelle_1min + 2*PAR_rTempHysteresisGenStatorDew)) AND_x000D_ (grTempGenStatorV_1min > (grTempNacelle_1min + 2*PAR_rTempHysteresisGenStatorDew)) AND_x000D_ (grTempGenStatorW_1min > (grTempNacelle_1min + 2*PAR_rTempHysteresisGenStatorDew))) OR_x000D_ gbMAIN_ResetStatusCodes_x000D_",
- "reset_cn": "条件1满足且条件3满足或者条件1不满足。_x000D_ (Condition1 AND Condition3) OR (NOT Condition1)_x000D_ 1.风机未并网并且发电机定子U, V或W温度低于露点温度。(giTurbineOperationMode <> CON_iGridOperation) AND (grTempGenStatorU_1min < PAR_rTempGen_HeaterON OR grTempGenStatorV_1min < PAR_rTempGen_HeaterON OR grTempGenStatorW_1min < PAR_rTempGen_HeaterON)_x000D_ 2.发电机定子温度低于机舱温度加一个滞环温度参数_x000D_ (grTempGenStatorU_1min < grTempNacelle_1min + PAR_rTempHysteresisGenStatorDew) OR_x000D_ (grTempGenStatorV_1min < grTempNacelle_1min + PAR_rTempHysteresisGenStatorDew) OR_x000D_ (grTempGenStatorW_1min < grTempNacelle_1min + PAR_rTempHysteresisGenStatorDew) _x000D_ 3.发电机定子温度高于机舱温度加一个滞环温度参数_x000D_ ((grTempGenStatorU_1min > (grTempNacelle_1min + 2*PAR_rTempHysteresisGenStatorDew)) AND_x000D_ (grTempGenStatorV_1min > (grTempNacelle_1min + 2*PAR_rTempHysteresisGenStatorDew)) AND_x000D_ (grTempGenStatorW_1min > (grTempNacelle_1min + 2*PAR_rTempHysteresisGenStatorDew))) OR_x000D_ gbMAIN_ResetStatusCodes",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_06_001": {
- "subsystem": "Generator",
- "name": "SC_TempGenStatorU1Error",
- "en": "U1 PT100 Error",
- "cn": "发电机U相温度信号1错误,报警不停机",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_06_002": {
- "subsystem": "Generator",
- "name": "SC_TempGenStatorU2Error",
- "en": "U2 PT100 Error",
- "cn": "发电机U相温度信号2错误,报警不停机",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_06_003": {
- "subsystem": "Generator",
- "name": "OC_TempGenStatorU1U2DiffMax",
- "en": "Outputs of U1 and U2 is not equal",
- "cn": "发电机U相两PT100读书差值过大,报警不停机",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_06_005": {
- "subsystem": "Generator",
- "name": "SC_TempGenStatorV1Error",
- "en": "Generator Stator V1 PT100 Fault",
- "cn": "发电机V相温度信号1错误,报警不停机",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_06_006": {
- "subsystem": "Generator",
- "name": "SC_TempGenStatorV2Error",
- "en": "Generator Stator V2 PT100 Fault",
- "cn": "发电机V相温度信号2错误,报警不停机",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_06_007": {
- "subsystem": "Generator",
- "name": "OC_TempGenStatorV1V2DiffMax",
- "en": "Generator Stator V1 V2 Temp Diff Over Max Threshold",
- "cn": "发电机V相两PT100读书差值过大,报警不停机",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_06_009": {
- "subsystem": "Generator",
- "name": "SC_TempGenStatorW1Error",
- "en": "Generator Stator W1 PT100 Fault",
- "cn": "发电机W相温度信号1错误,报警不停机",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_06_010": {
- "subsystem": "Generator",
- "name": "SC_TempGenStatorW2Error",
- "en": "Generator Stator W2 PT100 Fault",
- "cn": "发电机W相温度信号2错误,报警不停机",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_06_011": {
- "subsystem": "Generator",
- "name": "OC_TempGenStatorW1W2DiffMax",
- "en": "Generator Stator W1 W2 Temp Diff Over Max Threshold",
- "cn": "发电机W相两PT100读书差值过大,报警不停机",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_06_013": {
- "subsystem": "Generator",
- "name": "OC_GENFanControlManualMode",
- "en": "Generator Fan Enter in ManualMode",
- "cn": "发电机风扇控制进入手动模式",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#50ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_06_014": {
- "subsystem": "Generator",
- "name": "OC_GENFanControlForcelMode",
- "en": "Generator Fan Enter in ForceMode",
- "cn": "发电机风扇控制进入强制模式",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#50ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_06_015": {
- "subsystem": "Generator",
- "name": "OC_GENHeaterControlManualMode",
- "en": "Generator Heater Enter in ManualMode",
- "cn": "发电机加热器控制进入手动模式",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#50ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_06_016": {
- "subsystem": "Generator",
- "name": "OC_GENHeaterControlForceMode",
- "en": "Generator Heater Enter in ForceMode",
- "cn": "发电机加热器控制进入强制模式",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#50ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_06_035": {
- "subsystem": "Generator",
- "name": "SC_GENWaterLeakWarning",
- "en": "Generator WaterLeak Warning",
- "cn": "发电机空水冷却器漏水警告",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_06_036": {
- "subsystem": "Generator",
- "name": "SC_GENLubricationWarning",
- "en": "Generator Lubrication Warning",
- "cn": "发电机润滑系统警告",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "02_08_001": {
- "subsystem": "GridMeasurement",
- "name": "SC_GenMaxPower10min",
- "en": "10 min average generator power exceeds maximum limit",
- "cn": "发电机10分钟平均功率高于上限值",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "5",
- "repeat_period": "T#24h",
- "trigger_en": "The 10min mean value for power output exceeds the maximum limit given by parameter.(grGenPowerForProcess_10min > PAR_rMaxPower10min)_x000D_",
- "trigger_cn": "10分钟平均发电机功率高于上限值。(grGenPowerForProcess_10min > PAR_rMaxPower10min)",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "The 10min mean value for power output falls below the maximum limit given by parameter AND the 100ms mean value for generator speed falls below the minimum limit of normal operation.(grGenPowerForProcess_10min <= PAR_rMaxPower10min AND grGenSpeedForProcess_100ms < PAR_rGenSpeedSlipLimit_MIN)",
- "reset_cn": "10分钟平均发电机功率降低到上限值以内,并且发电机100ms平均转速低于风机正常运转的下限值。(grGenPowerForProcess_10min <= PAR_rMaxPower10min AND grGenSpeedForProcess_100ms < PAR_rGenSpeedSlipLimit_MIN)",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "100"
- },
- "02_08_002": {
- "subsystem": "GridMeasurement",
- "name": "SC_GenMaxPower30s",
- "en": "30 seconds average generator power exceeds maximum limit",
- "cn": "发电机30秒平均功率高于上限值",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "10",
- "repeat_period": "T#24h",
- "trigger_en": "The 30 sec mean value for power output exceeds the maximum limit.(grGenPowerForProcess_30sec > PAR_rMaxPower30sec)",
- "trigger_cn": "30秒平均发电机功率高于上限值。(grGenPowerForProcess_30sec > PAR_rMaxPower30sec)",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "The 30 sec mean value for power output falls below the maximum limit and 100ms mean value for power output falls below a given parameter (grGenPowerForProcess_30sec <= PAR_rMaxPower30sec) AND (grGenSpeedForProcess_100ms < PAR_rGenSpeedSlipLimit_MIN)",
- "reset_cn": "30秒平均发电机功率降低到上限值以下并且100ms平均值低于给定参数。_x000D_ (grGenPowerForProcess_30sec <= PAR_rMaxPower30sec) AND (grGenSpeedForProcess_100ms < PAR_rGenSpeedSlipLimit_MIN)",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "100"
- },
- "02_08_003": {
- "subsystem": "GridMeasurement",
- "name": "SC_GenMaxPower1s",
- "en": "1 second average generator power exceeds maximum limit",
- "cn": "发电机1秒平均功率高于上限值",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "10",
- "repeat_period": "T#24h",
- "trigger_en": "The 1 sec mean value for power output exceeds the maximum limit. (grGenPowerForProcess_1sec > PAR_rMaxPower1sec)",
- "trigger_cn": "1秒平均发电机功率高于上限值。(grGenPowerForProcess_1sec > PAR_rMaxPower1sec)",
- "set_delay": "T#5s",
- "yp": "0",
- "reset_en": "The 1 sec mean value for power output falls below the maximum limit. (grGenPowerForProcess_1sec <= PAR_rMaxPower1sec)",
- "reset_cn": "1秒平均发电机功率降低到上限值内。(grGenPowerForProcess_1sec <= PAR_rMaxPower1sec)",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "100"
- },
- "02_08_004": {
- "subsystem": "GridMeasurement",
- "name": "SC_RepFaultGenMaxPower10min",
- "en": "The fault that 10 min average generator power exceeds maximum limit has repeated",
- "cn": "发电机10分钟平均功率高于上限值故障重复出现",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "One of the statuscodes for \"SC_GenMaxPower10min\" in a given time periode becomes more times TRUE than maximum allowed.(gbRepeat_02_08_001=1)",
- "trigger_cn": "10分钟发电机功率超限故障重复出现。(gbRepeat_02_08_001=1)",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "One of the statuscodes for \"SC_GenMaxPower10min\" in a given time periode becomes less times TRUE than maximum allowed.(gbRepeat_02_08_001=0)",
- "reset_cn": "10分钟发电机功率超限故障不重复出现。(gbRepeat_02_08_001=0)",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "100"
- },
- "02_08_009": {
- "subsystem": "GridMeasurement",
- "name": "SC_DevicePowerUnequalGenPower",
- "en": "Generator Power Got from External Device Diff From Generator Power Caculated",
- "cn": "外部设备测得发电机功率与变频器测得的差异大于设定值",
- "powerup_delay": "T#30s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "GenPower Calculated Internal and GenPower get From External Device diff more than PAR_rMaxPowerDiff100ms.(ABS(grGenPower_KL3403_10min - grConverter_ActivePowerCalculated_10min) > PAR_rPower100msDiffMax)AND diConverter_GridConnected=TRUE last for more than 1min",
- "trigger_cn": "变频器报告电网已经接入超过1min,且外部设备测得功率与自测功率差异大于上限值。(ABS(grGenPower_KL3403_10min - grConverter_ActivePowerCalculated_10min) > PAR_rPower100msDiffMax)",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "GenPower Calculated Internal and GenPower get From External Device diff less than PAR_rMaxPowerDiff100ms_x000D_ (ABS(grGenPower_KL3403_10min - grConverter_ActivePowerCalculated_10min) <= PAR_rPower100msDiffMax) OR diConverter_GridConnected=false OR diConverter_GridConnected=TRUE last for less than 1min",
- "reset_cn": "外部设备测得功率与自测功率差异不大于上限值或者变频器尚未报告报告电网接入或者接入时间不超过1min。 (ABS(grGenPower_KL3403_10min - grConverter_ActivePowerCalculated_10min) <= PAR_rPower100msDiffMax) OR diConverter_GridConnected=false OR diConverter_GridConnected=TRUE last for less than 1min",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "100"
- },
- "02_08_040": {
- "subsystem": "GridMeasurement",
- "name": "SC_RepFaultGenMaxPower30s",
- "en": "The fault that 30 seconds average generator power exceeds maximum limit has repeated",
- "cn": "发电机30秒平均功率高于上限值故障重复出现",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "One of the statuscodes for \"GenMaxPower30sec\" in a given time periode becomes more times TRUE than maximum allowed.(gbRepeat_02_08_002=1)_x000D_",
- "trigger_cn": "30秒发电机功率超限故障重复出现次数超限。(gbRepeat_02_08_002=1)",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "One of the statuscodes for \"GenMaxPower30sec\" in a given time periode becomes less times TRUE than maximum allowed.(gbRepeat_02_08_002=0)",
- "reset_cn": "30秒发电机功率超限故障重复出现次数低于限制次数。(gbRepeat_02_08_002=0)",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "100"
- },
- "02_08_041": {
- "subsystem": "GridMeasurement",
- "name": "SC_RepFaultGenMaxPower1s",
- "en": "The fault that 1 second average generator power exceeds maximum limit has repeated",
- "cn": "发电机1秒平均功率高于上限值故障重复出现",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "One of the statuscodes for \"GenMaxPower1sec\" in a given time periode becomes more times TRUE than maximum allowed.(gbRepeat_02_08_003=1)",
- "trigger_cn": "1秒发电机功率超限故障重复出现。(gbRepeat_02_08_003=1)",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "One of the statuscodes for \"GenMaxPower1sec\" in a given time periode becomes less times TRUE than maximum allowed.(gbRepeat_02_08_003=0)",
- "reset_cn": "1秒发电机功率超限故障不重复出现。(gbRepeat_02_08_003=0)",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "100"
- },
- "03_04_002": {
- "subsystem": "GridMeasurement",
- "name": "SC_GridVoltageL1_high",
- "en": "Grid voltage of phase L1 exceeds high limit",
- "cn": "电网电压L1相超出上限值",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "10",
- "repeat_period": "T#24h",
- "trigger_en": "The grid voltage (current value) measured for this phase exceeds the maximum value given by parameter.(grUL1_690V_KL3403 > (PAR_rNominalVoltage_Level_690V * (1 + PAR_rGridVoltageMAX_percent / 100)))_x000D_",
- "trigger_cn": "当前电网电压高于此阶段的测量参数给出的最高值。(grUL1_690V_KL3403 > (PAR_rNominalVoltage_Level_690V * (1 + PAR_rGridVoltageMAX_percent / 100)))_x000D_",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "The grid voltage (current value) measured for this phase falls below the maximum value given by parameter.(grUL1_690V_KL3403 <= (PAR_rNominalVoltage_Level_690V * (1 + PAR_rGridVoltageMAX_percent / 100)))_x000D_",
- "reset_cn": "当前电网电压低于此阶段的测量参数给出的最高值。(grUL1_690V_KL3403 <= (PAR_rNominalVoltage_Level_690V * (1 + PAR_rGridVoltageMAX_percent / 100)))_x000D_",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "180-电网故障",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "180",
- "brake_state_design": "100"
- },
- "03_04_003": {
- "subsystem": "GridMeasurement",
- "name": "SC_GridVoltageL2_high",
- "en": "Grid voltage of phase L2 exceeds high limit",
- "cn": "电网电压L2相超出上限值",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "10",
- "repeat_period": "T#24h",
- "trigger_en": "The grid voltage (current value) measured for this phase exceeds the maximum value given by parameter.(grUL2_690V_KL3403 > (PAR_rNominalVoltage_Level_690V * (1 + PAR_rGridVoltageMAX_percent / 100)))_x000D_",
- "trigger_cn": "当前电网电压高于此阶段的测量参数给出的最高值。(grUL2_690V_KL3403 > (PAR_rNominalVoltage_Level_690V * (1 + PAR_rGridVoltageMAX_percent / 100)))_x000D_",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "The grid voltage (current value) measured for this phase falls below the maximum value given by parameter.(grUL2_690V_KL3403 <= (PAR_rNominalVoltage_Level_690V * (1 + PAR_rGridVoltageMAX_percent / 100)))_x000D_",
- "reset_cn": "当前电网电压低于此阶段的测量参数给出的最高值。(grUL2_690V_KL3403 <= (PAR_rNominalVoltage_Level_690V * (1 + PAR_rGridVoltageMAX_percent / 100)))_x000D_",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "180-电网故障",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "180",
- "brake_state_design": "100"
- },
- "03_04_004": {
- "subsystem": "GridMeasurement",
- "name": "SC_GridVoltageL3_high",
- "en": "Grid voltage of phase L3 exceeds high limit",
- "cn": "电网电压L3相超出上限值",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "10",
- "repeat_period": "T#24h",
- "trigger_en": "The grid voltage (current value) measured for this phase exceeds the maximum value given by parameter.(grUL3_690V_KL3403 > (PAR_rNominalVoltage_Level_690V * (1 + PAR_rGridVoltageMAX_percent / 100)))",
- "trigger_cn": "当前电网电压高于此阶段的测量参数给出的最高值。(grUL3_690V_KL3403 > (PAR_rNominalVoltage_Level_690V * (1 + PAR_rGridVoltageMAX_percent / 100)))",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "The grid voltage (current value) measured for this phase falls below the maximum value given by parameter.(grUL3_690V_KL3403 <= (PAR_rNominalVoltage_Level_690V * (1 + PAR_rGridVoltageMAX_percent / 100)))",
- "reset_cn": "当前电网电压低于此阶段的测量参数给出的最高值。(grUL3_690V_KL3403 <= (PAR_rNominalVoltage_Level_690V * (1 + PAR_rGridVoltageMAX_percent / 100)))",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "180-电网故障",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "180",
- "brake_state_design": "100"
- },
- "03_04_005": {
- "subsystem": "GridMeasurement",
- "name": "SC_RepFaultGridVoltageHigh",
- "en": "The fault of grid overvoltage has repeated",
- "cn": "电网电压过高故障重复出现",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "One of the statuscodes for \"Grid Voltage too high\" in a given time periode becomes more times TRUE than maximum allowed. (gbRepeat_03_04_002=1 OR gbRepeat_03_04_003=1 OR gbRepeat_03_04_004=1)",
- "trigger_cn": "电网电压L1或L2或L3相过高故障重复出现。(gbRepeat_03_04_002=1 OR gbRepeat_03_04_003=1 OR gbRepeat_03_04_004=1)",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "All of the statuscodes for \"Grid Voltage too high\" in a given time periode becomes less times TRUE than maximum allowed. (gbRepeat_03_04_002=0 AND gbRepeat_03_04_003=0 AND gbRepeat_03_04_004=0)",
- "reset_cn": "电网电压L1、L2和L3相过高故障均没有重复出现。(gbRepeat_03_04_002=0 AND gbRepeat_03_04_003=0 AND gbRepeat_03_04_004=0)",
- "reset_mode": "M",
- "type": "A",
- "alarm": "True",
- "level": "180-电网故障",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "180",
- "brake_state_design": "100"
- },
- "03_04_006": {
- "subsystem": "GridMeasurement",
- "name": "SC_GridVoltageL1_low",
- "en": "Grid voltage of phase L1 exceeds low limit",
- "cn": "电网电压L1相超出下限值",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "10",
- "repeat_period": "T#24h",
- "trigger_en": "The grid voltage (current value) measured for this phase falls below the minimum value given by parameter.(grUL1_690V_KL3403 < (PAR_rNominalVoltage_Level_690V * (1 - PAR_rGridVoltageMIN_percent / 100)))_x000D_",
- "trigger_cn": "当前电网电压低于此阶段的测量参数给出的最低值。(grUL1_690V_KL3403 < (PAR_rNominalVoltage_Level_690V * (1 - PAR_rGridVoltageMIN_percent / 100)))_x000D_",
- "set_delay": "PAR_tSetDelayForGridVoltageLow",
- "yp": "100",
- "reset_en": "The grid voltage (current value) measured for this phase exceeds the minimum value given by parameter.(grUL1_690V_KL3403 >= (PAR_rNominalVoltage_Level_690V * (1 - PAR_rGridVoltageMIN_percent / 100)))_x000D_",
- "reset_cn": "当前电网电压高于此阶段的测量参数给出的最低值。(grUL1_690V_KL3403 >= (PAR_rNominalVoltage_Level_690V * (1 - PAR_rGridVoltageMIN_percent / 100))) AND (grUL1_690V_KL3403 > (PAR_rNominalVoltage_Level_690V * (1 - (PAR_rGridVoltageMIN_percent - 3.0)/ 100)))_x000D_",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "180-电网故障",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "180",
- "brake_state_design": "100"
- },
- "03_04_007": {
- "subsystem": "GridMeasurement",
- "name": "SC_GridVoltageL2_low",
- "en": "Grid voltage of phase L2 exceeds low limit",
- "cn": "电网电压L2相超出下限值",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "10",
- "repeat_period": "T#24h",
- "trigger_en": "The grid voltage (current value) measured for this phase falls below the minimum value given by parameter.(grUL2_690V_KL3403 < (PAR_rNominalVoltage_Level_690V * (1 - PAR_rGridVoltageMIN_percent / 100)))_x000D_",
- "trigger_cn": "当前电网电压低于此阶段的测量参数给出的最低值。(grUL2_690V_KL3403 < (PAR_rNominalVoltage_Level_690V * (1 - PAR_rGridVoltageMIN_percent / 100)))_x000D_",
- "set_delay": "PAR_tSetDelayForGridVoltageLow",
- "yp": "100",
- "reset_en": "The grid voltage (current value) measured for this phase exceeds the minimum value given by parameter.(grUL2_690V_KL3403 >= (PAR_rNominalVoltage_Level_690V * (1 - PAR_rGridVoltageMIN_percent / 100)) AND (grUL2_690V_KL3403 > (PAR_rNominalVoltage_Level_690V * (1 - (PAR_rGridVoltageMIN_percent - 3.0)/ 100))",
- "reset_cn": "当前电网电压高于此阶段的测量参数给出的最低值。(grUL2_690V_KL3403 >= (PAR_rNominalVoltage_Level_690V * (1 - PAR_rGridVoltageMIN_percent / 100))) AND (grUL2_690V_KL3403 > (PAR_rNominalVoltage_Level_690V * (1 - (PAR_rGridVoltageMIN_percent - 3.0)/ 100))",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "180-电网故障",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "180",
- "brake_state_design": "100"
- },
- "03_04_008": {
- "subsystem": "GridMeasurement",
- "name": "SC_GridVoltageL3_low",
- "en": "Grid voltage of phase L3 exceeds low limit",
- "cn": "电网电压L3相超出下限值",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "10",
- "repeat_period": "T#24h",
- "trigger_en": "The grid voltage (current value) measured for this phase falls below the minimum value given by parameter.(grUL3_690V_KL3403 < (PAR_rNominalVoltage_Level_690V * (1 - PAR_rGridVoltageMIN_percent / 100)))",
- "trigger_cn": "当前电网电压低于此阶段的测量参数给出的最低值。(grUL3_690V_KL3403 < (PAR_rNominalVoltage_Level_690V * (1 - PAR_rGridVoltageMIN_percent / 100)))",
- "set_delay": "PAR_tSetDelayForGridVoltageLow",
- "yp": "100",
- "reset_en": "The grid voltage (current value) measured for this phase exceeds the minimum value given by parameter.(grUL3_690V_KL3403 >= (PAR_rNominalVoltage_Level_690V * (1 - PAR_rGridVoltageMIN_percent / 100)))",
- "reset_cn": "当前电网电压高于此阶段的测量参数给出的最低值。(grUL3_690V_KL3403 >= (PAR_rNominalVoltage_Level_690V * (1 - PAR_rGridVoltageMIN_percent / 100))) AND (grUL3_690V_KL3403 > (PAR_rNominalVoltage_Level_690V * (1 - (PAR_rGridVoltageMIN_percent - 3.0)/ 100)))",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "180-电网故障",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "180",
- "brake_state_design": "100"
- },
- "03_04_009": {
- "subsystem": "GridMeasurement",
- "name": "SC_RepFaultGridVoltageLow",
- "en": "The fault of grid undervoltage has repeated",
- "cn": "电网电压过低故障重复出现",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "One of the statuscodes for \"Grid Voltage too low\" in a given time periode becomes more times TRUE than maximum allowed. (gbRepeat_03_04_006=1 OR gbRepeat_03_04_007=1 OR gbRepeat_03_04_008=1)",
- "trigger_cn": "电网电压L1或L2或L3过低故障重复出现。(gbRepeat_03_04_006=1 OR gbRepeat_03_04_007=1 OR gbRepeat_03_04_008=1)",
- "set_delay": "T#100ms",
- "yp": "100",
- "reset_en": "All of the statuscodes for \"Grid Voltage too low\" in a given time periode becomes more times TRUE than maximum allowed. (gbRepeat_03_04_006=0 AND gbRepeat_03_04_007=0 AND gbRepeat_03_04_008=0)",
- "reset_cn": "电网电压L1、L2和L3过低故障均不重复出现。(gbRepeat_03_04_006=0 AND gbRepeat_03_04_007=0 AND gbRepeat_03_04_008=0)",
- "reset_mode": "M",
- "type": "A",
- "alarm": "True",
- "level": "180-电网故障",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "180",
- "brake_state_design": "100"
- },
- "03_04_010": {
- "subsystem": "GridMeasurement",
- "name": "SC_GridFrequencyHigh",
- "en": "Grid frequency is too high",
- "cn": "电网频率过高",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "10",
- "repeat_period": "T#24h",
- "trigger_en": "The grid frequency (100ms mean value) exceeds the maximum value given by parameter.(grGridFrequencyForProcess_100ms > PAR_rGridFrequencyMAX_Hz)",
- "trigger_cn": "电网100ms平均值频率高于给定最大值。(grGridFrequencyForProcess_100ms > PAR_rGridFrequencyMAX_Hz)",
- "set_delay": "PAR_tSetDelayForFrequencyHigh",
- "yp": "0",
- "reset_en": "The grid frequency (100ms mean value) falls below the maximum value given by parameter.(grGridFrequencyForProcess_100ms <= PAR_rGridFrequencyMAX_Hz)",
- "reset_cn": "电网100ms平均值频率不高于给定最大值。(grGridFrequencyForProcess_100ms <= PAR_rGridFrequencyMAX_Hz)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "180-电网故障",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "180",
- "brake_state_design": "100"
- },
- "03_04_011": {
- "subsystem": "GridMeasurement",
- "name": "SC_GridFrequencyLow",
- "en": "Grid frequency is too low",
- "cn": "电网频率过低",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "10",
- "repeat_period": "T#24h",
- "trigger_en": "The grid frequency (100ms mean value) falls below the minimum value given by parameter.(grGridFrequencyForProcess_100ms < PAR_rGridFrequencyMIN_Hz)",
- "trigger_cn": "电网频率100ms平均值低于给定最小值。(grGridFrequencyForProcess_100ms < PAR_rGridFrequencyMIN_Hz)",
- "set_delay": "PAR_tSetDelayForFrequencyLow",
- "yp": "0",
- "reset_en": "The grid frequency (100ms mean value) exceeds the minimum value given by parameter.(grGridFrequencyForProcess_100ms >= PAR_rGridFrequencyMIN_Hz)",
- "reset_cn": "电网频率100ms平均值高于给定最小值。(grGridFrequencyForProcess_100ms >= PAR_rGridFrequencyMIN_Hz)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "180-电网故障",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "180",
- "brake_state_design": "100"
- },
- "03_04_012": {
- "subsystem": "GridMeasurement",
- "name": "SC_RepFaultGridFrequency",
- "en": "The faults, grid frequency is too high or low, have repeated",
- "cn": "电网频率过高过低故障重复出现",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "One of the statuscodes for \"Grid Frequency too high\" in a given time periode becomes more times TRUE than maximum allowed.(gbRepeat_03_04_010=1 OR gbRepeat_03_04_011=1)",
- "trigger_cn": "电网频率过高或过低故障重复出现。(gbRepeat_03_04_010=1 OR gbRepeat_03_04_011=1)",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "One of the statuscodes for \"Grid Frequency too high\" in a given time periode becomes less times TRUE than maximum allowed.(gbRepeat_03_04_010=0 AND gbRepeat_03_04_011=0)",
- "reset_cn": "电网频率过高和过低故障均无重复出现。(gbRepeat_03_04_010=0 AND gbRepeat_03_04_011=0)",
- "reset_mode": "M",
- "type": "A",
- "alarm": "True",
- "level": "180-电网故障",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "180",
- "brake_state_design": "100"
- },
- "03_04_018": {
- "subsystem": "GridMeasurement",
- "name": "SC_GridLost_PowerFailure",
- "en": "Grid is lost",
- "cn": "掉网故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The grid voltage (current value) for all three phases falls below the minimum value given by parameter.(grUL1_690V_KL3403 < PAR_rVoltageForGridLost_Volt OR grUL2_690V_KL3403 < PAR_rVoltageForGridLost_Volt OR grUL3_690V_KL3403 < PAR_rVoltageForGridLost_Volt)",
- "trigger_cn": "电网电压L1、L2或L3相高于下限。(grUL1_690V_KL3403 < PAR_rVoltageForGridLost_Volt OR grUL2_690V_KL3403 < PAR_rVoltageForGridLost_Volt OR grUL3_690V_KL3403 < PAR_rVoltageForGridLost_Volt)",
- "set_delay": "T#100ms",
- "yp": "100",
- "reset_en": "The grid voltage (current value) for all three phases falls below the minimum value given by parameter.(grUL1_690V_KL3403 >= PAR_rVoltageForGridLost_Volt AND grUL2_690V_KL3403 >= PAR_rVoltageForGridLost_Volt AND grUL3_690V_KL3403 >= PAR_rVoltageForGridLost_Volt)",
- "reset_cn": "电网电压L1、L2或L3相低于下限值。(grUL1_690V_KL3403 >= PAR_rVoltageForGridLost_Volt AND grUL2_690V_KL3403 >= PAR_rVoltageForGridLost_Volt AND grUL3_690V_KL3403 >= PAR_rVoltageForGridLost_Volt)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "180-电网故障",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "180",
- "brake_state_design": "100"
- },
- "03_04_020": {
- "subsystem": "GridMeasurement",
- "name": "SC_GridFrequencyMax",
- "en": "Grid frequency exceeds maximum value",
- "cn": "电网频率高于上限值",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "10",
- "repeat_period": "T#24h",
- "trigger_en": "The grid frequency is exceed maximum value (grGridFrequencyForProcess_100ms > PAR_rGridFrequencyMAX_Hz)",
- "trigger_cn": "电网频率高于上限值",
- "set_delay": "PAR_tSetDelayForFrequencyMax",
- "yp": "0",
- "reset_en": "Grid frequency not exceeds the maximum value",
- "reset_cn": "电网频率恢复上限值以下",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "180-电网故障",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "180",
- "brake_state_design": "100"
- },
- "03_04_021": {
- "subsystem": "GridMeasurement",
- "name": "SC_GridFrequencyMin",
- "en": "Grid frequency belows minimum value",
- "cn": "电网频率低于下限值",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "10",
- "repeat_period": "T#24h",
- "trigger_en": "The grid frequency is belows minimum value(grGridFrequencyForProcess_100ms < PAR_rGridFrequencyMIN_Hz)",
- "trigger_cn": "电网频率低于下限值",
- "set_delay": "PAR_tSetDelayForFrequencyMin",
- "yp": "0",
- "reset_en": "Grid frequency not below the minimum value",
- "reset_cn": "电网频率恢复到下限值以上",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "180-电网故障",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "180",
- "brake_state_design": "100"
- },
- "03_04_022": {
- "subsystem": "GridMeasurement",
- "name": "OC_HVRT_Activated",
- "en": "High voltage ride-through is activated",
- "cn": "高电压穿越",
- "powerup_delay": "T#2m",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Grid voltage is above 1.1Un, i.e._x000D_ (PAR_rHVRTVolLevel0Multiplier*PAR_rNominalVoltage_Level_690V)",
- "trigger_cn": "风机并网运行时电网电压越上限",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "Grid voltage is not above 1.1Un, i.e._x000D_ (PAR_rHVRTVolLevel0Multiplier*PAR_rNominalVoltage_Level_690V)",
- "reset_cn": "电网电压回落至上限值以下",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "03_04_200": {
- "subsystem": "GridMeasurement",
- "name": "SC_GridCurrentAsymmetric",
- "en": "Asymmetry of grid 3 phase current",
- "cn": "电网三相电流不平衡",
- "powerup_delay": "T#10s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The grid 3 phase current is asymmetric.(ABS(grIL1_690V_KL3403 - grIL2_690V_KL3403) > PAR_rMaxCurrentDiff_A OR ABS(grIL1_690V_KL3403 - grIL3_690V_KL3403) > PAR_rMaxCurrentDiff_A OR ABS(grIL2_690V_KL3403 - grIL3_690V_KL3403) > PAR_rMaxCurrentDiff_A)",
- "trigger_cn": "电网三相电流中有两相差值大于设定值。(ABS(grIL1_690V_KL3403 - grIL2_690V_KL3403) > PAR_rMaxCurrentDiff_A OR ABS(grIL1_690V_KL3403 - grIL3_690V_KL3403) > PAR_rMaxCurrentDiff_A OR ABS(grIL2_690V_KL3403 - grIL3_690V_KL3403) > PAR_rMaxCurrentDiff_A)",
- "set_delay": "T#4s",
- "yp": "0",
- "reset_en": "The grid 3 phase current is symmetric.(ABS(grIL1_690V_KL3403 - grIL2_690V_KL3403) < PAR_rMaxCurrentDiff_A AND ABS(grIL1_690V_KL3403 - grIL3_690V_KL3403) < PAR_rMaxCurrentDiff_A AND ABS(grIL2_690V_KL3403 - grIL3_690V_KL3403) < PAR_rMaxCurrentDiff_A)",
- "reset_cn": "电网三相电流中任两相差值均小于设定值。(ABS(grIL1_690V_KL3403 - grIL2_690V_KL3403) < PAR_rMaxCurrentDiff_A AND ABS(grIL1_690V_KL3403 - grIL3_690V_KL3403) < PAR_rMaxCurrentDiff_A AND ABS(grIL2_690V_KL3403 - grIL3_690V_KL3403) < PAR_rMaxCurrentDiff_A)",
- "reset_mode": "M",
- "type": "A",
- "alarm": "True",
- "level": "180-电网故障",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "180",
- "brake_state_design": "100"
- },
- "03_09_101": {
- "subsystem": "GridMeasurement",
- "name": "OC_PowerAboveShutDown_10min",
- "en": "10min average power is higher than shutdown minimum limit",
- "cn": "发电机10分钟平均功率大于正常运行下限值",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "_x000D_ When the power output of the turbine (10min mean value) will be higher than a value, given by parameter after grid connection.(diConverter_GridConnected=1 AND grGenPowerForProcess_10min > PAR_rShutDownSlowForLowPower)",
- "trigger_cn": "并网发电后10分钟平均发电功率大于正常运行下限值。(diConverter_GridConnected=1 AND grGenPowerForProcess_10min > PAR_rShutDownSlowForLowPower)",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "_x000D_ When the power output of the turbine (10min mean value) is lower than a value, given by parameter or there is no grid connection.(diConverter_GridConnected=0 OR grGenPowerForProcess_10min < PAR_rShutDownSlowForLowPower)",
- "reset_cn": "没有并网发电或10分钟平均发电功率小于正常运行下限值。(diConverter_GridConnected=0 OR grGenPowerForProcess_10min < PAR_rShutDownSlowForLowPower)",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "03_09_102": {
- "subsystem": "GridMeasurement",
- "name": "OC_PowerAboveShutDown_30s",
- "en": "30sec average power is higher than shutdown minimum limit",
- "cn": "发电机30秒平均功率大于正常运行下限值",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "When the power output of the turbine (30sec mean value) will be higher than a value, given by parameter after grid connection.(diConverter_GridConnected=1 AND grGenPowerForProcess_30sec > PAR_rShutDownSlowForLowPower)",
- "trigger_cn": "并网发电后30秒平均发电功率大于正常运行下限值。(diConverter_GridConnected=1 AND grGenPowerForProcess_30sec > PAR_rShutDownSlowForLowPower)",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "When the power output of the turbine (30sec mean value) is lower than a value, given by parameter or there is no grid connection.(diConverter_GridConnected=0 OR grGenPowerForProcess_30sec < PAR_rShutDownSlowForLowPower)",
- "reset_cn": "没有并网发电或30秒钟平均发电功率小于正常运行下限值。(diConverter_GridConnected=0 OR grGenPowerForProcess_30sec < PAR_rShutDownSlowForLowPower)",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "02_02_041": {
- "subsystem": "HSBrakeSystem",
- "name": "SC_MotorProtection_HydrPump",
- "en": "The motor protection system for the hydraulic pump has tripped.",
- "cn": "机舱柜中液压站的液压泵保护空开跳开",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The motor protection system for the hydraulic pump has tripped.(gbDI_NacelleMotorProtHydrPump=0)",
- "trigger_cn": "液压泵的电机保护系统发生故障。(gbDI_NacelleMotorProtHydrPump=0)",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "The motor protection system for the hydraulic pump is OK.(gbDI_NacelleMotorProtHydrPump=1)",
- "reset_cn": "液压泵的电机保护系统故障解除。(gbDI_NacelleMotorProtHydrPump=1)",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_02_090": {
- "subsystem": "HSBrakeSystem",
- "name": "SC_FaultAI_HydraulicPressurePreCharge",
- "en": "Pressure sensor of hydraulic precharger has fault",
- "cn": "液压站储能罐压力传感器故障",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Bit 6 from the hydraulic precharger input becomes TRUE.(giStateAIWindDirection.6=1)",
- "trigger_cn": "液压系统蓄压器的压力传感器输入状态字节第6位是TRUE。(giStateAIWindDirection.6=1)",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "Bit 6 from the hydraulic precharger input becomes FALSE.(giStateAIWindDirection.6=0)",
- "reset_cn": "液压系统蓄压器的压力传感器输入状态字节第6位是FALSE。(giStateAIWindDirection.6=0)",
- "reset_mode": "M",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_02_091": {
- "subsystem": "HSBrakeSystem",
- "name": "SC_FaultAI_HydraulicPressureSump",
- "en": "Pressure sensor of hydraulic Sump has fault",
- "cn": "液压站主回路压力传感器故障",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Bit 6 from the hydraulic precharger input becomes TRUE.(giStateAIWindDirection.6=1)",
- "trigger_cn": "液压系统蓄压器的压力传感器输入状态字节第6位是TRUE。(giStateAIWindDirection.6=1)",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "Bit 6 from the hydraulic precharger input becomes FALSE.(giStateAIWindDirection.6=0)",
- "reset_cn": "液压系统蓄压器的压力传感器输入状态字节第6位是FALSE。(giStateAIWindDirection.6=0)",
- "reset_mode": "M",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_02_092": {
- "subsystem": "HSBrakeSystem",
- "name": "SC_FaultAI_HydraulicPressureBrake",
- "en": "Pressure sensor of hydraulic Brake has fault",
- "cn": "液压站刹车回路压力传感器故障",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Bit 6 from the hydraulic precharger input becomes TRUE.(giStateAIWindDirection.6=1)",
- "trigger_cn": "液压系统蓄压器的压力传感器输入状态字节第6位是TRUE。(giStateAIWindDirection.6=1)",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "Bit 6 from the hydraulic precharger input becomes FALSE.(giStateAIWindDirection.6=0)",
- "reset_cn": "液压系统蓄压器的压力传感器输入状态字节第6位是FALSE。(giStateAIWindDirection.6=0)",
- "reset_mode": "M",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_02_093": {
- "subsystem": "HSBrakeSystem",
- "name": "SC_NacelleFuseHeaterHydrOil",
- "en": "Hydr heater fuse tripped",
- "cn": "液压站油加热器熔丝开关跳开",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "gbDI_NacelleFuseHeaterHydrOil",
- "trigger_cn": "gbDI_NacelleFuseHeaterHydrOil",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "Bit 6 from the hydraulic precharger input becomes FALSE.(giStateAIWindDirection.6=0)",
- "reset_cn": "液压系统蓄压器的压力传感器输入状态字节第6位是FALSE。(giStateAIWindDirection.6=0)",
- "reset_mode": "M",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_02_094": {
- "subsystem": "HSBrakeSystem",
- "name": "SC_AccumulatorPressure_High",
- "en": "Accumulator Pressure High",
- "cn": "储能罐压力高",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "gbDI_NacelleFuseHeaterHydrOil",
- "trigger_cn": "grHydrPressurePreCharge",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "Bit 6 from the hydraulic precharger input becomes FALSE.(giStateAIWindDirection.6=0)",
- "reset_cn": "液压系统蓄压器的压力传感器输入状态字节第6位是FALSE。(giStateAIWindDirection.6=0)",
- "reset_mode": "M",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_02_095": {
- "subsystem": "HSBrakeSystem",
- "name": "SC_AccumulatorPressure_Low",
- "en": "Accumulator Pressure Low",
- "cn": "储能罐压力低",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "gbDI_NacelleFuseHeaterHydrOil",
- "trigger_cn": "grHydrPressurePreCharge",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "Bit 6 from the hydraulic precharger input becomes FALSE.(giStateAIWindDirection.6=0)",
- "reset_cn": "液压系统蓄压器的压力传感器输入状态字节第6位是FALSE。(giStateAIWindDirection.6=0)",
- "reset_mode": "M",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_02_100": {
- "subsystem": "HSBrakeSystem",
- "name": "OC_Valve1RotorBrake_ON",
- "en": "Rotor brake valve1 is set to on",
- "cn": "机械刹车1号阀动作",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "PLC output for controlling Valve 1 for the rotor brake becomes TRUE.(DQ_NacelleValve1RotorBrakeON_sudden=1)",
- "trigger_cn": "PLC控制机械刹车1号阀的输出为TRUE。(DQ_NacelleValve1RotorBrakeON_sudden=1)",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "PLC output for controlling Valve 1 for the rotor brake becomes FALSE.(DQ_NacelleValve1RotorBrakeON_sudden=0)",
- "reset_cn": "PLC控制机械刹车1号阀的输出为FALSE。(DQ_NacelleValve1RotorBrakeON_sudden=0)",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "02_02_109": {
- "subsystem": "HSBrakeSystem",
- "name": "OC_HydrPump_ON",
- "en": "Hydraulic pump is set to on",
- "cn": "液压站的液压泵运行",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "PLC output for controlling the hydraulic pump becomes TRUE.(DQ_NacelleHydrPump=1)",
- "trigger_cn": "PLC控制液压系统油泵的输出为TRUE。(DQ_NacelleHydrPump=1)",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "PLC output for controlling the hydraulic pump becomes FALSE.(DQ_NacelleHydrPump=0)",
- "reset_cn": "PLC控制液压系统油泵的输出为FALSE。(DQ_NacelleHydrPump=0)",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "02_02_117": {
- "subsystem": "HSBrakeSystem",
- "name": "OC_Valve2RotorBrake_ON",
- "en": "Rotor brake valve2 is set to on",
- "cn": "机械刹车2号阀动作",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "PLC output for controlling Valve 2 for the rotor brake becomes TRUE.(DQ_NacelleValve2RotorBrakeON_dimmed=1)",
- "trigger_cn": "PLC控制机械刹车2号阀的输出为TRUE。(DQ_NacelleValve2RotorBrakeON_dimmed=1)",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "PLC output for controlling Valve 2 for the rotor brake becomes FALSE.(DQ_NacelleValve2RotorBrakeON_dimmed=0)",
- "reset_cn": "PLC控制机械刹车2号阀的输出为FALSE。(DQ_NacelleValve2RotorBrakeON_dimmed=0)",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "02_02_118": {
- "subsystem": "HSBrakeSystem",
- "name": "OC_Valve3RotorBrake_ON",
- "en": "Rotor brake valve3 is set to on",
- "cn": "机械刹车3号阀动作",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "PLC output for controlling Valve 3 for the rotor brake becomes TRUE.(DQ_NacelleValve3RotorBrakeOFF_sudden=1)",
- "trigger_cn": "PLC控制机械刹车3号阀的输出为TRUE。(DQ_NacelleValve3RotorBrakeOFF_sudden=1)",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "PLC output for controlling Valve 3 for the rotor brake becomes FALSE.(DQ_NacelleValve3RotorBrakeOFF_sudden=0)",
- "reset_cn": "PLC控制机械刹车3号阀的输出为FALSE。(DQ_NacelleValve3RotorBrakeOFF_sudden=0)",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "02_02_119": {
- "subsystem": "HSBrakeSystem",
- "name": "OC_Valve4RotorBrake_ON",
- "en": "Rotor brake valve4 is set to on",
- "cn": "机械刹车4号阀动作",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "PLC output for controlling Valve 4 for the rotor brake becomes TRUE.(DQ_NacelleValve4RotorBrakeOFF_dimmed=1)",
- "trigger_cn": "PLC控制机械刹车4号阀的输出为TRUE。(DQ_NacelleValve4RotorBrakeOFF_dimmed=1)",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "PLC output for controlling Valve 4 for the rotor brake becomes FALSE.(DQ_NacelleValve4RotorBrakeOFF_dimmed=0)",
- "reset_cn": "PLC控制机械刹车4号阀的输出为FALSE。(DQ_NacelleValve4RotorBrakeOFF_dimmed=0)",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "02_07_001": {
- "subsystem": "HSBrakeSystem",
- "name": "SC_MotorOverLoad_HydrPump",
- "en": "Hydraulic pump overload",
- "cn": "液压泵电机过载",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_07_002": {
- "subsystem": "HSBrakeSystem",
- "name": "SC_RotorBrakePadsWorn_Alarm",
- "en": "Rotor brake pad is worn-out for alarm",
- "cn": "机械刹车刹车盘磨损警告",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Rotor brake pad is worn for alarm.(gbDI_NacelleRotorBrakePadsAlarm=0)",
- "trigger_cn": "机械刹车片磨损警告。(gbDI_NacelleRotorBrakePadsAlarm=0)",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "Rotor brake pad is not worn for alarm.(gbDI_NacelleRotorBrakePadsAlarm=1)",
- "reset_cn": "机械刹车片磨损警告解除。(gbDI_NacelleRotorBrakePadsAlarm=1)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_07_003": {
- "subsystem": "HSBrakeSystem",
- "name": "SC_RotorBrakePadsWorn_STOP",
- "en": "Rotor brake pad is worn-out for stop",
- "cn": "机械刹车刹车盘磨损故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Rotor brake pad is worn-out for stop.(gbDI_NacelleRotorBrakePadsSTOP=0)",
- "trigger_cn": "机械刹车摩擦片磨损故障。(gbDI_NacelleRotorBrakePadsSTOP=0)",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "Rotor brake pad is not worn-out for stop.(gbDI_NacelleRotorBrakePadsSTOP=1)",
- "reset_cn": "机械刹车摩擦片无磨损故障。(gbDI_NacelleRotorBrakePadsSTOP=1)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_07_005": {
- "subsystem": "HSBrakeSystem",
- "name": "SC_RotorBrakeClosed",
- "en": "Rotor brake fails to open",
- "cn": "机械刹车释放失灵",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "TurbineOperationMode is not in selftest1, selftest2 and selftest3, rotor brake fails to open.(giTurbineOperationMode ≠ CON_iSelftest1 AND giTurbineOperationMode ≠ CON_iSelftest2 AND giTurbineOperationMode ≠ CON_iSelftest3 AND gbBrakeMustBeOpen=1 AND gbDI_NacelleRotorBrakeOpen=0)",
- "trigger_cn": "风机不处于自检1、自检2和自检3,收到机械刹车释放信号,但释放失灵。(giTurbineOperationMode ≠ CON_iSelftest1 AND giTurbineOperationMode ≠ CON_iSelftest2 AND giTurbineOperationMode ≠ CON_iSelftest3 AND gbBrakeMustBeOpen=1 AND gbDI_NacelleRotorBrakeOpen=0)",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "TurbineOperationMode is in selftest1, selftest2 or selftest3, rotor brake succeeds to open.(giTurbineOperationMode = CON_iSelftest1 OR giTurbineOperationMode = CON_iSelftest2 OR giTurbineOperationMode = CON_iSelftest3 OR gbBrakeMustBeOpen=0 OR gbDI_NacelleRotorBrakeOpen=1)",
- "reset_cn": "风机进入自检1、自检2或自检3,或没有收到机械刹车释放信号,释放正常。(giTurbineOperationMode = CON_iSelftest1 OR giTurbineOperationMode = CON_iSelftest2 OR giTurbineOperationMode = CON_iSelftest3 OR gbBrakeMustBeOpen=0 OR gbDI_NacelleRotorBrakeOpen=1)",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_09_001": {
- "subsystem": "HSBrakeSystem",
- "name": "SC_HydrPressureSystemMin_Warning",
- "en": "Hydraulic pressure is below minimum limit for warning",
- "cn": "液压系统刹车回路压力低于下限值警告",
- "powerup_delay": "T#3m",
- "disable_level": "100",
- "repeat_n": "3",
- "repeat_period": "T#1h",
- "trigger_en": "The turbine operation mode is not \"selftest3\", the system pressure (1 sec mean value) from the hydraulic system falls below a minimum value given by parameter.(giTurbineOperationMode ≠ CON_iSelftest3 AND grHydrPressurePreCharge_1sec < PAR_rHydSystemPressMIN_Warn)",
- "trigger_cn": "风机不运行在自检3模式,且液压系统1秒钟平均压力低于下限值。(giTurbineOperationMode ≠ CON_iSelftest3 AND grHydrPressurePreCharge_1sec < PAR_rHydSystemPressMIN_Warn)",
- "set_delay": "T#5s",
- "yp": "0",
- "reset_en": "The turbine operation mode is \"selftest3\", OR the system pressure (1 sec mean value) from the hydraulic system exceeds a minimum value given by parameter.(giTurbineOperationMode = CON_iSelftest3 OR grHydrPressurePreCharge_1sec >= PAR_rHydSystemPressMIN_Warn)",
- "reset_cn": "风机运行在自检3模式,或液压系统1秒钟平均压力低于下限值。(giTurbineOperationMode = CON_iSelftest3 OR grHydrPressurePreCharge_1sec >= PAR_rHydSystemPressMIN_Warn)",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_09_003": {
- "subsystem": "HSBrakeSystem",
- "name": "SC_HydrPressureSystemMin_STOP",
- "en": "Hydraulic pressure is below minimum limit for stop",
- "cn": "液压系统刹车回路压力低于下限值故障",
- "powerup_delay": "T#3m",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The system pressure (1 sec mean value) from the hydraulic system falls below a minimum value given by parameter, AND TurbineOperation is not in selftest3.(grHydrPressurePreCharge_1sec < PAR_rHydSystemPressMIN_STOP AND giTurbineOperationMode ≠ CON_iSelftest3)",
- "trigger_cn": "风机模式不在自检3且液压系统压力低于下限值故障。(grHydrPressurePreCharge_1sec < PAR_rHydSystemPressMIN_STOP AND giTurbineOperationMode ≠ CON_iSelftest3)",
- "set_delay": "T#5s",
- "yp": "0",
- "reset_en": "The system pressure (1 sec mean value) from the hydraulic system exceeds a minimum value given by parameter, OR TurbineOperation is in selftest3.(grHydrPressurePreCharge_1sec >= PAR_rHydSystemPressMIN_STOP OR giTurbineOperationMode = CON_iSelftest3)",
- "reset_cn": "风机在自检3或液压系统压力不低于下限值故障。(grHydrPressurePreCharge_1sec >= PAR_rHydSystemPressMIN_STOP OR giTurbineOperationMode = CON_iSelftest3)",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "165",
- "brake_state_design": "0"
- },
- "02_09_004": {
- "subsystem": "HSBrakeSystem",
- "name": "SC_HydrSystemOilTemp_High",
- "en": "Overtemperature, oil in brake circuit of hydraulic system",
- "cn": "液压系统刹车回路油温过高",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#5s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_09_005": {
- "subsystem": "HSBrakeSystem",
- "name": "SC_HydrSystemPressMAX_STOP",
- "en": "1s average Hydraulic pressure pre-charge value exceeds MAX limit.",
- "cn": "液压系统压力高于最大限值",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "If below statements are all TRUE,_x000D_ 1. NOT (giTurbineOperationMode = CON_iSelftest3)_x000D_ 2. grHydrPressurePreCharge_1sec > PAR_rHydSystemPressMAX_STOP",
- "trigger_cn": "当前WTG不在Selftest3状态,且输入变量的值高于参数设定值",
- "set_delay": "T#5s",
- "yp": "0",
- "reset_en": "If one of below statement goes to true,_x000D_ 1.giTurbineOperationMode = CON_iSelftest3_x000D_ 2.grHydrPressurePreCharge_1sec<=PAR_rHydSystemPressMAX_STOP _x000D_",
- "reset_cn": "当前WTG处于在Selftest3状态,且输入变量的值小于参数设定值",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_09_006": {
- "subsystem": "HSBrakeSystem",
- "name": "SC_HydrPressureSystemMainCircuitMin_Warning",
- "en": "1s average Hydraulic pressure below low value(Set by parameter)",
- "cn": "液压系统主回路压力低于下限值警告",
- "powerup_delay": "T#3m",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "if below statements are all TRUE,_x000D_ 1. NOT (giTurbineOperationMode = CON_iSelftest3)_x000D_ 2.NOT (gbDQ_Gen1YawBrake1 OR gbDQ_Gen1YawBrake2 OR TPDelayForYaw.Q)_x000D_ 3. (grHydrPressureSump_1sec <PAR_rHydSystemPressMainCircuitMIN_Warn)",
- "trigger_cn": "1. 当前WTG不在Selftest3状态_x000D_ 2. 偏航刹车不在工作中_x000D_ 3. 输入变量的值高于参数设定值",
- "set_delay": "T#10s",
- "yp": "0",
- "reset_en": "if any one of below statement is not TRUE,_x000D_ 1. NOT (giTurbineOperationMode = CON_iSelftest3)_x000D_ 2.NOT (gbDQ_Gen1YawBrake1 OR gbDQ_Gen1YawBrake2 OR TPDelayForYaw.Q)_x000D_ 3. (grHydrPressureSump_1sec <PAR_rHydSystemPressMainCircuitMIN_Warn)",
- "reset_cn": "以下任一条件满足,_x000D_ 1. 当前WTG处于在selftest3 状态_x000D_ 2. 偏航刹车进行中_x000D_ 3. 输入变量大于预设低限报警值",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_09_007": {
- "subsystem": "HSBrakeSystem",
- "name": "SC_HydrPressureSystemMainCircuitMin_STOP",
- "en": "1s average Hydraulic pressure below MIN limit.",
- "cn": "液压系统主回路压力低于下限值故障",
- "powerup_delay": "T#3m",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "if below statements are all TRUE,_x000D_ 1. NOT (giTurbineOperationMode = CON_iSelftest3)_x000D_ 2.NOT (gbDQ_Gen1YawBrake1 OR gbDQ_Gen1YawBrake2 OR TPDelayForYaw.Q)_x000D_ 3. (grHydrPressureSump_1sec <PAR_rHydSystemPressMainCircuitMIN_STOP)",
- "trigger_cn": "1. 当前WTG不在Selftest3状态_x000D_ 2. 偏航刹车不在工作中_x000D_ 3. 输入变量的值小于参数设定值",
- "set_delay": "T#10s",
- "yp": "0",
- "reset_en": "if any one of below statement is not TRUE,_x000D_ 1. NOT (giTurbineOperationMode = CON_iSelftest3)_x000D_ 2.NOT (gbDQ_Gen1YawBrake1 OR gbDQ_Gen1YawBrake2 OR TPDelayForYaw.Q)_x000D_ 3. (grHydrPressureSump_1sec <PAR_rHydSystemPressMainCircuitMIN_STOP)",
- "reset_cn": "以下任一条件满足,_x000D_ 1. 当前WTG处于在selftest3 状态_x000D_ 2. 偏航刹车进行中_x000D_ 3. 输入变量大于预设最小值",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "100"
- },
- "02_09_008": {
- "subsystem": "HSBrakeSystem",
- "name": "OC_ManualControlHydrPump",
- "en": "Manual control Mode of Hydr Pump Active",
- "cn": "液压泵手动控制模式",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "02_09_009": {
- "subsystem": "HSBrakeSystem",
- "name": "OC_ForceControlHydrPump",
- "en": "Force Control Mode of Hydr Pump Active",
- "cn": "液压泵强制控制模式",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "02_09_010": {
- "subsystem": "HSBrakeSystem",
- "name": "OC_RemControlHydrStart",
- "en": "Remote start Hydr pump",
- "cn": "远程控制液压泵启动",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "02_09_011": {
- "subsystem": "HSBrakeSystem",
- "name": "OC_ManualControlHSBrk",
- "en": "Manual Control OF HS Brk",
- "cn": "手动控制液压刹车",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "51"
- },
- "02_09_017": {
- "subsystem": "HSBrakeSystem",
- "name": "SC_HydrPumpTime_MAX",
- "en": "Hydraulic pump is on too long",
- "cn": "液压泵运行时间过长",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "3",
- "repeat_period": "T#1h",
- "trigger_en": "The ON-time of the hydraulic pump exceeds the maximum allowed time (given by parameter).(DQ_NacelleHydrPump=1)",
- "trigger_cn": "液压泵运行时间高于上限值。(DQ_NacelleHydrPump=1)",
- "set_delay": "PAR_tDelayHydPumpTime_MAX",
- "yp": "0",
- "reset_en": "The ON-time of the hydraulic pump falls below the maximum allowed time (given by parameter).(DQ_NacelleHydrPump=0)",
- "reset_cn": "液压泵运行时间回归到上限值以内。(DQ_NacelleHydrPump=0)",
- "reset_mode": "M",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_09_018": {
- "subsystem": "HSBrakeSystem",
- "name": "SC_RepFault_HydrPumpTime_MAX",
- "en": "The fault, pump is on too long, has repeated",
- "cn": "液压泵运行时间过长故障重复出现",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The statuscode \"SC_HydrPressureSystemMin_Warning\" in a given time periode becomes more times TRUE than maximum allowed.(gbRepeat_02_09_001=1)",
- "trigger_cn": "液压泵运行时间过长故障重复出现。(gbRepeat_02_09_001=1)",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "The statuscode \"SC_HydrPressureSystemMin_Warning\" in a given time periode becomes less times TRUE than maximum allowed.(gbRepeat_02_09_001=0)",
- "reset_cn": "液压泵运行时间过长故障不重复出现。(gbRepeat_02_09_001=0)",
- "reset_mode": "M",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_09_019": {
- "subsystem": "HSBrakeSystem",
- "name": "SC_HydrPumpDecompressionTimeOut",
- "en": "Hydr system decompression to 0bar time out",
- "cn": "液压系统泄压超时",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "When the hydr system pressure don't decompress to 0bar in a certain time after the valve2 of gen1 yaw brake open(grHydrPressureSump_1sec > PAR_rPressToReleaseYawMotor_MIN + PAR_rPressHysteresisUpper)",
- "trigger_cn": "在Gen1偏航刹车电磁阀2打开后主回路压力没有在一定的时间里泄压到0bar。",
- "set_delay": "PAR_tDelayForHydraulicsDecompression",
- "yp": "100",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_09_020": {
- "subsystem": "HSBrakeSystem",
- "name": "SC_HydrPumpCompressionLevel1TimeOut",
- "en": "Hydr system compression to 20bar time out",
- "cn": "液压系统打压超时",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "When the hydr system pressure don't compress to 20bar in a certain time after the valve2 of gen1 yaw brake closes(grHydrPressureSump_1sec < PAR_rPressToReleaseYawMotor_MAX - PAR_rPressHysteresisLower)",
- "trigger_cn": "在Gen1偏航刹车电磁阀2关闭后主回路压力没有在一定的时间里打压到20bar。",
- "set_delay": "PAR_tDelayForHydraulicsCompressionLevel1",
- "yp": "100",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_09_021": {
- "subsystem": "HSBrakeSystem",
- "name": "SC_HydrPumpTooManyStarts",
- "en": "Hydraulic pump is turned on too frequently",
- "cn": "液压泵开启过于频繁",
- "powerup_delay": "T#30s",
- "disable_level": "20",
- "repeat_n": "PAR_iNumberMaxStartHydPump",
- "repeat_period": "PAR_tIntervalMaxStartHydPump",
- "trigger_en": "During a given time periode the \"ON status\" of the hydraulic pump exceeds the maximum allowed number (given by the initial values for the statuscode).(PAR_iNumberMaxStartHydPump > 0 AND iRepCount >= PAR_iNumberMaxStartHydPump)",
- "trigger_cn": "液压泵在一定时间内开启次数高于最大值。(PAR_iNumberMaxStartHydPump > 0 AND iRepCount >= PAR_iNumberMaxStartHydPump)",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "Get reset signal of status code coming from Nacelle, Tower or Remote Command.(gbMAIN_ResetStatusCodes=1)",
- "reset_cn": "收到reset信号。(gbMAIN_ResetStatusCodes=1)",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_09_024": {
- "subsystem": "HSBrakeSystem",
- "name": "SC_UnfilHydraulicLoadManual",
- "en": "Hydraulic Unfill Load By Manual",
- "cn": "用户手动释放液压系统压力",
- "powerup_delay": "T#0s",
- "disable_level": "50",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Unfill Hydraulic Pressure by Manual(PAR_UnfilHydraulicLoad=1)",
- "trigger_cn": "用户手动释放液压系统压力PAR_UnfilHydraulicLoad=1",
- "set_delay": "T#0s",
- "yp": "30",
- "reset_en": "Stop Manual Unfill Hydraulic Pressure(PAR_UnfilHydraulicLoad=0)",
- "reset_cn": "PAR_UnfilHydraulicLoad=1",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "30-待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "30",
- "brake_state_design": "51"
- },
- "02_09_033": {
- "subsystem": "HSBrakeSystem",
- "name": "SC_HYDSumpLevelLow",
- "en": "HYDSumpLevel too low",
- "cn": "液压站液位低",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "t#0S",
- "trigger_en": "IF NOT gbDI_HYDSumpLevel",
- "trigger_cn": "如果gbDI_HYDSumpLevel为0",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "03_09_005": {
- "subsystem": "HSBrakeSystem",
- "name": "SC_SELFTEST_BrakeTestFailed",
- "en": "Braking function selftest fails",
- "cn": "刹车功能自检失败",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Braking function selftest fails.(gbBrakeTestFailure=1)",
- "trigger_cn": "刹车功能自检失败。(gbBrakeTestFailure=1)",
- "set_delay": "T#5s",
- "yp": "0",
- "reset_en": "Braking function selftest suceeds.(gbBrakeTestFailure=0)",
- "reset_cn": "刹车功能自检成功。(gbBrakeTestFailure=0)",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "100"
- },
- "03_06_002": {
- "subsystem": "LogSystem",
- "name": "SC_LogErrorRingBufferStatuscodes",
- "en": "Status code logging error",
- "cn": "状态字数据记录出错",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "When any fault will be detected during initialization or writing one of the logs for \"Ring Buffer Statuscodes\" to the hard disc.(fbSCLogger.iErrCounterEventData <> iErrCounterLast)",
- "trigger_cn": "在初始化或将状态字数据写到硬盘上的日志中记录出错。(fbSCLogger.iErrCounterEventData <> iErrCounterLast)",
- "set_delay": "T#50ms",
- "yp": "0",
- "reset_en": "When no fault will be detected during initialization and writing one of the logs for \"Ring Buffer Statuscodes\" to the hard disc.(fbSCLogger.iErrCounterEventData = iErrCounterLast)",
- "reset_cn": "在初始化和将状态字数据写到硬盘上的日志中未记录出错。(fbSCLogger.iErrCounterEventData = iErrCounterLast)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "03_06_011": {
- "subsystem": "LogSystem",
- "name": "SC_LogErrorTrace",
- "en": "Error trace logging error",
- "cn": "Tracelog记录出错",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "When any fault will be detected during initialization or writing one of the logs for power curves to the hard disc.(PRG_MAIN_TraceLogger.iErrCounter <> iErrCounterLast)",
- "trigger_cn": "写功率曲线到硬盘中的日志出错。_x000D_ (PRG_MAIN_TraceLogger.iErrCounter <> iErrCounterLast)",
- "set_delay": "T#50ms",
- "yp": "0",
- "reset_en": "When no fault will be detected during initialization or writing one of the logs for power curves to the hard disc.(PRG_MAIN_TraceLogger.iErrCounter = iErrCounterLast)",
- "reset_cn": "写功率曲线到硬盘中的日志没有出错。_x000D_ (PRG_MAIN_TraceLogger.iErrCounter = iErrCounterLast)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "01_05_001": {
- "subsystem": "Pitchsystem",
- "name": "SC_Blade1_OnePitchSensorDefect",
- "en": "Blade1 has angle sensors defect",
- "cn": "1号桨出现角度传感器故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The bit for \"EncoderIncoherence\" sent from the pitchsystem becomes TRUE OR the difference between the signals for pitch angle measured by the two position encoders for this axis / blade is higher than a parameter, and data from PitchSystem is valid.(ABS (grPitchAngle1Blade1 - grPitchAngle2Blade1) > _x000D_ PAR_rMaxDiffSensorsBladeAngle_PitchLimit5) OR di_Blade1_EncoderIncoherence=1) AND di_Pitch_MaintenanceMode!=1 AND gbDQ_PitchManualMode!=1",
- "trigger_cn": "如果变桨系统报“叶片1一秒前后的角度差大于2或叶片1的变桨不连续”(ABS (grPitchAngle1Blade1 - grPitchAngle2Blade1) > _x000D_ PAR_rMaxDiffSensorsBladeAngle_PitchLimit5) OR di_Blade1_EncoderIncoherence=1)并且从变桨系统过来的数据是有效的di_Pitch_MaintenanceMode!=1 AND gbDQ_PitchManualMode!=1",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "Blade1 angle sensors is OK and special individual reset-conditions are fulfilled OR the data received from pitch system are not valid①(ABS (grPitchAngle1Blade1 - grPitchAngle2Blade1) ≦ _x000D_ PAR_rMaxDiffSensorsBladeAngle_PitchLimit5) AND di_Blade1_EncoderIncoherence=0 AND bSpecResCond=1)②di_Pitch_MaintenanceMode=1 OR gbDQ_PitchManualMode=1",
- "reset_cn": "①1号桨角度传感器恢复正常(ABS (grPitchAngle1Blade1 - grPitchAngle2Blade1) ≦ _x000D_ PAR_rMaxDiffSensorsBladeAngle_PitchLimit5) AND di_Blade1_EncoderIncoherence=0 AND bSpecResCond=1);②从变桨系统过来的数据是无效的di_Pitch_MaintenanceMode=1 OR gbDQ_PitchManualMode=1",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "198"
- },
- "01_05_003": {
- "subsystem": "PitchSystem",
- "name": "SC_PitchModeFeedbackError",
- "en": "PitchModeFeedbackError",
- "cn": "变桨系统状态反馈错误",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "IF NOT dqPitchSystemNormalOperationMode AND di_Pitch_NormalOperation AND NOT gbProfibusPitchDisturbed THEN _x000D_ SC become true_x000D_",
- "trigger_cn": "如果主控使变桨不在正常状态,但是变桨反馈在正常状态,且没有profibus故障时,则报出该故障",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "01_05_004": {
- "subsystem": "PitchSystem",
- "name": "SC_Blade1_DetachEndPos91Failed",
- "en": "Blade1 Detach EndPos91 Failed",
- "cn": "1号桨叶从91度限位脱开失败",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "IF di_Pitch_NormalOperation AND di_Blade1_EndPos91Deg AND NOT (giTurbineOperationMode=CON_iSelftest2)_x000D_ THEN_x000D_ SC=TRUE_x000D_",
- "trigger_cn": "变桨系统NormalMode信号正常di_Pitch_NormalOperation),如果检测到变桨1号桨叶触发限位开关,并且不在自检2的情况下,则延时5s报故障停机",
- "set_delay": "T#5s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "01_05_005": {
- "subsystem": "PitchSystem",
- "name": "SC_Blade2_DetachEndPos91Failed",
- "en": "Blade2 Detach EndPos91 Failed",
- "cn": "2号桨叶从91度限位脱开失败",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "IF di_Pitch_NormalOperation AND di_Blade2_EndPos91Deg AND NOT (giTurbineOperationMode=CON_iSelftest2)_x000D_ THEN_x000D_ SC=TRUE",
- "trigger_cn": "变桨系统NormalMode信号正常di_Pitch_NormalOperation),如果检测到变桨2号桨叶触发限位开关,并且不在自检2的情况下,则延时5s报故障停机",
- "set_delay": "T#5s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "01_05_006": {
- "subsystem": "PitchSystem",
- "name": "SC_Blade3_DetachEndPos91Failed",
- "en": "Blade3 Detach EndPos91 Failed",
- "cn": "3号桨叶从91度限位脱开失败",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "IF di_Pitch_NormalOperation AND di_Blade3_EndPos91Deg AND NOT (giTurbineOperationMode=CON_iSelftest2)_x000D_ THEN_x000D_ SC=TRUE",
- "trigger_cn": "变桨系统NormalMode信号正常di_Pitch_NormalOperation),如果检测到变桨3号桨叶触发限位开关,并且不在自检2的情况下,则延时5s报故障停机",
- "set_delay": "T#5s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "01_05_009": {
- "subsystem": "Pitchsystem",
- "name": "SC_Blade1_EndPos95Deg",
- "en": "Blade1 95-degree end switch is tripped",
- "cn": "1号桨的95度限位开关被撞开",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Blade1 95-degree end switch is tripped.(di_Blade1_EndPos95Deg = 1)",
- "trigger_cn": "如果变桨系统报“叶片1撞开95度限位开关”(di_Blade1_EndPos95Deg = 1)",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "Blade1 95-degree end switch is recovered: di_Blade1_EndPos95Deg=0",
- "reset_cn": "95度限位开关脱离di_Blade1_EndPos95Deg=0",
- "reset_mode": "M",
- "type": "A",
- "alarm": "True",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "100"
- },
- "01_05_011": {
- "subsystem": "Pitchsystem",
- "name": "SC_Blade1_EndPos91Deg",
- "en": "Blade1 91-degree end switch is tripped",
- "cn": "1号桨的91度限位开关被撞开",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Blade1 91-degree end switch is tripped.(giTurbineOperationMode≠CON_iSelftest2 AND giTurbineOperationMode≠CON_iSelftest3 AND di_Blade1_EndPos91Deg=1)",
- "trigger_cn": "如果变桨系统报“当前风机运行模式不在自检2和自检3且叶片1撞开91度限位开关”。(giTurbineOperationMode≠CON_iSelftest2 AND giTurbineOperationMode≠CON_iSelftest3 AND di_Blade1_EndPos91Deg=1)",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "The Turbine Operation Mode is selftest2 or selftest3, or Blade1 91-degree end switch is recovered and special individual reset-conditions are fulfilled.(giTurbineOperationMode=13 OR giTurbineOperationMode=14 OR di_Blade1_EndPos91Deg=0) AND bSpecResCond=1",
- "reset_cn": "风机运行在自检2或自检3或叶片1的91度限位开关脱离。(giTurbineOperationMode=13 OR giTurbineOperationMode=14 OR di_Blade1_EndPos91Deg=0) AND bSpecResCond=1",
- "reset_mode": "M",
- "type": "A",
- "alarm": "True",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "51"
- },
- "01_05_016": {
- "subsystem": "Pitchsystem",
- "name": "SC_Blade1_PositionIncoherence",
- "en": "Blade1 position is incoherent",
- "cn": "1号桨实际值与给定值相差过大",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Pitch in NormalOperation AND giTurbineOperationMode=CON_iGridOperation_x000D_ AND ABS (grPitchAngle1Blade1-aqPitchAngle_SetValueBlade1)>2_x000D_ AND Blade1 position is incoherent.(di_Blade1_PositionIncoherence=1)",
- "trigger_cn": "在并网且变桨处于正常模式下,如果变桨系统报“叶片1的位置变化不连贯”且实际桨矩角和设置值相差超过2度(di_Blade1_PositionIncoherence=1)",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "Blade1 position is coherent and special individual reset-conditions are fulfilled(di_Blade1_PositionIncoherence=0 AND bSpecResCond=1)",
- "reset_cn": "叶片1的位置变化是连贯的(di_Blade1_PositionIncoherence=0 AND bSpecResCond=1)",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "198"
- },
- "01_05_021": {
- "subsystem": "Pitchsystem",
- "name": "SC_Blade2_OnePitchSensorDefect",
- "en": "Blade2 has angle sensors defect",
- "cn": "2号桨出现角度传感器故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The bit for \"EncoderIncoherence\" sent from the pitchsystem becomes TRUE OR the difference between the signals for pitch angle measured by the two position encoders for this axis / blade is higher than a parameter.(ABS (grPitchAngle1Blade2 - grPitchAngle2Blade2) > _x000D_ 2) )",
- "trigger_cn": "如果变桨系统报“叶片2一秒前后的角度差大于2或叶片2的变桨不连续”(ABS (grPitchAngle1Blade2 - grPitchAngle2Blade2) > _x000D_ 2) OR di_Blade2_EncoderIncoherence=1)",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "①The bit for \"EncoderIncoherence\" sent from the pitchsystem becomes FALSE AND the difference between the signals for pitch angle measured by the two position encoders for this axis / blade is lower than a parameter.(ABS (grPitchAngle1Blade2 - grPitchAngle2Blade2) ≦ _x000D_ PAR_rMaxDiffSensorsBladeAngle_PitchLimit5) AND di_Blade2_EncoderIncoherence=0 AND bSpecResCond=1)。②Data received from pitch system are not valid.(di_Pitch_MaintenanceMode=1 OR gbDQ_PitchManualMode=1 OR di_Pitch_DataValid=0)AND bSpecResCond=1",
- "reset_cn": "①叶片2一秒前后的角度差不大于2且叶片2的变桨连续。(ABS (grPitchAngle1Blade2 - grPitchAngle2Blade2) ≦ _x000D_ PAR_rMaxDiffSensorsBladeAngle_PitchLimit5) AND di_Blade2_EncoderIncoherence=0 AND bSpecResCond=1)。②当从变桨系统过来的数据是无效时。(di_Pitch_MaintenanceMode=1 OR gbDQ_PitchManualMode=1 OR di_Pitch_DataValid=0)AND bSpecResCond=1",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "198"
- },
- "01_05_029": {
- "subsystem": "Pitchsystem",
- "name": "SC_Blade2_EndPos95Deg",
- "en": "Blade2 95-degree end switch is tripped",
- "cn": "2号桨的95度限位开关被撞开",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Blade2 95-degree end switch is tripped.(di_Blade2_EndPos95Deg = 1)",
- "trigger_cn": "如果变桨系统报“叶片2撞开95度行程开关”(di_Blade2_EndPos95Deg = 1)。",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "Blade2 95-degree end switch is recovered and special individual reset-conditions are fulfilled(di_Blade2_EndPos95Deg = 0 AND bSpecResCond=1)",
- "reset_cn": "95度限位开关脱离(di_Blade2_EndPos95Deg = 0 AND bSpecResCond=1)",
- "reset_mode": "M",
- "type": "A",
- "alarm": "True",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "100"
- },
- "01_05_031": {
- "subsystem": "Pitchsystem",
- "name": "SC_Blade2_EndPos91Deg",
- "en": "Blade2 91-degree end switch is tripped",
- "cn": "2号桨的91度限位开关被撞开",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The Turbine Operation Mode is not selftest2 and selftest3, Blade2 91-degree end switch is tripped.(giTurbineOperationMode≠CON_iSelftest2 AND giTurbineOperationMode≠CON_iSelftest3 AND di_Blade2_EndPos91Deg=1)",
- "trigger_cn": "如果变桨系统报“当前风机运行模式不在自检2和自检3且叶片2撞开91度限位开关”(giTurbineOperationMode≠CON_iSelftest2 AND giTurbineOperationMode≠CON_iSelftest3 AND di_Blade2_EndPos91Deg=1)",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "The Turbine Operation Mode is selftest2 or selftest3, or Blade2 91-degree end switch is recovered and special individual reset-conditions are fulfilled.(giTurbineOperationMode=CON_iSelftest2 OR giTurbineOperationMode=CON_iSelftest3 OR di_Blade2_EndPos91Deg=0) AND bSpecResCond=1",
- "reset_cn": "风机进入在自检2或自检3或叶片2的91度限位开关脱离。(giTurbineOperationMode=CON_iSelftest2 OR giTurbineOperationMode=CON_iSelftest3 OR di_Blade2_EndPos91Deg=0) AND bSpecResCond=1",
- "reset_mode": "M",
- "type": "A",
- "alarm": "True",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "51"
- },
- "01_05_036": {
- "subsystem": "Pitchsystem",
- "name": "SC_Blade2_PositionIncoherence",
- "en": "Blade2 position is incoherent",
- "cn": "2号桨实际值与给定值相差过大",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Pitch in NormalOperation AND giTurbineOperationMode=CON_iGridOperation_x000D_ AND ABS (grPitchAngle1Blade2-aqPitchAngle_SetValueBlade2)>2_x000D_ AND Blade2 position is incoherent.(di_Blade2_PositionIncoherence=1)",
- "trigger_cn": "在并网且变桨处于正常模式下,如果变桨系统报“叶片2的位置变化不连贯”且实际桨矩角和设置值相差超过2度(di_Blade2_PositionIncoherence=1)",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "Blade2 position is coherent and special individual reset-conditions are fulfilled(di_Blade2_PositionIncoherence=0 AND bSpecResCond=1)",
- "reset_cn": "叶片2的位置变化是连贯的(di_Blade2_PositionIncoherence=0 AND bSpecResCond=1)",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "198"
- },
- "01_05_041": {
- "subsystem": "Pitchsystem",
- "name": "SC_Blade3_OnePitchSensorDefect",
- "en": "Blade3 has angle sensors defect",
- "cn": "3号桨出现角度传感器故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The bit for \"EncoderIncoherence\" sent from the pitchsystem becomes TRUE OR the difference between the signals for pitch angle measured by the two position encoders for this axis / blade is higher than a parameter.(ABS (grPitchAngle1Blade3 - grPitchAngle2Blade3) > _x000D_ PAR_rMaxDiffSensorsBladeAngle_PitchLimit5) OR di_Blade3_EncoderIncoherence=1)",
- "trigger_cn": "如果变桨系统报“叶片3一秒前后的角度差大于2或叶片2的变桨不连续”(ABS (grPitchAngle1Blade3 - grPitchAngle2Blade3) > _x000D_ PAR_rMaxDiffSensorsBladeAngle_PitchLimit5) OR di_Blade3_EncoderIncoherence=1)",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "①The bit for \"EncoderIncoherence\" sent from the pitchsystem becomes FALSE OR the difference between the signals for pitch angle measured by the two position encoders for this axis / blade is lower than a parameter.(ABS (grPitchAngle1Blade3 - grPitchAngle2Blade3) ≦ _x000D_ PAR_rMaxDiffSensorsBladeAngle_PitchLimit5 AND di_Blade3_EncoderIncoherence=0;②Data received from pitch system are not valid(di_Pitch_MaintenanceMode=1 OR gbDQ_PitchManualMode=1 OR di_Pitch_DataValid=0)",
- "reset_cn": "①3号桨出现角度传感器正常(ABS (grPitchAngle1Blade3 - grPitchAngle2Blade3) ≦ _x000D_ PAR_rMaxDiffSensorsBladeAngle_PitchLimit5 AND di_Blade3_EncoderIncoherence=0;②从变桨系统过来的数据是无效的di_Pitch_MaintenanceMode=1 OR gbDQ_PitchManualMode=1 OR di_Pitch_DataValid=0",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "198"
- },
- "01_05_049": {
- "subsystem": "Pitchsystem",
- "name": "SC_Blade3_EndPos95Deg",
- "en": "Blade3 95-degree end switch is tripped",
- "cn": "3号桨的95度限位开关被撞开",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Blade3 95-degree end switch is tripped.(di_Blade3_EndPos95Deg = 1)",
- "trigger_cn": "如果变桨系统报“叶片3撞开95度行程开关”(di_Blade3_EndPos95Deg = 1)",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "Blade3 95-degree end switch is recovered and special individual reset-conditions are fulfilled(di_Blade3_EndPos95Deg = 0 AND bSpecResCond=1)",
- "reset_cn": "95度限位开关脱离(di_Blade3_EndPos95Deg = 0 AND bSpecResCond=1)",
- "reset_mode": "M",
- "type": "A",
- "alarm": "True",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "100"
- },
- "01_05_051": {
- "subsystem": "Pitchsystem",
- "name": "SC_Blade3_EndPos91Deg",
- "en": "Blade3 91-degree end switch is tripped",
- "cn": "3号桨的91度限位开关被撞开",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The Turbine Operation Mode is not selftest2 and selftest3, Blade3 91-degree end switch is tripped.(giTurbineOperationMode≠CON_iSelftest2 AND giTurbineOperationMode≠CON_iSelftest3 AND di_Blade3_EndPos91Deg=1)",
- "trigger_cn": "如果变桨系统报“当前风机运行模式不在自检2和自检3且叶片3撞开91度限位开关”。(giTurbineOperationMode≠CON_iSelftest2 AND giTurbineOperationMode≠CON_iSelftest3 AND di_Blade3_EndPos91Deg=1)",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "The Turbine Operation Mode is selftest2 or selftest3, or Blade3 91-degree end switch is recovered and special individual reset-conditions are fulfilled.(giTurbineOperationMode=CON_iSelftest2 OR giTurbineOperationMode=CON_iSelftest3 OR di_Blade3_EndPos91Deg=0) AND bSpecResCond=1",
- "reset_cn": "风机运行在自检2或自检3或叶片3的91度限位开关脱离。(giTurbineOperationMode=CON_iSelftest2 OR giTurbineOperationMode=CON_iSelftest3 OR di_Blade3_EndPos91Deg=0) AND bSpecResCond=1",
- "reset_mode": "M",
- "type": "A",
- "alarm": "True",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "51"
- },
- "01_05_056": {
- "subsystem": "Pitchsystem",
- "name": "SC_Blade3_PositionIncoherence",
- "en": "Blade3 position is incoherent",
- "cn": "3号桨实际值与给定值相差过大",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Pitch in NormalOperation AND giTurbineOperationMode=CON_iGridOperation_x000D_ AND ABS (grPitchAngle1Blade3-aqPitchAngle_SetValueBlade3)>2_x000D_ AND Blade3 position is incoherent.(di_Blade3_PositionIncoherence=1)",
- "trigger_cn": "在并网且变桨处于正常模式下,如果变桨系统报“叶片3的位置变化不连贯”且实际桨矩角和设置值相差超过2度(di_Blade3_PositionIncoherence=1)",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "Blade3 position is coherent and special individual reset-conditions are fulfilled(di_Blade3_PositionIncoherence=0 AND bSpecResCond=1)",
- "reset_cn": "叶片3的位置变化是连贯的(di_Blade3_PositionIncoherence=0 AND bSpecResCond=1)",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "198"
- },
- "01_05_063": {
- "subsystem": "Pitchsystem",
- "name": "SC_AllBlades_EndPos91Or95",
- "en": "Blades 1 and 2 and 3 all trip 91 or 95 degrees end switches",
- "cn": "1号,2号和3号桨都撞开91度或95度限位开关",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Blades 1 and 2 and 3 all trip 91 degrees end switches,and WTG is not in selftest2, selftest3 and 198 brakemode. (giTurbineOperationMode≠13 AND giTurbineOperationMode≠14 AND giBPLevel≠198 AND gbDI_NacellePitchAllBladesInFeatherPos=1)",
- "trigger_cn": "如果变桨系统报“1号,2号和3号桨都撞开91度限位开关”,并且不处于自检2、自检3以及198号刹车中。(giTurbineOperationMode≠13 AND giTurbineOperationMode≠14 AND giBPLevel≠198 AND gbDI_NacellePitchAllBladesInFeatherPos=1)",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "Blade1,2,3 95-degree end switch is recovered or WTG runs in selftest2, selftest3 mode or in 198 brakemode. (giTurbineOperationMode=13 OR giTurbineOperationMode=14 OR giBPLevel=198 OR gbDI_NacellePitchAllBladesInFeatherPos=O)",
- "reset_cn": "叶片1,2和3的91度限位开关脱离或者风机处于自检2或自检3或者处于198号刹车。_x000D_ (giTurbineOperationMode=13 OR giTurbineOperationMode=14 OR giBPLevel=198 OR gbDI_NacellePitchAllBladesInFeatherPos=O)",
- "reset_mode": "M",
- "type": "A",
- "alarm": "True",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "100"
- },
- "01_05_064": {
- "subsystem": "Pitchsystem",
- "name": "SC_PitchEmergencyMode",
- "en": "Pitch system is in emergency mode",
- "cn": "变桨系统处在紧急模式",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Pitch system is in emergency mode.(di_Pitch_EmergencyMode=1)",
- "trigger_cn": "如果变桨系统报“变桨系统处在紧急模式”(di_Pitch_EmergencyMode=1)",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "Pitch system is out of emergency mode.(di_Pitch_EmergencyMode=0 AND bSpecResCond=1)",
- "reset_cn": "变桨系统脱离紧急模式(di_Pitch_EmergencyMode=0 AND bSpecResCond=1)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "01_05_072": {
- "subsystem": "Pitchsystem",
- "name": "SC_Pitch_SyncError_Limit1_5s",
- "en": "The difference between the maximum and minimum blade angle of the three blades (1-sec-mean-value) exceeds the given value for more than 5 s.",
- "cn": "两桨叶间的角度差大于设定值(相差1度持续10秒)",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "2",
- "repeat_period": "T#12h",
- "trigger_en": "All Below Conditions are fullfilled: 1. BlockMonitoring=false(BlockMonitoring=(giTurbineOperationMode = CON_iSelftest2 OR_x000D_ giTurbineOperationMode = CON_iSelftest3 OR_x000D_ grPitchAngle >= PAR_rPitchAngleSetValueVanePosition OR giBPLevel>=198)2.difference between max and min blade angle exceeds certain value(IF PAR_bAsymControlEn AND gbReleaseExternalPitchAndTorqueController : the condition can be formulated: ABS (grPitchSyncErrorRaw) >_x000D_ PAR_rMaxDiffSensorsBladeAngle_PitchLimit1+ ABS(PitchDeltaDiff)+ ABS(PitchScaleDiff) ; otherwise, the condition is : ABS(grPitchSyncError) >_x000D_ PAR_rMaxDiffSensorsBladeAngle_PitchLimit1 3.di_Pitch_MaintenanceMode =FALSE AND gbDQ_PitchManualMode=FALSE )4. (gbDI_NacellePitchAllBladesInFeatherPos=FALSE)",
- "trigger_cn": "风机满足如下所有条件:1.风机不满足BlockMonitoring条件(BlockMonitoring:刹车等级大于等于198或者风机运行模式在13或14模式时,或者桨叶角度大于设定值(giTurbineOperationMode = CON_iSelftest2 OR_x000D_ giTurbineOperationMode = CON_iSelftest3 OR_x000D_ grPitchAngle >= PAR_rPitchAngleSetValueVanePosition OR giBPLevel>=198)2.两桨叶间的角度差大于设定值(当非对称变浆功能打开,外部变浆控制器释放时,此条件为ABS (grPitchSyncErrorRaw) >_x000D_ PAR_rMaxDiffSensorsBladeAngle_PitchLimit1+ ABS(PitchDeltaDiff)+ ABS(PitchScaleDiff) ; 否则,此条件为ABS(grPitchSyncError) >_x000D_ PAR_rMaxDiffSensorsBladeAngle_PitchLimit1 3.变桨系统不处于维护模式或者手动控制模式 ( di_Pitch_MaintenanceMode =FALSE AND gbDQ_PitchManualMode=FALSE )4. 桨叶没有撞到限位开关(gbDI_NacellePitchAllBladesInFeatherPos=FALSE)",
- "set_delay": "T#10s",
- "yp": "0",
- "reset_en": "At least One Below Conditions are not fullfilled: 1. BlockMonitoring=false(BlockMonitoring=(giTurbineOperationMode = CON_iSelftest2 OR_x000D_ giTurbineOperationMode = CON_iSelftest3 OR_x000D_ grPitchAngle >= PAR_rPitchAngleSetValueVanePosition OR giBPLevel>=198)2.difference between max and min blade angle exceeds certain value(IF PAR_bAsymControlEn AND gbReleaseExternalPitchAndTorqueController : the condition can be formulated: ABS (grPitchSyncErrorRaw) >_x000D_ PAR_rMaxDiffSensorsBladeAngle_PitchLimit1+ ABS(PitchDeltaDiff)+ ABS(PitchScaleDiff) ; otherwise, the condition is : ABS(grPitchSyncError) >_x000D_ PAR_rMaxDiffSensorsBladeAngle_PitchLimit1 3.di_Pitch_MaintenanceMode =FALSE AND gbDQ_PitchManualMode=FALSE )4. (gbDI_NacellePitchAllBladesInFeatherPos=FALSE)",
- "reset_cn": "如下条件中至少一个风机不满足:1.风机不满足BlockMonitoring条件(BlockMonitoring:刹车等级大于等于198或者风机运行模式在13或14模式时,或者桨叶角度大于设定值(giTurbineOperationMode = CON_iSelftest2 OR_x000D_ giTurbineOperationMode = CON_iSelftest3 OR_x000D_ grPitchAngle >= PAR_rPitchAngleSetValueVanePosition OR giBPLevel>=198)2.两桨叶间的角度差大于设定值(当非对称变浆功能打开,外部变浆控制器释放时,此条件为ABS (grPitchSyncErrorRaw) >_x000D_ PAR_rMaxDiffSensorsBladeAngle_PitchLimit1+ ABS(PitchDeltaDiff)+ ABS(PitchScaleDiff) ; 否则,此条件为ABS(grPitchSyncError) >_x000D_ PAR_rMaxDiffSensorsBladeAngle_PitchLimit1 3.变桨系统不处于维护模式或者手动控制模式 ( di_Pitch_MaintenanceMode =FALSE AND gbDQ_PitchManualMode=FALSE )4. 桨叶没有撞到限位开关(gbDI_NacellePitchAllBladesInFeatherPos=FALSE)",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "198"
- },
- "01_05_073": {
- "subsystem": "Pitchsystem",
- "name": "SC_Pitch_SyncError_Limit2_1s",
- "en": "The difference between the maximum and minimum blade angle of the three blades (1-sec-mean-value)exceeds the given value for more than 1 s.",
- "cn": "两桨叶间的角度差大于设定值(相差2度持续200毫秒)",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "2",
- "repeat_period": "T#12h",
- "trigger_en": "All Below Conditions are fullfilled: 1. BlockMonitoring=false(BlockMonitoring=(giTurbineOperationMode = CON_iSelftest2 OR_x000D_ giTurbineOperationMode = CON_iSelftest3 OR_x000D_ grPitchAngle >= PAR_rPitchAngleSetValueVanePosition OR giBPLevel>=198)2.difference between max and min blade angle exceeds certain value(IF PAR_bAsymControlEn AND gbReleaseExternalPitchAndTorqueController : the condition can be formulated: ABS (grPitchSyncErrorRaw) >_x000D_ PAR_rMaxDiffSensorsBladeAngle_PitchLimit2+ ABS(PitchDeltaDiff)+ ABS(PitchScaleDiff) ; otherwise, the condition is : ABS (grPitchSyncError) > PAR_rMaxDiffSensorsBladeAngle_PitchLimit2) ) 3.di_Pitch_MaintenanceMode =FALSE AND gbDQ_PitchManualMode=FALSE )4. (gbDI_NacellePitchAllBladesInFeatherPos=FALSE)",
- "trigger_cn": "风机满足如下所有条件:1.风机不满足BlockMonitoring条件(BlockMonitoring:刹车等级大于等于198或者风机运行模式在13或14模式时,或者桨叶角度大于设定值(giTurbineOperationMode = CON_iSelftest2 OR_x000D_ giTurbineOperationMode = CON_iSelftest3 OR_x000D_ grPitchAngle >= PAR_rPitchAngleSetValueVanePosition OR giBPLevel>=198)2.两桨叶间的角度差大于设定值(当非对称变浆功能打开,外部变浆控制器释放时,此条件为ABS (grPitchSyncErrorRaw) >_x000D_ PAR_rMaxDiffSensorsBladeAngle_PitchLimit2+ ABS(PitchDeltaDiff)+ ABS(PitchScaleDiff) ; 否则,此条件为ABS (grPitchSyncError) > PAR_rMaxDiffSensorsBladeAngle_PitchLimit2) ) 3.变桨系统不处于维护模式或者手动控制模式 ( di_Pitch_MaintenanceMode =FALSE AND gbDQ_PitchManualMode=FALSE )4. 桨叶没有撞到限位开关(gbDI_NacellePitchAllBladesInFeatherPos=FALSE)",
- "set_delay": "T#200ms",
- "yp": "0",
- "reset_en": "At least One Below Conditions are not fullfilled: 1. BlockMonitoring=false(BlockMonitoring=(giTurbineOperationMode = CON_iSelftest2 OR_x000D_ giTurbineOperationMode = CON_iSelftest3 OR_x000D_ grPitchAngle >= PAR_rPitchAngleSetValueVanePosition OR giBPLevel>=198)2.difference between max and min blade angle exceeds certain value(IF PAR_bAsymControlEn AND gbReleaseExternalPitchAndTorqueController : the condition can be formulated: ABS (grPitchSyncErrorRaw) >_x000D_ PAR_rMaxDiffSensorsBladeAngle_PitchLimit1+ ABS(PitchDeltaDiff)+ ABS(PitchScaleDiff) ; otherwise, the condition is : ABS (grPitchSyncError) > PAR_rMaxDiffSensorsBladeAngle_PitchLimit2) ) 3.di_Pitch_MaintenanceMode =FALSE AND gbDQ_PitchManualMode=FALSE )4. (gbDI_NacellePitchAllBladesInFeatherPos=FALSE)",
- "reset_cn": "如下条件中至少一个风机不满足:1.风机不满足BlockMonitoring条件(BlockMonitoring:刹车等级大于等于198或者风机运行模式在13或14模式时,或者桨叶角度大于设定值(giTurbineOperationMode = CON_iSelftest2 OR_x000D_ giTurbineOperationMode = CON_iSelftest3 OR_x000D_ grPitchAngle >= PAR_rPitchAngleSetValueVanePosition OR giBPLevel>=198)2.两桨叶间的角度差大于设定值(当非对称变浆功能打开,外部变浆控制器释放时,此条件为ABS (grPitchSyncErrorRaw) >_x000D_ PAR_rMaxDiffSensorsBladeAngle_PitchLimit1+ ABS(PitchDeltaDiff)+ ABS(PitchScaleDiff) ; 否则,此条件为ABS (grPitchSyncError) > PAR_rMaxDiffSensorsBladeAngle_PitchLimit2) ) 3.变桨系统不处于维护模式或者手动控制模式 ( di_Pitch_MaintenanceMode =FALSE AND gbDQ_PitchManualMode=FALSE )4. 桨叶没有撞到限位开关(gbDI_NacellePitchAllBladesInFeatherPos=FALSE)",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "198"
- },
- "01_06_001": {
- "subsystem": "Pitchsystem",
- "name": "SC_PitchNoFeedBackEFC_Signal",
- "en": "Main controller does NOT get EFC feedback signal from pitch system",
- "cn": "主控制器没有收到来自变桨系统的EFC确认信号",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "bBlockMonitoring is true when WTG is in PowerUp, EFC Reset Progess or System Reset Progress. When bBlockMonitoring is false, turbine is not in Selftest2 and Selftest3, main controller does NOT get EFC feedback signal from pitch system.(bBlockMonitoring=0 AND gbEFC_ImpulsAtPowerUp=0 AND giTurbineOperationMode ≠ CON_iSelftest2 AND giTurbineOperationMode ≠ CON_iSelftest3 AND DQ_PitchEFCSignalForController=1 AND gbDI_PitchFeedBackEFC_OK=0 )_x000D_",
- "trigger_cn": "在EFC系统复位过程、风机刚上电中、系统复位过程中时bBlockMonitoring为True。当bBlockMonitoring为false,风机不处于自检2和自检3模式且调桨系统有EFC信号,但主控制器没有收到来自调桨系统的EFC确认信号。(bBlockMonitoring=0 AND gbEFC_ImpulsAtPowerUp=0 AND giTurbineOperationMode ≠ CON_iSelftest2 AND giTurbineOperationMode ≠ CON_iSelftest3 AND DQ_PitchEFCSignalForController=1 AND gbDI_PitchFeedBackEFC_OK=0)",
- "set_delay": "T#150ms",
- "yp": "0",
- "reset_en": "bBlockMonitoring is true when WTG is in PowerUp, EFC Reset Progess or System Reset Progress. When bBlockMonitoring is true or turbine is in Selftest2 and Selftest3, or main controller gets EFC feedback signal from pitch system.(bBlockMonitoring=1 or gbEFC_ImpulsAtPowerUp=1 or giTurbineOperationMode = CON_iSelftest2 OR giTurbineOperationMode = CON_iSelftest3) OR DQ_PitchEFCSignalForController=1 AND gbDI_PitchFeedBackEFC_OK=1)",
- "reset_cn": "在EFC系统复位过程、风机刚上电中、系统复位过程中时bBlockMonitoring为True。当bBlockMonitoring为true或者风机处于自检2或者自检3模式,或者调桨系统有EFC信号,主控制器也收到来自调桨系统的EFC确认信号。(bBlockMonitoring=1 or gbEFC_ImpulsAtPowerUp=1 or giTurbineOperationMode = CON_iSelftest2 OR giTurbineOperationMode = CON_iSelftest3) OR DQ_PitchEFCSignalForController=1 AND gbDI_PitchFeedBackEFC_OK=1)",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "200"
- },
- "02_02_018": {
- "subsystem": "Pitchsystem",
- "name": "SC_NacelleFuse400VPitch",
- "en": "The fuse for 400V power supply of the pitch system has tripped.",
- "cn": "机舱柜中变桨系统400V电源保护空开跳开",
- "powerup_delay": "T#1s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The fuse for 400V power supply of the pitch system has tripped.(gbDI_NacelleFuse400VPitch=0)",
- "trigger_cn": "变桨系统400伏电源保险丝发生故障。(gbDI_NacelleFuse400VPitch=0)",
- "set_delay": "T#100ms",
- "yp": "100",
- "reset_en": "",
- "reset_cn": "变桨系统400伏电源保险丝故障解除。(gbDI_NacelleFuse400VPitch=1 AND bSpecResCond=1)",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "198"
- },
- "02_02_125": {
- "subsystem": "Pitchsystem",
- "name": "OC_PitchBypassFeatherSwitchPitch_ON",
- "en": "The bypass for feather limit switches in the pitch system is set to on",
- "cn": "变桨系统96度限位开关的旁路信号设定发出",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "PLC output for controlling the bypass for the feather limit switches in the pitch system becomes TRUE.(DQ_PitchBypassFeatherLimitSwitch96=1)",
- "trigger_cn": "PLC控制变桨系统限位开关旁路电路的输出为TRUE。(DQ_PitchBypassFeatherLimitSwitch96=1)",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "PLC output for controlling the bypass for the feather limit switches in the pitch system becomes FALSE.(DQ_PitchBypassFeatherLimitSwitch96=0)",
- "reset_cn": "PLC控制变桨系统限位开关旁路电路的输出为TRUE。(DQ_PitchBypassFeatherLimitSwitch96=0 AND bSpecResCond=1)",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "02_04_014": {
- "subsystem": "RotorLock",
- "name": "SC_RotorBoltLocked",
- "en": "Rotor is locked by bolt",
- "cn": "风机风轮锁被锁定",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The signal for \"rotor bolt locked\" comes.(gbDI_NacelleRotorBoltLocked=0)",
- "trigger_cn": "风机的销子锁死。(gbDI_NacelleRotorBoltLocked=0)",
- "set_delay": "T#1s",
- "yp": "30",
- "reset_en": "The signal for \"rotor bolt locked\" does not come.(gbDI_NacelleRotorBoltLocked=1)",
- "reset_cn": "风机的销子打开。(gbDI_NacelleRotorBoltLocked=1)",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "210-维护",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "210",
- "brake_state_design": "51"
- },
- "02_04_101": {
- "subsystem": "RotorLock",
- "name": "OC_RotorBoltUnlocked",
- "en": "Rotor is unlocked.",
- "cn": "风机风轮锁解锁",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Rotor is unlocked.(gbDI_NacelleRotorBoltLocked=1)",
- "trigger_cn": "风机转子解锁。(gbDI_NacelleRotorBoltLocked=1)",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "Rotor is locked.(gbDI_NacelleRotorBoltLocked=0)",
- "reset_cn": "风机转子锁定。(gbDI_NacelleRotorBoltLocked=0)",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "02_01_001": {
- "subsystem": "SafetySystem",
- "name": "SC_SafetyChain_EmergencySTOP1nacelle",
- "en": "Node 1 of nacelle safetychain is open for emergency stop",
- "cn": "机舱柜柜门急停按钮被拍下触发了紧急停机",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Node 1 of nacelle safetychain is open.(gbDI_SafetyChainNacelleEmergencySTOP=0)",
- "trigger_cn": "机舱安全链的1号节点断开。(gbDI_SafetyChainNacelleEmergencySTOP=0)",
- "set_delay": "T#0s",
- "yp": "100",
- "reset_en": "Node 1 of nacelle safetychain is reclosed.(gbDI_SafetyChainNacelleEmergencySTO=0 AND bSpecResCond=1)",
- "reset_cn": "机舱安全链的1号节点重连接。(gbDI_SafetyChainNacelleEmergencySTO=1 AND bSpecResCond=1)",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "210"
- },
- "02_01_002": {
- "subsystem": "SafetySystem",
- "name": "SC_SafetyChain_EmergencySTOP2nacelle",
- "en": "Node 2 of nacelle safetychain is open for emergency stop",
- "cn": "机舱柜预留急停按钮节点断开触发了紧急停机",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Node 2 of nacelle safetychain is open.(gbDI_SafetyChainNacelleEmergencySTOP2=1)",
- "trigger_cn": "机舱安全链的2号节点断开。(gbDI_SafetyChainNacelleEmergencySTOP2=0)",
- "set_delay": "T#0s",
- "yp": "100",
- "reset_en": "Node 2 of nacelle safetychain is reclosed.(gbDI_SafetyChainNacelleEmergencySTOP2=1 AND bSpecResCond=1)",
- "reset_cn": "机舱安全链的2号节点重连接。(gbDI_SafetyChainNacelleEmergencySTOP2=1 AND bSpecResCond=1)",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "210"
- },
- "02_01_003": {
- "subsystem": "SafetySystem",
- "name": "SC_SafetyChain_VibrationSwitch",
- "en": "Safetychain is open due to tower vibration switch",
- "cn": "PCH的振动过大继电器断开导致安全链断开",
- "powerup_delay": "T#15s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Safetychain is open due to tower vibration switch.(gbdqCANPCH_SSDTest=0 AND bBlockMonitoring1=O AND bBlockMonitoring2=0 AND gbdi_SafetyChainNacelleVibrationSwitch=1)",
- "trigger_cn": "塔架振动过大导致安全链断开。(gbdqCANPCH_SSDTest=0 AND bBlockMonitoring1=O AND bBlockMonitoring2=0 AND gbdi_SafetyChainNacelleVibrationSwitch=1)",
- "set_delay": "T#0s",
- "yp": "100",
- "reset_en": "Safetychain is reclosed.((gbdqCANPCH_SSDTest=1 OR bBlockMonitoring1=1 OR bBlockMonitoring2=1) OR gbdi_SafetyChainNacelleVibrationSwitch=0)AND bSpecResCond=1",
- "reset_cn": "安全链重连。((gbdqCANPCH_SSDTest=1 OR bBlockMonitoring1=1 OR bBlockMonitoring2=1) OR gbdi_SafetyChainNacelleVibrationSwitch=0)AND bSpecResCond=1",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "200"
- },
- "02_01_004": {
- "subsystem": "SafetySystem",
- "name": "SC_SafetyChain_OverspeedRelayTriggered",
- "en": "Safetychain is open due to overspeed relay triggered",
- "cn": "过速继电器断开导致安全链断开",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Overspeed relay triggered.(gbDI_SafetyChainNacelleRelayOverspeed=0)",
- "trigger_cn": "过速继电器被触发。(gbDI_SafetyChainNacelleRelayOverspeed=0)",
- "set_delay": "T#0s",
- "yp": "100",
- "reset_en": "Safetychain is reclosed._x000D_ gbDI_SafetyChainNacelleRelayOverspeed=1",
- "reset_cn": "安全链重连接。gbDI_SafetyChainNacelleRelayOverspeed=1",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "200"
- },
- "02_01_005": {
- "subsystem": "SafetySystem",
- "name": "SC_SafetyChain_SSDSwitch",
- "en": "Safetychain is open due to SSD switch open",
- "cn": "PCH的SSD开关断开导致安全链断开",
- "powerup_delay": "T#15s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Safetychain is open due to SSD switch open._x000D_ gbdi_SafetyChainNacelleSSDSwitch=1 AND gbdqCANPCH_SSDTest=0 AND bBlockMonitoring1=0 AND bBlockMonitoring2=0 _x000D_ bBlockMonitoring1 will last for 15 seconds when gbdqCANPCH_SSDTest drop from 1 to 0._x000D_ bBlockMonitoring2 will last for 15 seconds when gbMAIN_ResetStatusCodes rises from 0 to 1.",
- "trigger_cn": "SSD开关断开导致安全链断开。(gbdi_SafetyChainNacelleSSDSwitch=1 AND gbdqCANPCH_SSDTest=0 AND bBlockMonitoring1=0 AND bBlockMonitoring2=0)_x000D_ gbdqCANPCH_SSDTest(主控命令PCH进行SSD自检)从True变为false,触发15秒的bBlockMonitoring1为True_x000D_ gbMAIN_ResetStatusCodes(复位状态字命令)从False变为True,触发15秒的bBlockMonitoring2为True_x000D_",
- "set_delay": "T#0s",
- "yp": "100",
- "reset_en": "Safetychain is closed. (gbdi_SafetyChainNacelleSSDSwitch=0 OR gbdqCANPCH_SSDTest=1 OR bBlockMonitoring1=1 OR bBlockMonitoring2=1) bBlockMonitoring1 will last for 15 seconds when gbdqCANPCH_SSDTest drop from 1 to 0._x000D_ bBlockMonitoring2 will last for 15 seconds when gbMAIN_ResetStatusCodes rises from 0 to 1.",
- "reset_cn": "SSD开关闭合导致安全链闭合。(gbdi_SafetyChainNacelleSSDSwitch=0 OR gbdqCANPCH_SSDTest=1 OR bBlockMonitoring1=1 OR bBlockMonitoring2=1)_x000D_ gbdqCANPCH_SSDTest(主控命令PCH进行SSD自检)从True变为false,触发15秒的bBlockMonitoring1为True_x000D_ gbMAIN_ResetStatusCodes(复位状态字命令)从False变为True,触发15秒的bBlockMonitoring2为True",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "200"
- },
- "02_01_006": {
- "subsystem": "SafetySystem",
- "name": "SC_SafetyChain_SSDMax",
- "en": "SSD Triggered",
- "cn": "PCH测得的SSD震动值高于设定值",
- "powerup_delay": "T#30s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "When the signal for SSD switch is more than PAR_rSSDMax.(grSSDValue_PCH_100ms > PAR_rSSDMax AND gbdqCANPCH_SSDTest=0 AND bBlockMonitoring1=0AND (giTurbineOperationMode <> CON_iSelfTest4)_x000D_ bBlockMonitoring1 will last for 15 seconds when gbdqCANPCH_SSDTest drop from 1 to 0.",
- "trigger_cn": "以下4点同时满足:1.当SSD 100ms平均值大于允许的最大值(由参数给出)2.主控未发出PCH进行SSD自检的命令3.不满足bBlockMonitor1条件4.风机不处于自检4(grSSDValue_PCH_100ms > PAR_rSSDMax AND gbdqCANPCH_SSDTest=0 AND bBlockMonitoring1=0AND (giTurbineOperationMode <> CON_iSelfTest4)gbdqCANPCH_SSDTest_x000D_ (主控命令PCH进行SSD自检)从True变为false,触发15秒的bBlockMonitoring1为True",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "When the signal for SSD switch is less than PAR_rSSDMax.(grSSDValue_PCH_100ms <= PAR_rSSDMax OR gbdqCANPCH_SSDTest=1 OR bBlockMonitoring1=1)_x000D_ bBlockMonitoring1 will last for 15 seconds when gbdqCANPCH_SSDTest drop from 1 to 0.",
- "reset_cn": "以下4点满足一点即可:1.当SSD 100ms平均值小于等于允许的最大值(由参数给出)2.主控发出PCH进行SSD自检的命令3.满足bBlockMonitor1条件4.风机处于自检4。(grSSDValue_PCH_100ms <= PAR_rSSDMax OR gbdqCANPCH_SSDTest=1 OR bBlockMonitoring1=1)OR(giTurbineOperationMode = CON_iSelfTest4)",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "100"
- },
- "02_01_007": {
- "subsystem": "SafetySystem",
- "name": "SC_NacelleNoFeedBack24VOutHumanOrMachine",
- "en": "Nacelle human or machine safetychain does NOT get 24 V feedback",
- "cn": "机舱人员安全链或机器安全链没有反馈信号",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Nacelle human or machine safetychain does NOT get 24 V feedback.(gbDI_SafetyChainHumanNacelleFeedback24VOutput=0 OR gbDI_SafetyChainMachineNacelleFeedback24VOutput=0)",
- "trigger_cn": "机舱人员安全链或机器安全链未收到24伏反馈信号。(gbDI_SafetyChainHumanNacelleFeedback24VOutput=0 OR gbDI_SafetyChainMachineNacelleFeedback24VOutput=0)",
- "set_delay": "T#120ms",
- "yp": "100",
- "reset_en": "Nacelle human or machine safetychain gets 24 V feedback. (gbDI_SafetyChainHumanNacelleFeedback24VOutput=1 AND gbDI_SafetyChainMachineNacelleFeedback24VOutput=1)",
- "reset_cn": "机舱人员安全链和机器安全链均能收到24伏反馈信号。(gbDI_SafetyChainHumanNacelleFeedback24VOutput=1 AND gbDI_SafetyChainMachineNacelleFeedback24VOutput=1 )",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "100"
- },
- "02_01_101": {
- "subsystem": "SafetySystem",
- "name": "OC_SafetyChainResetFromNacelle",
- "en": "Safetychain is reset from nacelle cabinet switch",
- "cn": "机舱柜安全链复位按钮被按下对安全链进行复位",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Safetychain is reset from nacelle cabinet switch.(gbDI_NacelleSafetyChain_RESET=1)",
- "trigger_cn": "机舱控制柜开关被按下。(gbDI_NacelleSafetyChain_RESET=1)",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "Safetychain finishs resetting.(gbDI_NacelleSafetyChain_RESET=0 AND bSpecResCond=1)",
- "reset_cn": "机舱控制柜开关复位。(gbDI_NacelleSafetyChain_RESET=0 AND bSpecResCond=1)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "185-复位操作",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "185",
- "brake_state_design": "0"
- },
- "02_02_015": {
- "subsystem": "SafetySystem",
- "name": "SC_NacelleOL24VOutputsSafetyChain",
- "en": "24V power supply for the safety chain devices is not available",
- "cn": "机舱人工安全链或机舱机器安全链的24V电源开路",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "24V power supply for the safety Chain devices / components not available.①gbDI_SafetyChainHumanNacelleFeedback24VOutput=1 AND gbDI_SafetyChainHumanNacelleOL24VOutputs=0;②gbDI_SafetyChainMachineNacelleFeedback24VOutput=1 AND gbDI_SafetyChainMachineNacelleOL24VOutputs=0",
- "trigger_cn": "①机舱人员安全链收到24伏反馈信号:机舱人员安全链的24V电源不通gbDI_SafetyChainHumanNacelleFeedback24VOutput=1 AND gbDI_SafetyChainHumanNacelleOL24VOutputs=0; ②机舱机器安全链收到24伏反馈信号:机舱机器安全链的24V电源不通gbDI_SafetyChainMachineNacelleFeedback24VOutput=1 AND gbDI_SafetyChainMachineNacelleOL24VOutputs=0",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "24V power supply for the safety Chain devices / components available.①gbDI_SafetyChainHumanNacelleFeedback24VOutput=1 AND gbDI_SafetyChainHumanNacelleOL24VOutputs=1;②gbDI_SafetyChainMachineNacelleFeedback24VOutput=1 AND gbDI_SafetyChainMachineNacelleOL24VOutputs=1.",
- "reset_cn": "①机舱人员安全链收到24伏反馈信号:机舱人员安全链的24V电源连通。gbDI_SafetyChainHumanNacelleFeedback24VOutput=1 AND gbDI_SafetyChainHumanNacelleOL24VOutputs=1; ②机舱机器安全链收到24伏反馈信号:机舱机器安全链的24V电源连通。gbDI_SafetyChainMachineNacelleFeedback24VOutput=1 AND gbDI_SafetyChainMachineNacelleOL24VOutputs=1.",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "100"
- },
- "02_04_002": {
- "subsystem": "SafetySystem",
- "name": "SC_RotorOverSpeedLevel2",
- "en": "Rotor speed exceeds the level2 overspeed limit",
- "cn": "风机低速端转速高于2级超速门限值",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The current value for rotor speed exceeds the limit given by parameter.(grRotorSpeedForProcess > grRotorOverSpeedLevel2",
- "trigger_cn": "风机转速高于2级超速门限值 grRotorSpeedForProcess > grRotorOverSpeedLevel2",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "The current value for rotor speed falls below the limit given by parameter.(grRotorSpeedForProcess <= rRotorOverSpeedLevel2",
- "reset_cn": "风机转速不高于2级超速门限值",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "200"
- },
- "02_04_004": {
- "subsystem": "SafetySystem",
- "name": "SC_GeneratorOverSpeedLevel2",
- "en": "Generator speed exceeds the level2 overspeed limit",
- "cn": "发电机转速高于2级超速门限值",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Generator speed exceeds the level2 overspeed limit.(grGenSpeedForProcess > PAR_rGenOverSpeedLevel2)",
- "trigger_cn": "发电机转速大于发电机2级超速门限值。(grGenSpeedForProcess > PAR_rGenOverSpeedLevel2)",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "Generator speed falls below the level2 overspeed limitgrGenSpeedForProcess <= grGenOverSpeedLevel2",
- "reset_cn": "发电机转速不大于发电机2级超速门限值",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "200"
- },
- "03_01_001": {
- "subsystem": "SafetySystem",
- "name": "SC_SafetyChainEmergencySTOP_TowerBase",
- "en": "Emergency stop button on tower cabinet door is pressed",
- "cn": "塔底柜急停按钮被拍下触发了紧急停机",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "When the signal for Emergency STOP on the hardware input becomes FALSE.(gbDI_TowerSafetyChainTowerEmergencySTOP=0)",
- "trigger_cn": "当紧急停止信号在塔底控制柜硬件输入上变为FALSE。(gbDI_TowerSafetyChainTowerEmergencySTOP=0)",
- "set_delay": "T#0s",
- "yp": "100",
- "reset_en": "When the signal for Emergency STOP on the hardware input becomes TRUE.(gbDI_TowerSafetyChainTowerEmergencySTOP=1)",
- "reset_cn": "当紧急停止信号在塔底控制柜硬件输入上变为TRUE。(gbDI_TowerSafetyChainTowerEmergencySTOP=1)",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "210"
- },
- "03_01_003": {
- "subsystem": "SafetySystem",
- "name": "SC_TowerNoFeedBack24VOut_Human",
- "en": "Human safety chain is open, and no 24V feedback is received in tower",
- "cn": "塔底人工安全链没有反馈信号",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Human safety chain is open, and no 24V feedback is received in tower.(gbDI_TowerFeedback24VOutputSafetyChainHuman=1)",
- "trigger_cn": "人体安全链断开,塔底没有收到24V反馈信号。(gbDI_TowerFeedback24VOutputSafetyChainHuman=1)",
- "set_delay": "T#120ms",
- "yp": "100",
- "reset_en": "Human safety chain is open, and a 4V feedback is received in tower.(gbDI_TowerFeedback24VOutputSafetyChainHuman=0)",
- "reset_cn": "人体安全链断开,塔底能够收到24V反馈信号。(gbDI_TowerFeedback24VOutputSafetyChainHuman=0)",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "100"
- },
- "03_01_004": {
- "subsystem": "SafetySystem",
- "name": "SC_SafetyChainOpenedByConverter",
- "en": "Converter trips safety chain",
- "cn": "变频柜上的急停按钮被拍下触发了紧急停机",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The corresponding signal from the converter (Converter trips safety chain) becomes TRUE.(diConverter_EmergencySTOP=1)",
- "trigger_cn": "从变频器过来的相应信号(变频器触发安全链断开)变为TRUE。(diConverter_EmergencySTOP=1)",
- "set_delay": "T#0s",
- "yp": "100",
- "reset_en": "The corresponding signal from the converter (Converter trips safety chain) becomes FALSE.(diConverter_EmergencySTOP=0)",
- "reset_cn": "从变频器过来的相应信号(变频器触发安全链断开)变为FALSE。(diConverter_EmergencySTOP=0)",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "100"
- },
- "03_01_005": {
- "subsystem": "SafetySystem",
- "name": "SC_TowerNoFeedBack24VOut_Machine",
- "en": "Machine safety chain is open, and no 24V feedback is received in tower",
- "cn": "塔底机器安全链没有反馈信号",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Machine safety chain is open, and no 24V feedback is received in tower.(gbDI_TowerFeedback24VOutputSafetyChainMachine=1)",
- "trigger_cn": "机器安全链断开,塔底没有收到24V反馈信号。(gbDI_TowerFeedback24VOutputSafetyChainMachine=1)",
- "set_delay": "T#120ms",
- "yp": "100",
- "reset_en": "Machine safety chain is reclosed, and a 24V feedback is received in tower.(gbDI_TowerFeedback24VOutputSafetyChainMachine=0)",
- "reset_cn": "机器安全链闭合,塔底有收到24V反馈信号。(gbDI_TowerFeedback24VOutputSafetyChainMachine=0)",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "100"
- },
- "03_01_006": {
- "subsystem": "SafetySystem",
- "name": "SC_SafetyChainResetFromTowerBase",
- "en": "Safetychain resetting is commanded from tower base",
- "cn": "塔底发出复位安全链命令",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "When the corresponding PLC input(safetychain resetting) becomes TRUE.(gbDI_TowerSafetyChain_RESET=1)",
- "trigger_cn": "相应的输入为TRUE(塔底发出安全链复位命令)。(gbDI_TowerSafetyChain_RESET=1)",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "When the corresponding PLC input(safetychain resetting) becomes FALSE.(gbDI_TowerSafetyChain_RESET=0)",
- "reset_cn": "相应的输入为FALSE(塔底发出安全链复位命令)。(gbDI_TowerSafetyChain_RESET=0)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "185-复位操作",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "185",
- "brake_state_design": "0"
- },
- "03_01_007": {
- "subsystem": "SafetySystem",
- "name": "SC_SafetyChainResetRemoteOrTargetVISU",
- "en": "Safetychain resetting is commanded remotely",
- "cn": "远程发出复位安全链命令",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "A reset of the safety chain is triggered by an accepted remote command(No Nacelle, No Tower).(gbMAIN_ResetSafetyChain=1 AND gbDI_NacelleSafetyChain_RESET=0 AND gbDI_TowerSafetyChain_RESET=0)",
- "trigger_cn": "安全链复位由一个远程命令触发(不是机舱也不是塔底发出)。(gbMAIN_ResetSafetyChain=1 AND gbDI_NacelleSafetyChain_RESET=0 AND gbDI_TowerSafetyChain_RESET=0)",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "No reset, or get reset signal of status code coming from Nacelle or Tower.(gbMAIN_ResetSafetyChain=0 OR gbDI_NacelleSafetyChain_RESET=1 OR gbDI_TowerSafetyChain_RESET=1)",
- "reset_cn": "没有安全链复位信号或安全链复位信号由一个机舱命令或塔底命令触发。(gbMAIN_ResetSafetyChain=0 OR gbDI_NacelleSafetyChain_RESET=1 OR gbDI_TowerSafetyChain_RESET=1)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "185-复位操作",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "185",
- "brake_state_design": "0"
- },
- "03_01_009": {
- "subsystem": "SafetySystem",
- "name": "SC_ResetSatetyChainStart",
- "en": "Reset the System",
- "cn": "系统复位",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "ResetSafetyChain is start",
- "trigger_cn": "复位安全链开始",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "185-复位操作",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "185",
- "brake_state_design": "0"
- },
- "03_01_010": {
- "subsystem": "SafetySystem",
- "name": "SC_SafetyChainOpenedByConverterOverPower",
- "en": "Safety chain is opened by converter over power",
- "cn": "变频器过功率触发安全链断开",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "gbDI_ConverterOverPowerTriggerSaftychainOpen is TRUE(Only for Gen1 Gen2)",
- "trigger_cn": "gbDI_ConverterOverPowerTriggerSaftychainOpen为TRUE(只有Gen1 Gen2会触发)",
- "set_delay": "T#0s",
- "yp": "100",
- "reset_en": "gbDI_ConverterOverPowerTriggerSaftychainOpen is FALSE",
- "reset_cn": "gbDI_ConverterOverPowerTriggerSaftychainOpen为FALSE",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "100"
- },
- "03_02_013": {
- "subsystem": "SafetySystem",
- "name": "SC_TowerFuse24V_SafetyChain",
- "en": "The fuse for tower 24V safetychain power supply has tripped",
- "cn": "塔底柜安全链回路24V电源保护空开跳开",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The fuse for 24V power supply for the components of the Safety Chain has tripped(corresponding hardware input becomes FALSE).(gbDI_TowerFuse24V_SafetyChain=0)",
- "trigger_cn": "塔底24V安全链电源保险丝故障(相应的硬件输入为FALSE)。(gbDI_TowerFuse24V_SafetyChain=0)",
- "set_delay": "T#100ms",
- "yp": "100",
- "reset_en": "The fuse for 24V power supply for the components of the Safety Chain is OK(corresponding hardware input becomes TRUE).(gbDI_TowerFuse24V_SafetyChain=1)",
- "reset_cn": "塔底24V安全链电源保险丝正常(相应的硬件输入为TRUE)。(gbDI_TowerFuse24V_SafetyChain=0)",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "200"
- },
- "03_02_015": {
- "subsystem": "SafetySystem",
- "name": "SC_TowerOL24VOutputsSafetyChain",
- "en": "Tower 24V power supply for safety chain is not available",
- "cn": "塔底柜安全链24V电源开路",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Tower 24V power supply for safety chain is not available(corresponding hardware input becomes FALSE).(gbDI_TowerOL_OutputSafetyChainAll=0)",
- "trigger_cn": "塔底24V安全链电源开路(相应的硬件输入为FALSE)。(gbDI_TowerOL_OutputSafetyChainAll=0)",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "Tower 24V power supply for safety chain becomes available(corresponding hardware input becomes TRUE).(gbDI_TowerOL_OutputSafetyChainAll=1)",
- "reset_cn": "塔底24V安全链电源连通(相应的硬件输入为TRUE)。(gbDI_TowerOL_OutputSafetyChainAll=0)",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "100"
- },
- "03_02_101": {
- "subsystem": "SafetySystem",
- "name": "OC_SafetyChainSingleShotRelayON",
- "en": "Tower safetychain single shot relay is on",
- "cn": "塔底安全链单稳态继电器闭合",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Tower safetychain single shot relay is on.(gbDI_TowerSingleShotRelayON=1)",
- "trigger_cn": "塔底安全链单稳态继电器闭合(相应的数字输入)。(gbDI_TowerSingleShotRelayON=1)",
- "set_delay": "T#0s",
- "yp": "100",
- "reset_en": "Tower safetychain single shot relay is off.(gbDI_TowerSingleShotRelayON=0)",
- "reset_cn": "塔底安全链单稳态继电器打开(相应的数字输入)。(gbDI_TowerSingleShotRelayON=0)",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "100"
- },
- "03_08_104": {
- "subsystem": "SafetySystem",
- "name": "OC_RESET_SAFETY_CHAIN",
- "en": "Safetychain resetting is requested",
- "cn": "风机接收到复位安全链指令",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "A reset of the Safety Chain was activated by a user command.(gbMAIN_ResetSafetyChain=1)",
- "trigger_cn": "要求安全链复位。(gbMAIN_ResetSafetyChain=1)",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "No safetychain resetting is requested.(gbMAIN_ResetSafetyChain=0)",
- "reset_cn": "没有要求安全链复位。(gbMAIN_ResetSafetyChain=0)",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "03_01_008": {
- "subsystem": "UserAccess",
- "name": "SC_ResetStatusCodesStart",
- "en": "ResetStatusCodes is start",
- "cn": "复位状态字",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "ResetStatusCodes is start",
- "trigger_cn": "复位状态字开始",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "185-复位操作",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "185",
- "brake_state_design": "0"
- },
- "03_08_003": {
- "subsystem": "UserAccess",
- "name": "SC_ForceMajeure",
- "en": "force majeure",
- "cn": "不可抗力停机",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "240-不可抗力",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "240",
- "brake_state_design": "0"
- },
- "03_08_004": {
- "subsystem": "UserAccess",
- "name": "SC_STOP_RemoteOrServiceNotebook",
- "en": "Turbine is requested to stop remotely",
- "cn": "远程发出风机停机指令",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "A turbine STOP is activated by an accepted Remote Command(not from Nacelle and Tower).(gbMAIN_STOP=1 AND gbDI_NacelleWECStop=0 AND gbDI_TowerWECStop=0)",
- "trigger_cn": "远程命令要求风机停机(不来自机舱和塔底)。(gbMAIN_STOP=1 AND gbDI_NacelleWECStop=0 AND gbDI_TowerWECStop=0)",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "A turbine STOP is activated by a Nacelle Command or Tower Command(not from Remote Command).(gbMAIN_STOP=0 OR gbDI_NacelleWECStop=1 OR gbDI_TowerWECStop=1)",
- "reset_cn": "远程命令没有要求风机停机或来自机舱或塔底的命令要求停机。(gbMAIN_STOP=0 OR gbDI_NacelleWECStop=1 OR gbDI_TowerWECStop=1)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "200-用户停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "200",
- "brake_state_design": "51"
- },
- "03_08_006": {
- "subsystem": "UserAccess",
- "name": "SC_OperatorStop",
- "en": "Stop command from operator",
- "cn": "操作员停机",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "190-操作员停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "190",
- "brake_state_design": "51"
- },
- "03_08_103": {
- "subsystem": "UserAccess",
- "name": "OC_ManualTriggerTraceLog",
- "en": "Remote command triggers error trace logging",
- "cn": "远程命令手动触发Tracelog生成",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Remote command triggers error trace logging.(RemComOK_TriggerTraceLog=1)",
- "trigger_cn": "远程命令触发故障日志记录。(RemComOK_TriggerTraceLog=1)",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "No remote command triggers error trace logging.(RemComOK_TriggerTraceLog=0)",
- "reset_cn": "没有远程命令触发故障日志记录。(RemComOK_TriggerTraceLog=0)",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "03_04_300": {
- "subsystem": "WindFarm",
- "name": "SC_STOP_ForGridLimitation",
- "en": "Stop for limitation of grid",
- "cn": "电网容量原因停机",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The turbine receives STOP_ForGridLimitation.(gbSTOP_ForGridLimitation=1)",
- "trigger_cn": "风机收到STOP_ForGridLimitation信号。(gbSTOP_ForGridLimitation=1)",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "The turbine does not receive STOP_ForGridLimitation.(gbSTOP_ForGridLimitation=0)",
- "reset_cn": "风机没有收到STOP_ForGridLimitation信号。(gbSTOP_ForGridLimitation=0)",
- "reset_mode": "A",
- "type": "I",
- "alarm": "True",
- "level": "180-电网故障",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "180",
- "brake_state_design": "51"
- },
- "03_06_027": {
- "subsystem": "WindFarm",
- "name": "SC_NoHeartBeat_WindparkCOM",
- "en": "Communication with wind park has fault",
- "cn": "风场通讯故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#50ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "02_02_007": {
- "subsystem": "YawSystem",
- "name": "SC_NacelleFuseHeaterYawMotors",
- "en": "The fuse for power supply of the yaw motor heater is tripped",
- "cn": "偏航电机加热器保护空开跳开",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The fuse for power supply of the yaw motor heater is connected.(gbDI_NacelleFuseHeaterYawMotors=0)",
- "trigger_cn": "偏航马达加热器保险丝发生故障。(gbDI_NacelleFuseHeaterYawMotors=0)",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "The fuse for power supply of the yaw motor heater is tripped.(gbDI_NacelleFuseHeaterYawMotors=1 AND bSpecResCond=1)",
- "reset_cn": "偏航马达加热器保险丝故障清除。(gbDI_NacelleFuseHeaterYawMotors=1 AND bSpecResCond=1)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_02_023": {
- "subsystem": "YawSystem",
- "name": "SC_NacelleMotorProtectionYawMotorsGroup",
- "en": "The motor protection system for the group of yaw motors has tripped.",
- "cn": "机舱柜中偏航电机保护空开跳开",
- "powerup_delay": "T#0s",
- "disable_level": "99",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The motor protection for the group of yaw motors has tripped.(gbDI_NacelleMotorProtYawMotorsGroup=0)",
- "trigger_cn": "偏航电机的电机保护发生故障。(gbDI_NacelleMotorProtYawMotorsGroup=0)",
- "set_delay": "T#1s",
- "yp": "100",
- "reset_en": "The motor protection for the group of yaw motors is OK.(gbDI_NacelleMotorProtYawMotorsGroup=1)",
- "reset_cn": "偏航电机的电机故障解除。(gbDI_NacelleMotorProtYawMotorsGroup=1)",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "50-偏航警告",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "50",
- "brake_state_design": "0"
- },
- "02_02_046": {
- "subsystem": "YawSystem",
- "name": "SC_MotorProtection_YawMotor1",
- "en": "The motor protection for yaw motor 1 has tripped.",
- "cn": "偏航系统1号电机热保护继电器触发",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "if PAR_YawMotorProtectionReverse is True, gbDI_NacelleMotorProtYawMotor1=1 represents the motor protection for yaw motor 1 has tripped._x000D_ if PAR_YawMotorProtectionReverse is False, gbDI_NacelleMotorProtYawMotor1=0 represents the motor protection for yaw motor 1 has tripped.",
- "trigger_cn": "当PAR_YawMotorProtectionReverse为True时,gbDI_NacelleMotorProtYawMotor1=1表示偏航系统1号电机保护系统发生故障。当PAR_YawMotorProtectionReverse为False时,gbDI_NacelleMotorProtYawMotor1=0表示偏航系统1号电机保护系统发生故障。",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "if PAR_YawMotorProtectionReverse is True, gbDI_NacelleMotorProtYawMotor1=0 represents the motor protection for yaw motor 1 is OK._x000D_ if PAR_YawMotorProtectionReverse is False, gbDI_NacelleMotorProtYawMotor1=1 represents the motor protection for yaw motor 1 is OK.",
- "reset_cn": "当PAR_YawMotorProtectionReverse为True时,gbDI_NacelleMotorProtYawMotor1=0表示偏航系统1号电机保护系统故障清除。当PAR_YawMotorProtectionReverse为False时,gbDI_NacelleMotorProtYawMotor1=1表示偏航系统1号电机保护系统故障清除。",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_02_047": {
- "subsystem": "YawSystem",
- "name": "SC_MotorProtection_YawMotor2",
- "en": "The motor protection for yaw motor 2 has tripped",
- "cn": "偏航系统2号电机热保护继电器触发",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The motor protection for yaw motor 2 has tripped.(gbDI_NacelleMotorProtYawMotor2=0)",
- "trigger_cn": "偏航系统2号电机保护的硬件输入是FALSE。(gbDI_NacelleMotorProtYawMotor2=0)",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "The motor protection for yaw motor 2 is OK.(gbDI_NacelleMotorProtYawMotor2=1)",
- "reset_cn": "偏航系统2号电机保护系统故障清除。(gbDI_NacelleMotorProtYawMotor2=1)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_02_048": {
- "subsystem": "YawSystem",
- "name": "SC_MotorProtection_YawMotor3",
- "en": "The motor protection for yaw motor 3 has tripped",
- "cn": "偏航系统3号电机热保护继电器触发",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The motor protection for yaw motor 3 has tripped.(gbDI_NacelleMotorProtYawMotor3=0)",
- "trigger_cn": "偏航系统3号电机保护系统发生故障。(gbDI_NacelleMotorProtYawMotor3=0)",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "The motor protection for yaw motor 3 is OK.(gbDI_NacelleMotorProtYawMotor3=1)",
- "reset_cn": "偏航系统3号电机保护系统故障清除。(gbDI_NacelleMotorProtYawMotor3=1)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_02_049": {
- "subsystem": "YawSystem",
- "name": "SC_MotorProtection_YawMotor4",
- "en": "The motor protection for yaw motor 4 has tripped",
- "cn": "偏航系统4号电机热保护继电器触发",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The motor protection for yaw motor 4 has tripped.(gbDI_NacelleMotorProtYawMotor4=0)",
- "trigger_cn": "偏航系统4号电机保护系统发生故障。(gbDI_NacelleMotorProtYawMotor4=0)",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "The motor protection for yaw motor 4 is OK.(gbDI_NacelleMotorProtYawMotor4=1)",
- "reset_cn": "偏航系统4号电机保护系统故障清除。(gbDI_NacelleMotorProtYawMotor4=1)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_02_078": {
- "subsystem": "YawSystem",
- "name": "SC_NacelleFuseElectricalMotorBrakeYaw",
- "en": "The fuse for power supply for the electrical yaw motor brake has tripped.",
- "cn": "机舱柜中偏航电机抱闸的保护空开跳开",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The fuse for power supply for the electrical yaw motor brake has tripped.(gbDI_NacelleFuseElectricalMotorbrakeYaw=0)",
- "trigger_cn": "偏航系统电机制动电源保险丝发生故障。(gbDI_NacelleFuseElectricalMotorbrakeYaw=0)",
- "set_delay": "T#1s",
- "yp": "100",
- "reset_en": "The fuse for power supply for the electrical yaw motor brake is OK.(gbDI_NacelleFuseElectricalMotorbrakeYaw=1)",
- "reset_cn": "偏航系统电机制动电源保险丝故障解除。(gbDI_NacelleFuseElectricalMotorbrakeYaw=1)",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "50-偏航警告",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "50",
- "brake_state_design": "0"
- },
- "02_02_088": {
- "subsystem": "YawSystem",
- "name": "SC_FaultAI_YawPosition",
- "en": "Yaw position sensor has fault",
- "cn": "偏航系统位置传感器故障",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Bit 6 from the Yaw position input becomes TRUE.(giStateAIYAW_Position.6=1)",
- "trigger_cn": "偏航系统位置传感器输入的状态字节第6位是TRUE。(giStateAIYAW_Position.6=1)",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "Bit 6 from the Yaw position input becomes FALSE.(giStateAIYAW_Position.6=0)",
- "reset_cn": "偏航系统位置传感器输入的状态字节第6位是FALSE。(giStateAIYAW_Position.6=0 AND bSpecResCond=1)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_02_110": {
- "subsystem": "YawSystem",
- "name": "OC_HeaterYawMotors_ON",
- "en": "Heater of yaw motors is set to on",
- "cn": "偏航系统电机加热器设定打开",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "PLC output for controlling the yaw motors heater becomes TRUE.(DQ_NacelleYawHeaterMotors=1)",
- "trigger_cn": "PLC控制偏航系统电机加热器的输出为TRUE。(DQ_NacelleYawHeaterMotors=1)",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "PLC output for controlling the yaw motors heater becomes FALSE.(DQ_NacelleYawHeaterMotors=0)",
- "reset_cn": "PLC控制偏航系统电机加热器的输出为FALSE。(DQ_NacelleYawHeaterMotors=0)",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "02_02_114": {
- "subsystem": "YawSystem",
- "name": "OC_YawCW_ON",
- "en": "Yaw is set to rotate clockwise",
- "cn": "偏航系统设定顺时针偏航",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "PLC output for controlling the yaw motors in CW direction becomes TRUE.(DQ_NacelleStartYawCW=1)",
- "trigger_cn": "PLC控制偏航系统顺时针转动的输出为TRUE。(DQ_NacelleStartYawCW=1)",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "PLC output for controlling the yaw motors in CW direction becomes FALSE.(DQ_NacelleStartYawCW=0)",
- "reset_cn": "PLC控制偏航系统顺时针转动的输出为FALSE。(DQ_NacelleStartYawCW=0)",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "02_02_115": {
- "subsystem": "YawSystem",
- "name": "OC_YawCCW_ON",
- "en": "Yaw is set to rotate counterclockwise",
- "cn": "偏航系统设定逆时针偏航",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "PLC output for controlling the yaw motors in CCW direction becomes TRUE.(DQ_NacelleStartYawCCW=1)",
- "trigger_cn": "PLC控制偏航系统逆时针转动的输出为TRUE。(DQ_NacelleStartYawCCW=1)",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "PLC output for controlling the yaw motors in CCW direction becomes FALSE.(DQ_NacelleStartYawCCW=0)",
- "reset_cn": "PLC控制偏航系统逆时针转动的输出为FALSE。(DQ_NacelleStartYawCCW=0)",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "02_02_116": {
- "subsystem": "YawSystem",
- "name": "OC_OpenElectricalYawBrake_ON",
- "en": "The electrical brake of yaw motors is set to on",
- "cn": "偏航系统电机抱闸设定打开",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "PLC output for controlling the electrical brake of the yaw motors becomes TRUE.(DQ_NacelleOpenElectricalYawBrake=1)",
- "trigger_cn": "PLC控制偏航系统电机刹车的输出为TRUE。(DQ_NacelleOpenElectricalYawBrake=1)",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "PLC output for controlling the electrical brake of the yaw motors becomes FALSE.(DQ_NacelleOpenElectricalYawBrake=0)",
- "reset_cn": "PLC控制偏航系统电机刹车的输出为FALSE。(DQ_NacelleOpenElectricalYawBrake=0)",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "02_10_001": {
- "subsystem": "YawSystem",
- "name": "SC_CableTwistMax_CW",
- "en": "Cable twist exceeds level2 maximum limit clock wisely",
- "cn": "偏航系统顺时针2级限位开关被撞开",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Cable twist exceeds level2 maximum limit clock wisely(_x000D_ the corresponding digital input gives no OK signal).(gbDI_NacelleCableTwist_CW_MAX2=0 AND gbLimitSwitchCableTwistCCWBridge=0 AND gbLimitSwitchCableTwistCWBridge=0)",
- "trigger_cn": "电缆顺时针扭转高于2级上限值(相应的数字输入是FALSE)。(gbDI_NacelleCableTwist_CW_MAX2=0 AND gbLimitSwitchCableTwistCCWBridge=0 AND gbLimitSwitchCableTwistCWBridge=0)",
- "set_delay": "T#500ms",
- "yp": "100",
- "reset_en": "Cable twist falls below level2 maximum limit clock wisely(_x000D_ the corresponding digital input gives OK signal).(gbDI_NacelleCableTwist_CW_MAX2=1 OR gbLimitSwitchCableTwistCCWBridge=1 OR gbLimitSwitchCableTwistCWBridge=1)",
- "reset_cn": "电缆顺时针扭转回归2级上限值内(相应的数字输入是TRUE)。(gbDI_NacelleCableTwist_CW_MAX2=1 OR gbLimitSwitchCableTwistCCWBridge=1 OR gbLimitSwitchCableTwistCWBridge=1)",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "50-偏航警告",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "50",
- "brake_state_design": "0"
- },
- "02_10_002": {
- "subsystem": "YawSystem",
- "name": "SC_CableTwistMax_CCW",
- "en": "Cable twist exceeds level2 maximum limit counterclockwisely",
- "cn": "偏航系统逆时针2级限位开关被撞开",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Cable twist exceeds level2 maximum limit clock wisely(_x000D_ the corresponding digital input gives no OK signal).(gbDI_NacelleCableTwist_CCW_MAX2=0 AND gbLimitSwitchCableTwistCCWBridge=0 AND gbLimitSwitchCableTwistCWBridge=0)",
- "trigger_cn": "电缆逆时针扭转高于2级上限值(相应的数字输入是FALSE)。(gbDI_NacelleCableTwist_CCW_MAX2=0 AND gbLimitSwitchCableTwistCCWBridge=0 AND gbLimitSwitchCableTwistCWBridge=0)",
- "set_delay": "T#500ms",
- "yp": "100",
- "reset_en": "Cable twist falls below level2 maximum limit clock wisely(_x000D_ the corresponding digital input gives OK signal).(gbDI_NacelleCableTwist_CCW_MAX2=1 OR gbLimitSwitchCableTwistCCWBridge=1 OR gbLimitSwitchCableTwistCWBridge=1)",
- "reset_cn": "电缆逆时针扭转回归2级上限值内(相应的数字输入是TRUE)。(gbDI_NacelleCableTwist_CCW_MAX2=1 OR gbLimitSwitchCableTwistCCWBridge=1 OR gbLimitSwitchCableTwistCWBridge=1)",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "50-偏航警告",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "50",
- "brake_state_design": "0"
- },
- "02_10_008": {
- "subsystem": "YawSystem",
- "name": "SC_YawSpeedTooSlow",
- "en": "Yaw speed is too slow",
- "cn": "偏航系统速度过慢",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "3",
- "repeat_period": "T#1h",
- "trigger_en": "The true yaw angle will be less than the expected yaw angle.(ABS(grNacellePositionTotal - grNacellePositionTotal)< rExpectedYawAngle)",
- "trigger_cn": "真实的偏航角度小于期望的偏航角度。(ABS(grNacellePositionTotal - grNacellePositionTotal)< rExpectedYawAngle)",
- "set_delay": "PAR_tYawSlowDelay",
- "yp": "100",
- "reset_en": "The true yaw angle will be the same as the expected yaw angle.(ABS(grNacellePositionTotal - grNacellePositionTotal)= rExpectedYawAngle)",
- "reset_cn": "真实的偏航角度等于期望的偏航角度。(ABS(grNacellePositionTotal - grNacellePositionTotal)= rExpectedYawAngle)",
- "reset_mode": "M",
- "type": "A",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_10_009": {
- "subsystem": "YawSystem",
- "name": "SC_RepFault_YawSpeedTooSlow",
- "en": "The fault of yaw low speed has repeated",
- "cn": "偏航系统速度过慢故障重复出现",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The statuscode \"SC_YawSpeedTooSlow\" becomes more times TRUE than maximum allowed.(gbRepeat_02_10_008=1)",
- "trigger_cn": "偏航系统速度过慢故障重复出现。(gbRepeat_02_10_008=1)",
- "set_delay": "T#0s",
- "yp": "100",
- "reset_en": "The statuscode \"SC_YawSpeedTooSlow\" becomes less times TRUE than maximum allowed.(gbRepeat_02_10_008=0)",
- "reset_cn": "偏航系统速度过慢故障不重复出现。(gbRepeat_02_10_008=0)",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "50-偏航警告",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "50",
- "brake_state_design": "0"
- },
- "02_10_010": {
- "subsystem": "YawSystem",
- "name": "SC_YawMotorTimeTooLong",
- "en": "Yaw motor is running too long",
- "cn": "偏航系统电机运行时间过长",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "No cable untwisting active, the ON-time of the yaw motors (CW or CCW direction) will exceed the maximim allowed time given by the parameter.(SC_StartRewindingLoopCables=0 AND (DQ_NacelleStartYawCW OR=1 OR DQ_NacelleStartYawCCW=1) AND DQ_NacelleOpenElectricalYawBrake=1))",
- "trigger_cn": "没有电缆解缆活动,顺时针或逆时针偏航电机运行时间高于上限值。(SC_StartRewindingLoopCables=0 AND (DQ_NacelleStartYawCW OR=1 OR DQ_NacelleStartYawCCW=1) AND DQ_NacelleOpenElectricalYawBrake=1))",
- "set_delay": "PAR_tYawMotorTimeTooLong",
- "yp": "100",
- "reset_en": "Cable untwisting active, or the ON-time of the yaw motors (CW or CCW direction) falls below the maximim allowed time given by the parameter.(SC_StartRewindingLoopCables=1 OR (DQ_NacelleStartYawCW OR=0 AND DQ_NacelleStartYawCCW=0) OR DQ_NacelleOpenElectricalYawBrake=0))",
- "reset_cn": "有电缆解缆活动,或顺时针和逆时针偏航电机运行时间在上限值内。(SC_StartRewindingLoopCables=1 OR (DQ_NacelleStartYawCW OR=0 AND DQ_NacelleStartYawCCW=0) OR DQ_NacelleOpenElectricalYawBrake=0))",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "50-偏航警告",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "50",
- "brake_state_design": "0"
- },
- "02_10_011": {
- "subsystem": "YawSystem",
- "name": "SC_STOP_ForBlockedYaw",
- "en": "Nacelle has big deviation from wind direction, but yaw is blocked",
- "cn": "机舱与风向偏离过大,但偏航系统被禁止",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The statuscode \"SC_YawAndWinddirDeviationTooHigh\" becomes TRUE but yaw is blocked.(SC_YawAndWinddirDeviationTooHigh=1 AND giYPLevel >= CON_iYawBlocked)",
- "trigger_cn": "机舱与风向偏离过大,但偏航系统被禁止。(SC_YawAndWinddirDeviationTooHigh=1 AND giYPLevel >= CON_iYawBlocked)",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "The statuscode \"SC_YawAndWinddirDeviationTooHigh\" becomes FALSE or yaw is not blocked.(SC_YawAndWinddirDeviationTooHigh=0 OR giYPLevel < CON_iYawBlocked)",
- "reset_cn": "机舱与风向偏离不过大,或偏航系统处于开启。(SC_YawAndWinddirDeviationTooHigh=0 OR giYPLevel < CON_iYawBlocked)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "51"
- },
- "02_10_012": {
- "subsystem": "YawSystem",
- "name": "SC_YawPositionEncoderFault",
- "en": "Yaw position encoder is implausible",
- "cn": "偏航系统位置编码器数值错误",
- "powerup_delay": "T#0s",
- "disable_level": "50",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Analogue signal is not ok and Yaw position encoder is implausible.(gbDI_NacelleCableTwist_CW_MAX1=0 OR gbDI_NacelleCableTwist_CCW_MAX1=0) AND ABS ((grCableTwistTotal) <= (0.95 * PAR_rYawTurnsCableTwist_STOP * 360.0)) OR ABS ((grYawPosition - PAR_rYawSensorOffsetAtNorthPos) > (2 * PAR_rYawTurnsCableTwistPreSTOP * 360.0))",
- "trigger_cn": "模拟信号不正常,偏航系统位置编码器数值不对。(gbDI_NacelleCableTwist_CW_MAX1=0 OR gbDI_NacelleCableTwist_CCW_MAX1=0) AND ABS ((grCableTwistTotal) <= (0.95 * PAR_rYawTurnsCableTwist_STOP * 360.0)) OR ABS ((grYawPosition - PAR_rYawSensorOffsetAtNorthPos) > (2 * PAR_rYawTurnsCableTwistPreSTOP * 360.0))",
- "set_delay": "T#1s",
- "yp": "100",
- "reset_en": "Analogue signal is ok and Yaw position encoder is plausible.(gbDI_NacelleCableTwist_CW_MAX1=1 AND gbDI_NacelleCableTwist_CCW_MAX1=1) OR ABS ((grCableTwistTotal) > (0.95 * PAR_rYawTurnsCableTwist_STOP * 360.0)) AND ABS ((grYawPosition - PAR_rYawSensorOffsetAtNorthPos) <= (2 * PAR_rYawTurnsCableTwistPreSTOP * 360.0))",
- "reset_cn": "模拟信号正常,或偏航系统位置编码器数值正确。(gbDI_NacelleCableTwist_CW_MAX1=1 AND gbDI_NacelleCableTwist_CCW_MAX1=1) OR ABS ((grCableTwistTotal) > (0.95 * PAR_rYawTurnsCableTwist_STOP * 360.0)) AND ABS ((grYawPosition - PAR_rYawSensorOffsetAtNorthPos) <= (2 * PAR_rYawTurnsCableTwistPreSTOP * 360.0))",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_10_013": {
- "subsystem": "YawSystem",
- "name": "SC_YawAndWinddirDeviationTooHigh",
- "en": "Nacelle has big deviation from wind direction",
- "cn": "机舱与风向偏离过大",
- "powerup_delay": "T#0s",
- "disable_level": "50",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "when giTurbineOperationMode is not in CON_iSelftest1/2/3/4_x000D_ The deviation between wind direction and nacelle direction will exceed the value given by parameter.(rVaneDirForCheck > rMaxAllowedDeviation)_x000D_",
- "trigger_cn": "风机不在自检1、2、3、4时,风向和机舱方向之间的偏差超过给定的参数值。(rVaneDirForCheck > rMaxAllowedDeviation)",
- "set_delay": "T#10s",
- "yp": "0",
- "reset_en": "The deviation between wind direction and nacelle direction will fall below the value given by parameter.(rVaneDirForCheck < rMaxAllowedDeviation)",
- "reset_cn": "风向和机舱方向之间的偏差不高于给定的参数值。(rVaneDirForCheck < rMaxAllowedDeviation)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "51"
- },
- "02_10_019": {
- "subsystem": "YawSystem",
- "name": "SC_TempYawMotors1_MAX",
- "en": "Temperature of yaw motor1 exceeds maximum limit",
- "cn": "偏航系统1号电机PTC测温电阻触发",
- "powerup_delay": "T#0s",
- "disable_level": "50",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The corresponding digital input gives TRUE signal for a time given by the initial values for the statuscode.(gbDI_TempYawMotor1=1)",
- "trigger_cn": "偏航1号电机温度高于上限相应的数字输入给出了TRUE信号。(gbDI_TempYawMotor1=1)",
- "set_delay": "T#1s",
- "yp": "100",
- "reset_en": "The corresponding digital input gives FALSE signal for a time given by the initial values for the statuscode.(gbDI_TempYawMotor1=0)",
- "reset_cn": "偏航1号电机温度高于上限相应的数字输入给出了FALSE信号。(gbDI_TempYawMotor1=0)",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "50-偏航警告",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "50",
- "brake_state_design": "0"
- },
- "02_10_020": {
- "subsystem": "YawSystem",
- "name": "SC_TempYawMotors2_MAX",
- "en": "Temperature of yaw motor2 exceeds maximum limit",
- "cn": "偏航系统2号电机PTC测温电阻触发",
- "powerup_delay": "T#0s",
- "disable_level": "50",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The corresponding digital input gives TRUE signal for a time given by the initial values for the statuscode.(gbDI_TempYawMotor2=1)",
- "trigger_cn": "偏航2号电机温度高于上限相应的数字输入给出了TRUE信号。(gbDI_TempYawMotor2=1)",
- "set_delay": "T#1s",
- "yp": "100",
- "reset_en": "The corresponding digital input gives FALSE signal for a time given by the initial values for the statuscode.(gbDI_TempYawMotor2=0)",
- "reset_cn": "偏航2号电机温度高于上限相应的数字输入给出了FALSE信号。(gbDI_TempYawMotor2=0)",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "50-偏航警告",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "50",
- "brake_state_design": "0"
- },
- "02_10_021": {
- "subsystem": "YawSystem",
- "name": "SC_TempYawMotors3_MAX",
- "en": "Temperature of yaw motor3 exceeds maximum limit",
- "cn": "偏航系统3号电机PTC测温电阻触发",
- "powerup_delay": "T#0s",
- "disable_level": "50",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The corresponding digital input gives TRUE signal for a time given by the initial values for the statuscode.(gbDI_TempYawMotor3=1)",
- "trigger_cn": "偏航3号电机温度高于上限相应的数字输入给出了TRUE信号。(gbDI_TempYawMotor3=1)",
- "set_delay": "T#1s",
- "yp": "100",
- "reset_en": "The corresponding digital input gives FALSE signal for a time given by the initial values for the statuscode.(gbDI_TempYawMotor3=0)",
- "reset_cn": "偏航3号电机温度高于上限相应的数字输入给出了FALSE信号。(gbDI_TempYawMotor3=0)",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "50-偏航警告",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "50",
- "brake_state_design": "0"
- },
- "02_10_022": {
- "subsystem": "YawSystem",
- "name": "SC_TempYawMotors4_MAX",
- "en": "Temperature of yaw motor4 exceeds maximum limit",
- "cn": "偏航系统4号电机PTC测温电阻触发",
- "powerup_delay": "T#0s",
- "disable_level": "50",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The corresponding digital input gives TRUE signal for a time given by the initial values for the statuscode.(gbDI_TempYawMotor4=1)",
- "trigger_cn": "偏航4号电机温度高于上限相应的数字输入给出了TRUE信号。(gbDI_TempYawMotor4=1)",
- "set_delay": "T#1s",
- "yp": "100",
- "reset_en": "The corresponding digital input gives FALSE signal for a time given by the initial values for the statuscode.(gbDI_TempYawMotor4=0)",
- "reset_cn": "偏航4号电机温度高于上限相应的数字输入给出了FALSE信号。(gbDI_TempYawMotor4=0)",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "50-偏航警告",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "50",
- "brake_state_design": "0"
- },
- "02_10_101": {
- "subsystem": "YawSystem",
- "name": "SC_YawManualOperation",
- "en": "Yaw is in manual operation",
- "cn": "偏航系统处于手动模式",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The yaw program is that one for manual mode activated by a service switch on the turbine or by remote command.[gbMAIN_YawManual=1 OR ((gbDI_NacelleYawCW=1 OR gbDI_NacelleYawCCW=1) AND gbDI_SafetyChainNacelleWECinServiceGeneral=1) OR ((gbDI_TowerYawCW OR gbDI_TowerYawCW=1) AND gbDI_TowerSafetyChainWECinService=1) ]",
- "trigger_cn": "偏航系统处于手动模式(由风机上的开关激活或远程命令激活)[gbMAIN_YawManual=1 OR ((gbDI_NacelleYawCW=1 OR gbDI_NacelleYawCCW=1) AND gbDI_SafetyChainNacelleWECinServiceGeneral=1) OR ((gbDI_TowerYawCW OR gbDI_TowerYawCW=1) AND gbDI_TowerSafetyChainWECinService=1) ]",
- "set_delay": "T#0s",
- "yp": "30",
- "reset_en": "The yaw program is not ones for manual mode activated by a service switch on the turbine and by remote command.[gbMAIN_YawManual=0 AND ((gbDI_NacelleYawCW=0 AND gbDI_NacelleYawCCW=0) OR gbDI_SafetyChainNacelleWECinServiceGeneral=0) AND ((gbDI_TowerYawCW OR gbDI_TowerYawCW=0) OR gbDI_TowerSafetyChainWECinService=0) ]",
- "reset_cn": "偏航系统不处于任一手动模式(由风机上的开关激活或远程命令激活)[gbMAIN_YawManual=0 AND ((gbDI_NacelleYawCW=0 AND gbDI_NacelleYawCCW=0) OR gbDI_SafetyChainNacelleWECinServiceGeneral=0) AND ((gbDI_TowerYawCW OR gbDI_TowerYawCW=0) OR gbDI_TowerSafetyChainWECinService=0) ]",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "02_10_102": {
- "subsystem": "YawSystem",
- "name": "SC_StartRewindingLoopCables",
- "en": "Yaw starts to rewind loop cables",
- "cn": "偏航系统开始自动解缆",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "①Cable twist exceeds the range for PreSTOP AND P<Parameter.(MODTURNS(ABS (grCableTwistTotal_100ms), 36)/10.0>= PAR_rYawTurnsCableTwistPreSTOP) AND (grGenPowerForProcess_10min < PAR_rPowerAboveUntwistCablePreSTOP) AND (giYPLevel <= CON_iYawUntwistMode);②Cable twist exceeds the range for STOP.(gbDI_NacelleCableTwist_CW_MAX1=0 OR gbDI_NacelleCableTwist_CCW_MAX1=0) AND giYPLevel <= CON_iYawUntwistMode.",
- "trigger_cn": "①电缆缠绕高于PreSTOP 范围。(MODTURNS(ABS (grCableTwistTotal_100ms), 36)/10.0>= PAR_rYawTurnsCableTwistPreSTOP) AND (grGenPowerForProcess_10min < PAR_rPowerAboveUntwistCablePreSTOP) AND (giYPLevel <= CON_iYawUntwistMode);②电缆缠绕高于STOP范围。(gbDI_NacelleCableTwist_CW_MAX1=0 OR gbDI_NacelleCableTwist_CCW_MAX1=0) AND giYPLevel <= CON_iYawUntwistMode",
- "set_delay": "T#0s",
- "yp": "10",
- "reset_en": "Yaw finishes rewind loop cables.(bUntwistDone=1 OR (giYPLevel > CON_iYawUntwistMode))",
- "reset_cn": "偏航系统完成解缆工作。(bUntwistDone=1 OR (giYPLevel > CON_iYawUntwistMode))",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "30-待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "30",
- "brake_state_design": "51"
- },
- "02_10_105": {
- "subsystem": "YawSystem",
- "name": "OC_RewindingLoopCablesActive",
- "en": "Yaw is in cable untwist mode",
- "cn": "偏航系统处于自动解缆模式",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Yaw is in cable untwist mode.(giYPLevel = CON_iYawUntwistMode)",
- "trigger_cn": "偏航系统处于解缆模式。(giYPLevel = CON_iYawUntwistMode)",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "Yaw is not in cable untwist mode.(giYPLevel ≠ CON_iYawUntwistMode)",
- "reset_cn": "偏航系统不处于解缆模式。(giYPLevel ≠ CON_iYawUntwistMode)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "30-待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "30",
- "brake_state_design": "51"
- },
- "02_10_106": {
- "subsystem": "YawSystem",
- "name": "SC_AutoGreaseError",
- "en": "Error happens when auto grease",
- "cn": "偏航系统自润滑设备故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Error happens when auto grease.(gbDI_NacelleYawAutoGreasePulse=PAR_bAutoGreaseError)",
- "trigger_cn": "发生自润滑故障。(gbDI_NacelleYawAutoGreasePulse=PAR_bAutoGreaseError)",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "Error does not happen when auto grease.(gbDI_NacelleYawAutoGreasePulse=PAR_bAutoGreaseError)",
- "reset_cn": "自润滑故障解除。(gbDI_NacelleYawAutoGreasePulse=PAR_bAutoGreaseError)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_10_107": {
- "subsystem": "YawSystem",
- "name": "SC_StartAutoGrease",
- "en": "Starts to auto grease",
- "cn": "偏航系统开始自润滑",
- "powerup_delay": "T#40s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Starts to auto grease.(gbDQ_NacelleAutoGrease=1)",
- "trigger_cn": "开始自润滑。(gbDQ_NacelleAutoGrease=1)",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "Auto grease is over.(gbDQ_NacelleAutoGrease=0)",
- "reset_cn": "自润滑结束。(gbDQ_NacelleAutoGrease=0)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "02_10_109": {
- "subsystem": "YawSystem",
- "name": "SC_PreAutoGrease",
- "en": "Prepare for auto grease",
- "cn": "偏航系统自润滑预备",
- "powerup_delay": "T#40s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Auto grease does not finish, and wind and generator speed is less than auto grease limit.(gbAutoGreaseFinished=0 AND grGenSpeedForProcess_100ms < PAR_rGenSpeedLimitToAutoGrease AND PAR_bAutoGreaseEnable=1 AND grWindSpeed1_100ms<PAR_rWindSpeedLimitToAutoGrease )",
- "trigger_cn": "自润滑没有完成,且风机和发电机速度小于自润滑限制速度。(gbAutoGreaseFinished=0 AND grGenSpeedForProcess_100ms < PAR_rGenSpeedLimitToAutoGrease AND PAR_bAutoGreaseEnable=1 AND grWindSpeed1_100ms<PAR_rWindSpeedLimitToAutoGrease )",
- "set_delay": "T#1s",
- "yp": "3",
- "reset_en": "Auto grease does not finish, and wind and generator speed is less than auto grease limit.(gbAutoGreaseFinished=1 OR grGenSpeedForProcess_100ms > PAR_rGenSpeedLimitToAutoGrease OR PAR_bAutoGreaseEnable=1 OR grWindSpeed1_100ms>PAR_rWindSpeedLimitToAutoGrease )",
- "reset_cn": "自润滑完成,或风机\\发电机速度大于自润滑限制速度。(gbAutoGreaseFinished=1 OR grGenSpeedForProcess_100ms > PAR_rGenSpeedLimitToAutoGrease OR PAR_bAutoGreaseEnable=1 OR grWindSpeed1_100ms>PAR_rWindSpeedLimitToAutoGrease )",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "30-待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "30",
- "brake_state_design": "51"
- },
- "02_10_110": {
- "subsystem": "YawSystem",
- "name": "SC_AutoGreaseErrorBeka",
- "en": "Error happens when auto grease",
- "cn": "偏航系统自润滑设备故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Error happens when auto grease.(gbDI_NacelleYawAutoGreasePulse=PAR_bAutoGreaseError)",
- "trigger_cn": "发生自润滑故障。(gbDI_NacelleYawAutoGreasePulse=PAR_bAutoGreaseError)",
- "set_delay": "T#60s",
- "yp": "0",
- "reset_en": "Error does not happen when auto grease.(gbDI_NacelleYawAutoGreasePulse=PAR_bAutoGreaseError)",
- "reset_cn": "自润滑故障解除。(gbDI_NacelleYawAutoGreasePulse=PAR_bAutoGreaseError)",
- "reset_mode": "M",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_12_003": {
- "subsystem": "YawSystem",
- "name": "SC_ManualYawBySoftware",
- "en": "Manual yaw is commanded remotely",
- "cn": "远程发出手工偏航命令",
- "powerup_delay": "T#0s",
- "disable_level": "50",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The manual mode for yaw is activated by remote command.(RemComOK_YawManual=1)",
- "trigger_cn": "偏航手动模式被远程命令激活。(RemComOK_YawManual=1)",
- "set_delay": "T#0s",
- "yp": "30",
- "reset_en": "The manual mode for yaw is not activated by remote command.(RemComOK_YawManual=0)",
- "reset_cn": "偏航手动模式没有远程激活命令。(RemComOK_YawManual=0)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "03_08_002": {
- "subsystem": "YawSystem",
- "name": "SC_LimitSwitchCableTwistBridged",
- "en": "Cable twist limit switch is bridged for untwisting",
- "cn": "旁路扭缆限位开关,重新得电后可以手动解缆",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "_x000D_ One of the limit switches for cable twist is triggered AND a user command via switch for bridging the limit switch contacts is TRUE.((gbDI_NacelleCableTwist_CW_MAX2=1 OR gbDI_NacelleCableTwist_CCW_MAX2=1) AND gbDI_NacelleYawBridgeLimitSwitchCableTwist=1)",
- "trigger_cn": "电缆扭转限位开关被触发,且限位开关被旁路为TRUE。((gbDI_NacelleCableTwist_CW_MAX2=1 OR gbDI_NacelleCableTwist_CCW_MAX2=1) AND gbDI_NacelleYawBridgeLimitSwitchCableTwist=1)",
- "set_delay": "T#0s",
- "yp": "30",
- "reset_en": "One of the limit switches for cable twist is not triggered AND a user command via switch for bridging the limit switch contacts is FALSE.((gbDI_NacelleCableTwist_CW_MAX2=0 AND gbDI_NacelleCableTwist_CCW_MAX2=0) OR gbDI_NacelleYawBridgeLimitSwitchCableTwist=0)",
- "reset_cn": "电缆扭转限位开关没有被触发,或限位开关被旁路为FALSE。((gbDI_NacelleCableTwist_CW_MAX2=0 AND gbDI_NacelleCableTwist_CCW_MAX2=0) OR gbDI_NacelleYawBridgeLimitSwitchCableTwist=0)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "51"
- },
- "04_11_001": {
- "subsystem": "GCC",
- "name": "SC_Transformer_Gasses_Pressure_Fault",
- "en": "Transformer has dissoved gasses in oil or high pressure (outputs from DGPT2 relay)",
- "cn": "变压器油中溶解气体或压力过高",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#15ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "100"
- },
- "04_11_002": {
- "subsystem": "GCC",
- "name": "SC_Transformer_Temp_High",
- "en": "Transformer oil temperature is high (output from DGPT2 relay)",
- "cn": "变压器温度高报警",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_11_003": {
- "subsystem": "GCC",
- "name": "SC_Transformer_Temp_VeryHigh",
- "en": "Transformer oil temperature is very high (output from DGPT2 relay)",
- "cn": "变压器温度高故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_11_004": {
- "subsystem": "GCC",
- "name": "SC_Switchgear_LineDisconnector_Open",
- "en": "",
- "cn": "高压断路器无负荷开关分闸",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_11_005": {
- "subsystem": "GCC",
- "name": "SC_Switchgear_EarthingContactor_Closed",
- "en": "Earthing contactor on transformer side closed OR earthing contactor on grid side closed",
- "cn": "高压断路器接地开关合闸",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "51"
- },
- "04_11_006": {
- "subsystem": "GCC",
- "name": "SC_Switchgear_CB_Open",
- "en": "",
- "cn": "开关设备打开",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_11_007": {
- "subsystem": "GCC",
- "name": "SC_Switchgear_SF6_Pressure_Low",
- "en": "SF-6 gas pressure is low",
- "cn": "SF6压力过低报警",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "False",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_11_009": {
- "subsystem": "GCC",
- "name": "SC_Switchgear_MCB_Trip",
- "en": "Miniature circuit breaker 1 or 2 in switchgear internal supply has tripped",
- "cn": "开关设备空开跳开",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_11_010": {
- "subsystem": "GCC",
- "name": "SC_Switchgear_CB_Trip",
- "en": "Circuit breaker has tripped",
- "cn": "开关设备断路器跳开",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#15ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "100"
- },
- "04_11_011": {
- "subsystem": "GCC",
- "name": "SC_Switchgear_CB_Opening_Failure",
- "en": "Circuit breaker has failed to open after a DO command",
- "cn": "开关设备打开失败",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_11_012": {
- "subsystem": "GCC",
- "name": "SC_Switchgear_CB_Closing_Failure",
- "en": "Circuit breaker has failed to close after a DO command",
- "cn": "开关设备闭合失败",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_11_013": {
- "subsystem": "GCC",
- "name": "OC_Switchgear_CB_Closing_Coil",
- "en": "Output from WTC which attempts to close CB in switchgear",
- "cn": "开关设备正在关闭",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "100",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "51"
- },
- "04_11_014": {
- "subsystem": "GCC",
- "name": "OC_Switchgear_CB_Opening_Coil",
- "en": "Output from WTC which attempts to open CB in switchgear",
- "cn": "开关设备正在打开",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "100",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "51"
- },
- "04_11_015": {
- "subsystem": "GCC",
- "name": "SC_Switchboard_690V_In_CB",
- "en": "The incoming CB to the 690V switchboard has tripped",
- "cn": "电网到690V的CB跳开",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_11_016": {
- "subsystem": "GCC",
- "name": "SC_Switchboard_690V_AuxTrafo_CB",
- "en": "The CB at the incoming side of the 690/400V auxiliary supply transformer has tripped",
- "cn": "690V到400V的变压器CB跳开",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_11_017": {
- "subsystem": "GCC",
- "name": "SC_Switchboard_690V_ExtGen_CB",
- "en": "The CB for the external generator connection has tripped",
- "cn": "外部发电机到690V的CB跳开",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_11_018": {
- "subsystem": "GCC",
- "name": "SC_Switchboard_690V_Group_CB",
- "en": "At least one of the CB in the 690V group of CB's has tripped",
- "cn": "至少一个690V的CB跳开",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_11_019": {
- "subsystem": "GCC",
- "name": "SC_Switchboard_400V_In_CB",
- "en": "The CB at the incoming side of the 400V switchboard has tripped",
- "cn": "400V配电盘进电开关QTR2闭合",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_11_020": {
- "subsystem": "GCC",
- "name": "SC_Switchboard_400V_UPS_In_CB",
- "en": "The CB at the incoming side to the UPS has tripped",
- "cn": "400V配电盘QA12闭合",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_11_021": {
- "subsystem": "GCC",
- "name": "SC_Switchboard_400V_Group_CB",
- "en": "At least one of the CB in the 400V group of CB's has tripped",
- "cn": "400V配电盘(QA1-Q11+Q13-QA16)闭合",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_11_022": {
- "subsystem": "GCC",
- "name": "SC_Switchboard_400V_UPS_Out_CB",
- "en": "The CB on the output of the UPS has tripped",
- "cn": "UPS供电空开QUPS闭合",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#15ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "198"
- },
- "04_11_023": {
- "subsystem": "GCC",
- "name": "SC_Switchboard_400V_UPS_Group_CB",
- "en": "At least one of the CB's in the UPS group of CB's has tripped",
- "cn": "230V配电盘(QB1-QB8,QAUX)闭合",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#15ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_11_024": {
- "subsystem": "GCC",
- "name": "SC_UPS_AC_Fail",
- "en": "Failure on incoming AC supply",
- "cn": "UPS进电故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_11_025": {
- "subsystem": "GCC",
- "name": "SC_UPS_Batt_Low",
- "en": "Battery low",
- "cn": "UPS电池电压过低",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_11_026": {
- "subsystem": "GCC",
- "name": "SC_UPS_Batt_Low_Timeout",
- "en": "Battery has been low for longer time than allowed",
- "cn": "UPS进电故障或电池电压过低超时",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "PAR_tUPS_Batt_Low_Shutdown_Time",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "165",
- "brake_state_design": "51"
- },
- "04_11_029": {
- "subsystem": "GCC",
- "name": "SC_GCC_Temp_High",
- "en": "Temperature measured on one or both PT100's is high",
- "cn": "箱变温度过高报警",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_11_030": {
- "subsystem": "GCC",
- "name": "SC_GCC_Temp_VeryHigh",
- "en": "Temperature measured on one or both PT100's is very high",
- "cn": "箱变温度过高故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_11_031": {
- "subsystem": "GCC",
- "name": "SC_GCC_Temp_Low",
- "en": "Temperature measured on one or both PT100's is low",
- "cn": "箱变温度过低",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_11_032": {
- "subsystem": "GCC",
- "name": "SC_FaultPT100_GCC_Temp1",
- "en": "",
- "cn": "高压室内温度PT100故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_11_033": {
- "subsystem": "GCC",
- "name": "SC_FaultPT100_Transformer_Temp",
- "en": "",
- "cn": "箱变油温PT100故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_14_001": {
- "subsystem": "GridMeasurement",
- "name": "SC_PowerMeasurementUnit_Fail",
- "en": "",
- "cn": "电网测量设备故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_11_034": {
- "subsystem": "GCC",
- "name": "SC_UPS_Unhealthy",
- "en": "",
- "cn": "UPS设备供电时间过短",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_01_001": {
- "subsystem": "SafetySystem",
- "name": "SC_Safety_Loop_Open",
- "en": "",
- "cn": "安全系统断开安全链",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "200"
- },
- "04_01_002": {
- "subsystem": "SafetySystem",
- "name": "SC_SafetyController_Not_Alive",
- "en": "",
- "cn": "安全控制器失效",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "100",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "200"
- },
- "04_01_003": {
- "subsystem": "SafetySystem",
- "name": "SC_RotorSpeed_Unequal_SafetyController",
- "en": "",
- "cn": "PLC的测得转速与安全控制器不同",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "200"
- },
- "04_01_004": {
- "subsystem": "SafetySystem",
- "name": "SC_SSD_Active",
- "en": "",
- "cn": "SSD振动触发",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "100",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "200"
- },
- "04_01_005": {
- "subsystem": "SafetySystem",
- "name": "SC_Tower_Vibration_Active",
- "en": "",
- "cn": "塔筒振动过大",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "100",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "200"
- },
- "04_01_006": {
- "subsystem": "SafetySystem",
- "name": "SC_SafetyChain_RotorOverSpeedError",
- "en": "",
- "cn": "过速断开安全链",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "175",
- "brake_state_design": "0"
- },
- "04_01_007": {
- "subsystem": "SafetySystem",
- "name": "SC_SafetyChain_WTCAliveSignalError",
- "en": "",
- "cn": "来自主控的频率信号丢失断开安全链",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "175",
- "brake_state_design": "0"
- },
- "04_01_008": {
- "subsystem": "SafetySystem",
- "name": "SC_SafetyChain_SpeedSensorError",
- "en": "",
- "cn": "安全控制器测得转速与主控测得转速不匹配断开安全链",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "175",
- "brake_state_design": "0"
- },
- "04_01_009": {
- "subsystem": "SafetySystem",
- "name": "SC_SafetyChain_G_Sensor1_Error",
- "en": "",
- "cn": "SSD振动断开安全链",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "175",
- "brake_state_design": "0"
- },
- "04_01_010": {
- "subsystem": "SafetySystem",
- "name": "SC_SafetyChain_G_Sensor2_Error",
- "en": "",
- "cn": "塔筒振动断开安全链",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "175",
- "brake_state_design": "0"
- },
- "04_01_011": {
- "subsystem": "SafetySystem",
- "name": "SC_SafetyChain_EmergencyStopActivated",
- "en": "",
- "cn": "急停断开安全链",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "175",
- "brake_state_design": "0"
- },
- "04_01_012": {
- "subsystem": "SafetySystem",
- "name": "SC_SafetyChain_YawLimitSwitchActivated",
- "en": "",
- "cn": "偏航二级限位断开安全链",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "175",
- "brake_state_design": "0"
- },
- "04_01_013": {
- "subsystem": "SafetySystem",
- "name": "SC_SafetyChain_SafetyLoopFeedback_Error",
- "en": "",
- "cn": "安全链复位失败",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "175",
- "brake_state_design": "0"
- },
- "04_01_015": {
- "subsystem": "SafetySystem",
- "name": "SC_SafetyChain_GeneratorOverSpeedError",
- "en": "",
- "cn": "发电机过速断开安全链",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "175",
- "brake_state_design": "0"
- },
- "04_02_007": {
- "subsystem": "PitchSystem",
- "name": "SC_Blade1PitchAngleWrong91Pos",
- "en": "Blade1 Wrong angle at 91 position",
- "cn": "1号桨叶91度限位触发位置故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "gbBlade1Limit91WrongPos OR di_PITCH_Blade1Limit91Incoherence",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "当3号桨叶角脱开91度限位后,或1号桨叶触发91度限位后,编码器角度值在合理范围内",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_02_008": {
- "subsystem": "PitchSystem",
- "name": "SC_Blade2PitchAngleWrong91Pos",
- "en": "Blade2 Wrong angle at 91 position",
- "cn": "2号桨叶91度限位触发位置故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "gbBlade2Limit91WrongPos OR di_PITCH_Blade2Limit91Incoherence",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "当3号桨叶角脱开91度限位后,或1号桨叶触发91度限位后,编码器角度值在合理范围内",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_02_009": {
- "subsystem": "PitchSystem",
- "name": "SC_Blade3PitchAngleWrong91Pos",
- "en": "Blade3 Wrong angle at 91 position",
- "cn": "3号桨叶91度限位触发位置故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "gbBlade3Limit91WrongPos OR di_PITCH_Blade3Limit91Incoherence",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "当3号桨叶角脱开91度限位后,或1号桨叶触发91度限位后,编码器角度值在合理范围内",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_02_010": {
- "subsystem": "PitchSystem",
- "name": "SC_Blade1PitchAngleWrong95Pos",
- "en": "Blade1 Wrong angle at 95 position",
- "cn": "1号桨叶95度限位触发位置故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "当1号桨叶角触发95度时,桨叶角度值不在合理区间内。需要为合理区间设定一个可调的参数。_x000D_ 或当主控收到变桨系统故障信息DI_Position incoherence limit switch B axis 1=1时触发",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "当3号桨叶角脱开95度限位后,或1号桨叶触发95度限位后,编码器角度值在合理范围内",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_02_011": {
- "subsystem": "PitchSystem",
- "name": "SC_Blade2PitchAngleWrong95Pos",
- "en": "Blade2 Wrong angle at 95 position",
- "cn": "2号桨叶95度限位触发位置故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "当2号桨叶角触发95度时,桨叶角度值不在合理区间内。需要为合理区间设定一个可调的参数。_x000D_ 或当主控收到变桨系统故障信息DI_Position incoherence limit switch B axis 2=1时触发",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "当3号桨叶角脱开95度限位后,或1号桨叶触发95度限位后,编码器角度值在合理范围内",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_02_012": {
- "subsystem": "PitchSystem",
- "name": "SC_Blade3PitchAngleWrong95Pos",
- "en": "Blade3 Wrong angle at 95 position",
- "cn": "3号桨叶95度限位触发位置故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "当3号桨叶角触发95度时,桨叶角度值不在合理区间内。需要为合理区间设定一个可调的参数。_x000D_ 或当主控收到变桨系统故障信息DI_Position incoherence limit switch B axis 3=1时触发",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "当3号桨叶角脱开95度限位后,或1号桨叶触发95度限位后,编码器角度值在合理范围内",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_02_013": {
- "subsystem": "PitchSystem",
- "name": "SC_UndervoltageBackupAxis1",
- "en": "Undervoltage backup axis 1",
- "cn": "1号桨叶后备电源电压过低故障",
- "powerup_delay": "T#30s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_Backup1UnderVoltage",
- "trigger_cn": "",
- "set_delay": "T#10s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_Undervoltage backup axis 1=0",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_02_014": {
- "subsystem": "PitchSystem",
- "name": "SC_UndervoltageBackupAxis2",
- "en": "Undervoltage backup axis 2",
- "cn": "2号桨叶后备电源电压过低故障",
- "powerup_delay": "T#30s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_Backup2UnderVoltage",
- "trigger_cn": "",
- "set_delay": "T#10s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_Undervoltage backup axis 2=0",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_02_015": {
- "subsystem": "PitchSystem",
- "name": "SC_UndervoltageBackupAxis3",
- "en": "Undervoltage backup axis 3",
- "cn": "3号桨叶后备电源电压过低故障",
- "powerup_delay": "T#30s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_Backup3UnderVoltage",
- "trigger_cn": "",
- "set_delay": "T#10s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_Undervoltage backup axis 3=0",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_02_016": {
- "subsystem": "PitchSystem",
- "name": "SC_OvervoltageBackupAxis1",
- "en": "Overvoltage backup axis 1",
- "cn": "1号桨叶后备电源电压过高故障",
- "powerup_delay": "T#30s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_Backup1OverVoltage",
- "trigger_cn": "",
- "set_delay": "T#10s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_Overvoltage backup axis 1=0",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_02_017": {
- "subsystem": "PitchSystem",
- "name": "SC_OvervoltageBackupAxis2",
- "en": "Overvoltage backup axis 2",
- "cn": "2号桨叶后备电源电压过高故障",
- "powerup_delay": "T#30s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_Backup2OverVoltage",
- "trigger_cn": "",
- "set_delay": "T#10s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_Overvoltage backup axis 2=0",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_02_018": {
- "subsystem": "PitchSystem",
- "name": "SC_OvervoltageBackupAxis3",
- "en": "Overvoltage backup axis 3",
- "cn": "3号桨叶后备电源电压过高故障",
- "powerup_delay": "T#30s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_Backup3OverVoltage",
- "trigger_cn": "",
- "set_delay": "T#10s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_Overvoltage backup axis 3=0",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_02_019": {
- "subsystem": "PitchSystem",
- "name": "SC_OvertemperatureAxisBox1",
- "en": "Overtemperature axis box 1",
- "cn": "1号轴控柜温度过高故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_AxisBox1OverTemp",
- "trigger_cn": "",
- "set_delay": "T#1S",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_Overtemperature axis box 1=0",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_02_020": {
- "subsystem": "PitchSystem",
- "name": "SC_OvertemperatureAxisBox2",
- "en": "Overtemperature axis box 2",
- "cn": "2号轴控柜温度过高故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_AxisBox2OverTemp",
- "trigger_cn": "",
- "set_delay": "T#1S",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_Overtemperature axis box 2=0",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_02_021": {
- "subsystem": "PitchSystem",
- "name": "SC_OvertemperatureAxisBox3",
- "en": "Overtemperature axis box 3",
- "cn": "3号轴控柜温度过高故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_AxisBox3OverTemp",
- "trigger_cn": "",
- "set_delay": "T#1S",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_Overtemperature axis box 3=0",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_02_022": {
- "subsystem": "PitchSystem",
- "name": "SC_UndertemperatureAxisBox1",
- "en": "Undertemperature axis box 1",
- "cn": "1号轴控柜温度过低故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_AxisBox1UnderTemp",
- "trigger_cn": "",
- "set_delay": "T#1S",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_Undertemperature axis box 1=0",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_02_023": {
- "subsystem": "PitchSystem",
- "name": "SC_UndertemperatureAxisBox2",
- "en": "Undertemperature axis box 2",
- "cn": "2号轴控柜温度过低故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_AxisBox2UnderTemp",
- "trigger_cn": "",
- "set_delay": "T#1S",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_Undertemperature axis box 2=0",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_02_024": {
- "subsystem": "PitchSystem",
- "name": "SC_UndertemperatureAxisBox3",
- "en": "Undertemperature axis box 3",
- "cn": "3号轴控柜温度过低故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_AxisBox3UnderTemp",
- "trigger_cn": "",
- "set_delay": "T#1S",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_Undertemperature axis box 3=0",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_02_025": {
- "subsystem": "PitchSystem",
- "name": "SC_InfoTcuActive",
- "en": "Pitch Information Tcu active",
- "cn": "变桨系统发出内部信息",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_InfoTCUActive",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "di_PITCH_InfoTCUActive=0",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "30-待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "30",
- "brake_state_design": "0"
- },
- "04_02_026": {
- "subsystem": "PitchSystem",
- "name": "SC_WarnTcuActive",
- "en": "Pitch Warning Tcu active",
- "cn": "变桨系统发出报警信息",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_WarnTCUActive",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "当WarnTcu active=0时(DI_PITCH_WarnTcu active=0)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "30-待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "30",
- "brake_state_design": "0"
- },
- "04_02_027": {
- "subsystem": "PitchSystem",
- "name": "SC_ErrTcuActive",
- "en": "Pitch Error Tcu active",
- "cn": "变桨系统发出故障信息",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_ErrTCUActive",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "当ErrTcu active=0时(DI_ErrTcu active=0)",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "30-待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "30",
- "brake_state_design": "0"
- },
- "04_02_028": {
- "subsystem": "PitchSystem",
- "name": "SC_ErrPcuActive",
- "en": "Pitch Error Pcu active",
- "cn": "变桨系统出现内部故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_ErrPCUActive",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "当ErrPcu active=0时(DI_ErrPcu active=0)",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "30-待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "30",
- "brake_state_design": "0"
- },
- "04_02_029": {
- "subsystem": "PitchSystem",
- "name": "SC_Blade1DCLinkVoltageNotOK",
- "en": "Axis 1 DC bus voltage not OK",
- "cn": "1号桨直流母线电压不正常故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_Blade1DCLinkOK=0",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "当1号桨叶的直流母线电压正常时(DI_axis1_DC link voltage ok=1)",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "198"
- },
- "04_02_030": {
- "subsystem": "PitchSystem",
- "name": "SC_Blade2DCLinkVoltageNotOK",
- "en": "Axis 2 DC bus voltage not OK",
- "cn": "2号桨直流母线电压不正常故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_Blade2DCLinkOK=0",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "当2号桨叶的直流母线电压正常时(DI_axis2_DC link voltage ok=1)",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "198"
- },
- "04_02_031": {
- "subsystem": "PitchSystem",
- "name": "SC_Blade3DCLinkVoltageNotOK",
- "en": "Axis 3 DC bus voltage not OK",
- "cn": "3号桨直流母线电压不正常故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_Blade3DCLinkOK=0",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "当3号桨叶的直流母线电压正常时(DI_axis3_DC link voltage ok=1)",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "198"
- },
- "04_02_032": {
- "subsystem": "PitchSystem",
- "name": "SC_24VSupplyAxis1",
- "en": "24V supply axis 1",
- "cn": "1号桨叶24V电源故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_Blade1_24VSupplyError=1",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_24V supply axis 1=0",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "30-待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "30",
- "brake_state_design": "0"
- },
- "04_02_033": {
- "subsystem": "PitchSystem",
- "name": "SC_24VSupplyAxis2",
- "en": "24V supply axis 2",
- "cn": "2号桨叶24V电源故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_Blade2_24VSupplyError=1",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_24V supply axis 2=0",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "30-待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "30",
- "brake_state_design": "0"
- },
- "04_02_034": {
- "subsystem": "PitchSystem",
- "name": "SC_24VSupplyAxis3",
- "en": "24V supply axis 3",
- "cn": "3号桨叶24V电源故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_Blade3_24VSupplyError=1",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_24V supply axis 3=0",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "30-待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "30",
- "brake_state_design": "0"
- },
- "04_02_035": {
- "subsystem": "PitchSystem",
- "name": "SC_PitchCommunicationError",
- "en": "Communication error TCU",
- "cn": "主控制与变桨间的通讯故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "gbPitchCANDisturbed AND gbPitchProfibusDisturbed",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "当CANBUS和PROFIBUS通讯其中之一恢复后此故障可被复位",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "50",
- "brake_state_design": "198"
- },
- "04_02_036": {
- "subsystem": "PitchSystem",
- "name": "OC_PitchCANCommunicationError",
- "en": "Communication error TCU Field Bus Primary",
- "cn": "主控与变桨之间的Canbus通讯故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "PAR_iNumberMaxPitchComError",
- "repeat_period": "PAR_tIntervalMaxPitchComError",
- "trigger_en": "gbPitchCANDisturbed",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "如果CANBUS的通讯恢复后此故障可被复位",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "165",
- "brake_state_design": "0"
- },
- "04_02_037": {
- "subsystem": "PitchSystem",
- "name": "OC_PitchProfibusCommunicationError",
- "en": "Communication error TCU Field Bus Secondary",
- "cn": "主控与变桨之间的无线Profibus通讯故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "gbPitchProfibusDisturbed",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "如果ProfiBUS的通讯恢复后此故障可被复位",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "165",
- "brake_state_design": "0"
- },
- "04_02_038": {
- "subsystem": "PitchSystem",
- "name": "SC_PitchInLVRT",
- "en": "Pitch in LVRT status",
- "cn": "变桨系统处于低电压穿越模式",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_LVRT",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "100",
- "reset_en": "",
- "reset_cn": "当LVRT=0",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_02_039": {
- "subsystem": "PitchSystem",
- "name": "SC_OvertemperatureMotorAxis1",
- "en": "Overtemperature motor axis 1",
- "cn": "1号变桨电机温度过高故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_Motor1OverTemp",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_Overtemperature motor axis 1=0",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_02_040": {
- "subsystem": "PitchSystem",
- "name": "SC_OvertemperatureMotorAxis2",
- "en": "Overtemperature motor axis 2",
- "cn": "2号变桨电机温度过高故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_Motor2OverTemp",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_Overtemperature motor axis 2=0",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_02_041": {
- "subsystem": "PitchSystem",
- "name": "SC_OvertemperatureMotorAxis3",
- "en": "Overtemperature motor axis 3",
- "cn": "3号变桨电机温度过高故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_Motor3OverTemp",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_Overtemperature motor axis 3=0",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_02_042": {
- "subsystem": "PitchSystem",
- "name": "SC_UndertemperatureMotorAxis1",
- "en": "Undertemperature motor axis 1",
- "cn": "1号变桨电机温度过低故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_Motor1UnderTemp",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_Undertemperature motor axis 1=0",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_02_043": {
- "subsystem": "PitchSystem",
- "name": "SC_UndertemperatureMotorAxis2",
- "en": "Undertemperature motor axis 2",
- "cn": "2号变桨电机温度过低故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_Motor2UnderTemp",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_Undertemperature motor axis 2=0",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_02_044": {
- "subsystem": "PitchSystem",
- "name": "SC_UndertemperatureMotorAxis3",
- "en": "Undertemperature motor axis 3",
- "cn": "3号变桨电机温度过低故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_Motor3UnderTemp",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_Undertemperature motor axis 3=0",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_02_045": {
- "subsystem": "PitchSystem",
- "name": "SC_PcuOpenSafetychain",
- "en": "Pcu opens safetychain",
- "cn": "变桨系统断开EFC反馈信号",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_PCUSafetyLineClosed = 0",
- "trigger_cn": "",
- "set_delay": "T#300ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_Pcu safetychain is closed=1",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "198"
- },
- "04_02_046": {
- "subsystem": "PitchSystem",
- "name": "SC_TcuOpenSafetychainFirst",
- "en": "Tcu opens safetychain first",
- "cn": "主控先断开了EFC信号",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_TCUSafetyLineOpened OR di_PITCH_TCUOpenSafetyLineFirst",
- "trigger_cn": "",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_Tcu opens safetychain first=0且DI_TCU opens SafetyLine first=0",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_02_050": {
- "subsystem": "PitchSystem",
- "name": "SC_Axis1BackupMaintenanceRequired",
- "en": "Axis 1 backup maintenance required",
- "cn": "1号超级电容需要维护",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_Backup1MaintenanceRequired",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_Axis1 backup maintenance required=0",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_02_051": {
- "subsystem": "PitchSystem",
- "name": "SC_Axis2BackupMaintenanceRequired",
- "en": "Axis 2 backup maintenance required",
- "cn": "2号超级电容需要维护",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_Backup2MaintenanceRequired",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_Axis2 backup test warning=0",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_02_052": {
- "subsystem": "PitchSystem",
- "name": "SC_Axis3BackupMaintenanceRequired",
- "en": "Axis 3 backup maintenance required",
- "cn": "3号超级电容需要维护",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_Backup3MaintenanceRequired",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_Axis3 backup test error=0",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_02_053": {
- "subsystem": "PitchSystem",
- "name": "SC_Axis1backupTestWarning",
- "en": "Axis 1 backup test warning",
- "cn": "1号超级电容自检报警",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_Backup1Warining",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_Axis2 backup maintenance required=0",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_02_054": {
- "subsystem": "PitchSystem",
- "name": "SC_Axis2backupTestWarning",
- "en": "Axis 2 backup test warning",
- "cn": "2号超级电容自检报警",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_Backup2Warining",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_Axis2 backup test warning=0",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_02_055": {
- "subsystem": "PitchSystem",
- "name": "SC_Axis3backupTestWarning",
- "en": "Axis 3 backup test warning",
- "cn": "3号超级电容自检报警",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_Backup3Warining",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_Axis3 backup test warning=0",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_02_056": {
- "subsystem": "PitchSystem",
- "name": "SC_Axis1backupTestError",
- "en": "Axis 1 backup test error",
- "cn": "1号超级电容自检故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_Backup1Error",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_Axis2 backup test error=0",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "100"
- },
- "04_02_057": {
- "subsystem": "PitchSystem",
- "name": "SC_Axis2backupTestError",
- "en": "Axis 2 backup test error",
- "cn": "2号超级电容自检故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_Backup2Error",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_Axis2 backup test error=0",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "100"
- },
- "04_02_058": {
- "subsystem": "PitchSystem",
- "name": "SC_Axis3backupTestError",
- "en": "Axis 3 backup test error",
- "cn": "3号超级电容自检故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_Backup3Error",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_Axis3 backup test error=0",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "100"
- },
- "04_02_060": {
- "subsystem": "PitchSystem",
- "name": "SC_LubricationFuseError",
- "en": "Lubrication fuse error",
- "cn": "变桨自润滑系统电源故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_LubricationON=0 AND (NOT(gbPitchProfibusDisturbed AND gbPitchCANDisturbed))",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_Lubrication feedback 230V AC circuit breaker=1且通讯正常",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_02_061": {
- "subsystem": "PitchSystem",
- "name": "SC_LubricationSystemFault",
- "en": "Lubrication system fault",
- "cn": "变桨自润滑系统故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_LubricationFault=1 AND (NOT(gbPitchProfibusDisturbed AND gbPitchCANDisturbed))",
- "trigger_cn": "",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_Lubrication feedback Fault=1 且通讯正常",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_02_062": {
- "subsystem": "PitchSystem",
- "name": "SC_LubricationLowLevel",
- "en": "Lubrication low level fault",
- "cn": "变桨自润滑系统低油位故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_LubricationLowLevell=1 AND (NOT(gbPitchProfibusDisturbed AND gbPitchCANDisturbed))",
- "trigger_cn": "",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_Lubrication feedback Low Level=1 且通讯正常",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_02_063": {
- "subsystem": "PitchSystem",
- "name": "SC_PitchHeatingMode",
- "en": "Pitch system is in heating up",
- "cn": "变桨系统处于低温预加热模式",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "当检测到所有的轴控柜温度,电容温度,+LBA温度及电机温度小于-20摄氏度时,显示此信息。",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "当所有的变桨柜温度,电容温度,+LBA柜温度,电机温度都大于-20摄氏度时,该信息可以复位。",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "30-待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "30",
- "brake_state_design": "0"
- },
- "04_02_064": {
- "subsystem": "PitchSystem",
- "name": "SC_PitchMasterAxis1error",
- "en": "PitchMaster axis 1 error",
- "cn": "1号桨叶的PM出现故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_Master1Error",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_PitchMaster axis 1 error=0",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "198"
- },
- "04_02_065": {
- "subsystem": "PitchSystem",
- "name": "SC_PitchMasterAxis2error",
- "en": "PitchMaster axis 2 error",
- "cn": "2号桨叶的PM出现故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_Master2Error",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_PitchMaster axis 2 error=0",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "198"
- },
- "04_02_066": {
- "subsystem": "PitchSystem",
- "name": "SC_PitchMasterAxis3error",
- "en": "PitchMaster axis 3 error",
- "cn": "3号桨叶的PM出现故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_Master3Error",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_PitchMaster axis 3 error=0",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "198"
- },
- "04_02_067": {
- "subsystem": "PitchSystem",
- "name": "SC_CommunicationErrorPitchMasterAxis1",
- "en": "Communication error PitchMaster axis 1",
- "cn": "1号桨叶的PM出现通讯故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_Master1CommunicationError",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_Communication error PitchMaster axis 1=0",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "198"
- },
- "04_02_068": {
- "subsystem": "PitchSystem",
- "name": "SC_CommunicationErrorPitchMasterAxis2",
- "en": "Communication error PitchMaster axis 2",
- "cn": "2号桨叶的PM出现通讯故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_Master2CommunicationError",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_Communication error PitchMaster axis 2=0",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "198"
- },
- "04_02_069": {
- "subsystem": "PitchSystem",
- "name": "SC_CommunicationErrorPitchMasterAxis3",
- "en": "Communication error PitchMaster axis 3",
- "cn": "3号桨叶的PM出现通讯故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_Master3CommunicationError",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_Communication error PitchMaster axis 3=0",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "198"
- },
- "04_02_070": {
- "subsystem": "PitchSystem",
- "name": "SC_CommunicationErrorTCU",
- "en": "Communication error TCU",
- "cn": "变桨系统与主控的通讯出现故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_TCU_PCUCommunicationError",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_Communication error TCU=0",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "198"
- },
- "04_02_071": {
- "subsystem": "PitchSystem",
- "name": "SC_SafetyLineTCUOpen",
- "en": "SafetyLine TCU open",
- "cn": "主控断开了EFC信号故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_TCUOpenSafetyLine",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_SafetyLine TCU open=0",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "198"
- },
- "04_02_072": {
- "subsystem": "PitchSystem",
- "name": "SC_PCUOpensSafetyLineFirst",
- "en": "PCU opens SafetyLine first",
- "cn": "变桨系统先断开EFC信号",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_PCUOpenSafetyLineFirst",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_PCU opens SafetyLine first=0",
- "reset_mode": "M",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_02_073": {
- "subsystem": "PitchSystem",
- "name": "SC_EmmergencyModeCommandFromTCUViaFieldbus",
- "en": "Emmergency mode command from TCU via fieldbus",
- "cn": "主控发出了应急模式命令(信息)",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_EmergencyModeByTCU",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_Emmergency mode command from TCU via fieldbus=0",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_02_074": {
- "subsystem": "PitchSystem",
- "name": "SC_SafetyRunStartedAutonomousByPitchmasterAxis1",
- "en": "SafetyRun started autonomous by Pitchmaster axis 1",
- "cn": "1号桨叶开始自主回桨",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_PM1SafetyRun",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_SafetyRun started autonomous by Pitchmaster axis 1=0",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "198"
- },
- "04_02_075": {
- "subsystem": "PitchSystem",
- "name": "SC_SafetyRunStartedAutonomousByPitchmasterAxis2",
- "en": "SafetyRun started autonomous by Pitchmaster axis 2",
- "cn": "2号桨叶开始自主回桨",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_PM2SafetyRun",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_SafetyRun started autonomous by Pitchmaster axis 2=0",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "198"
- },
- "04_02_076": {
- "subsystem": "PitchSystem",
- "name": "SC_SafetyRunStartedAutonomousByPitchmasterAxis3",
- "en": "SafetyRun started autonomous by Pitchmaster axis 3",
- "cn": "3号桨叶开始自主回桨",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_PM3SafetyRun",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_SafetyRun started autonomous by Pitchmaster axis 3=0",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "198"
- },
- "04_02_077": {
- "subsystem": "PitchSystem",
- "name": "SC_SafetyRunTimeout",
- "en": "SafetyRun timeout",
- "cn": "安全回桨超时故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_SafetyRunTimeout",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_SafetyRun timeout=0",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "198"
- },
- "04_02_078": {
- "subsystem": "PitchSystem",
- "name": "SC_ContactorCyclesGridSupplyAxis",
- "en": "Contactor cycles grid supply axis",
- "cn": "400V进线主接触器2Q1的吸合次数超过了设计寿命报警",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_GridSupplyContactorExpireWarning",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_Contactor cycles grid supply axis=0",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_02_079": {
- "subsystem": "PitchSystem",
- "name": "SC_GridSupplyErrorAxis1",
- "en": "Grid supply error axis 1",
- "cn": "1号桨叶400V电源故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_Blade1GridSupplyError",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "100",
- "reset_en": "",
- "reset_cn": "DI_Grid supply error axis 1=0",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_02_080": {
- "subsystem": "PitchSystem",
- "name": "SC_GridSupplyErrorAxis2",
- "en": "Grid supply error axis 2",
- "cn": "2号桨叶400V电源故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_Blade2GridSupplyError",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "100",
- "reset_en": "",
- "reset_cn": "DI_Grid supply error axis 2=0",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_02_081": {
- "subsystem": "PitchSystem",
- "name": "SC_GridSupplyErrorAxis3",
- "en": "Grid supply error axis 3",
- "cn": "3号桨叶400V电源故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_Blade3GridSupplyError",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "100",
- "reset_en": "",
- "reset_cn": "DI_Grid supply error axis 3=0",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_02_082": {
- "subsystem": "PitchSystem",
- "name": "SC_LVRTError",
- "en": "LVRT error",
- "cn": "LVRT故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_LVRTError",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_LVRT error=0",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "198"
- },
- "04_02_083": {
- "subsystem": "PitchSystem",
- "name": "SC_DClinkFuseErrorAxis1",
- "en": "DC link fuse error axis 1",
- "cn": "1号轴控柜内1F2失效故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_Blade1DCLinkFuseError",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_DC link fuse error axis 1=0",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "198"
- },
- "04_02_084": {
- "subsystem": "PitchSystem",
- "name": "SC_DClinkFuseErrorAxis2",
- "en": "DC link fuse error axis 2",
- "cn": "2号轴控柜内1F2失效故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_Blade2DCLinkFuseError",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_DC link fuse error axis 2=0",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "198"
- },
- "04_02_085": {
- "subsystem": "PitchSystem",
- "name": "SC_DClinkFuseErrorAxis3",
- "en": "DC link fuse error axis 3",
- "cn": "3号轴控柜内1F2失效故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_Blade3DCLinkFuseError",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_DC link fuse error axis 3=0",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "198"
- },
- "04_02_086": {
- "subsystem": "PitchSystem",
- "name": "SC_DiodeMonitoringAxis1",
- "en": "Diode monitoring axis 1",
- "cn": "1号轴控柜内1F1跳开故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_Blade1DiodeError",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_Diode monitoring axis 1=0",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "198"
- },
- "04_02_087": {
- "subsystem": "PitchSystem",
- "name": "SC_DiodeMonitoringAxis2",
- "en": "Diode monitoring axis 2",
- "cn": "1号轴控柜内1F1跳开故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_Blade2DiodeError",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_Diode monitoring axis 2=0",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "198"
- },
- "04_02_088": {
- "subsystem": "PitchSystem",
- "name": "SC_DiodeMonitoringAxis3",
- "en": "Diode monitoring axis 3",
- "cn": "1号轴控柜内1F1跳开故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_Blade3DiodeError",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_Diode monitoring axis 3=0",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "198"
- },
- "04_02_089": {
- "subsystem": "PitchSystem",
- "name": "SC_Mainsupplycontactoropen",
- "en": "Main supply contactor open",
- "cn": "主接触器-2Q1断开",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_LightningProtectionError",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_Lightning protection=0",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "100"
- },
- "04_02_090": {
- "subsystem": "PitchSystem",
- "name": "SC_ErrorChargerAxis1",
- "en": "Error charger axis 1",
- "cn": "1号轴控柜充电故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_Backup1ChargerError",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_Error charger axis 1=0",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_02_091": {
- "subsystem": "PitchSystem",
- "name": "SC_ErrorChargerAxis2",
- "en": "Error charger axis 2",
- "cn": "2号轴控柜充电故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_Backup2ChargerError",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_Error charger axis 2=0",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_02_092": {
- "subsystem": "PitchSystem",
- "name": "SC_ErrorChargerAxis3",
- "en": "Error charger axis 3",
- "cn": "3号轴控柜充电故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_Backup3ChargerError",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_Error charger axis 3=0",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_02_093": {
- "subsystem": "PitchSystem",
- "name": "SC_ErrorHeatingAxis1",
- "en": "Error heating axis 1",
- "cn": "1号轴控柜加热器故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_Axis1HeatingError",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_Error heating axis 1=0",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_02_094": {
- "subsystem": "PitchSystem",
- "name": "SC_ErrorHeatingAxis2",
- "en": "Error heating axis 2",
- "cn": "2号轴控柜加热器故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_Axis2HeatingError",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_Error heating axis 2=0",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_02_095": {
- "subsystem": "PitchSystem",
- "name": "SC_ErrorHeatingAxis3",
- "en": "Error heating axis 3",
- "cn": "3号轴控柜加热器故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_Axis3HeatingError",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_Error heating axis 3=0",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_02_096": {
- "subsystem": "PitchSystem",
- "name": "SC_OvertemperatureBackupBox1",
- "en": "Overtemperature backup box 1",
- "cn": "1号后备电源柜温度过高故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_BackupBox1OverTemp",
- "trigger_cn": "",
- "set_delay": "T#1S",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_Overtemperature backup box 1=0",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_02_097": {
- "subsystem": "PitchSystem",
- "name": "SC_OvertemperatureBackupBox2",
- "en": "Overtemperature backup box 2",
- "cn": "2号后备电源柜温度过高故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_BackupBox2OverTemp",
- "trigger_cn": "",
- "set_delay": "T#1S",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_Overtemperature backup box 2=0",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_02_098": {
- "subsystem": "PitchSystem",
- "name": "SC_OvertemperatureBackupBox3",
- "en": "Overtemperature backup box 3",
- "cn": "3号后备电源柜温度过高故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_BackupBox3OverTemp",
- "trigger_cn": "",
- "set_delay": "T#1S",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_Overtemperature backup box 3=0",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_02_099": {
- "subsystem": "PitchSystem",
- "name": "SC_UndertemperatureBackupBox1",
- "en": "Undertemperature backup box 1",
- "cn": "1号后备电源柜温度过低故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_BackupBox1UnderTemp",
- "trigger_cn": "",
- "set_delay": "T#1S",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_Undertemperature backup box 1=0",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_02_100": {
- "subsystem": "PitchSystem",
- "name": "SC_UndertemperatureBackupBox2",
- "en": "Undertemperature backup box 2",
- "cn": "2号后备电源柜温度过低故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_BackupBox2UnderTemp",
- "trigger_cn": "",
- "set_delay": "T#1S",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_Undertemperature backup box 2=0",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_02_101": {
- "subsystem": "PitchSystem",
- "name": "SC_UndertemperatureBackupBox3",
- "en": "Undertemperature backup box 3",
- "cn": "3号后备电源柜温度过低故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_BackupBox3UnderTemp",
- "trigger_cn": "",
- "set_delay": "T#1S",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_Undertemperature backup box 3=0",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_02_102": {
- "subsystem": "PitchSystem",
- "name": "SC_WireBreakTemperatureAxisBox1",
- "en": "Wire break temperature axis box 1",
- "cn": "1号轴控柜温度传感器断线故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_AxisBox1TempSensorError",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_Wire break temperature axis box 1=0",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_02_103": {
- "subsystem": "PitchSystem",
- "name": "SC_WireBreakTemperatureAxisBox2",
- "en": "Wire break temperature axis box 2",
- "cn": "2号轴控柜温度传感器断线故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_AxisBox2TempSensorError",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_Wire break temperature axis box 2=0",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_02_104": {
- "subsystem": "PitchSystem",
- "name": "SC_WireBreakTemperatureAxisBox3",
- "en": "Wire break temperature axis box 3",
- "cn": "3号轴控柜温度传感器断线故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_AxisBox3TempSensorError",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_Wire break temperature axis box 3=0",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_02_105": {
- "subsystem": "PitchSystem",
- "name": "SC_WireBreakTemperatureBackupBox1",
- "en": "Wire break temperature backup box 1",
- "cn": "1号后备电源柜温度传感器断线故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_BackupBox1TempSensorError",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_Wire break temperature backup box 1=0",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_02_106": {
- "subsystem": "PitchSystem",
- "name": "SC_WireBreakTemperatureBackupBox2",
- "en": "Wire break temperature backup box 2",
- "cn": "2号后备电源柜温度传感器断线故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_BackupBox2TempSensorError",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_Wire break temperature backup box 2=0",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_02_107": {
- "subsystem": "PitchSystem",
- "name": "SC_WireBreakTemperatureBackupBox3",
- "en": "Wire break temperature backup box 3",
- "cn": "3号后备电源柜温度传感器断线故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_BackupBox3TempSensorError",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_Wire break temperature backup box 3=0",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_02_108": {
- "subsystem": "PitchSystem",
- "name": "SC_WireBreakTemperatureMotorAxis1",
- "en": "Wire break temperature motor axis 1",
- "cn": "1号变桨电机温度传感器断线故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_Motor1TempSensorError",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_Wire break temperature motor axis 1=0",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_02_109": {
- "subsystem": "PitchSystem",
- "name": "SC_WireBreakTemperatureMotorAxis2",
- "en": "Wire break temperature motor axis 2",
- "cn": "2号变桨电机温度传感器断线故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_Motor2TempSensorError",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_Wire break temperature motor axis 2=0",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_02_110": {
- "subsystem": "PitchSystem",
- "name": "SC_WireBreakTemperatureMotorAxis3",
- "en": "Wire break temperature motor axis 3",
- "cn": "3号变桨电机温度传感器断线故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_Motor3TempSensorError",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_Wire break temperature motor axis 3=0",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_02_111": {
- "subsystem": "PitchSystem",
- "name": "SC_WireBreakTemperatureHub",
- "en": "Wire break temperature hub",
- "cn": "轮毂温度传感器断线故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_HumTempSensorError",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_Wire break temperature hub=0",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_02_112": {
- "subsystem": "PitchSystem",
- "name": "SC_ErrorFanPitchmasterAxis1",
- "en": "Error fan Pitchmaster axis 1",
- "cn": "1号PM的风扇故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_PM1FanError",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_Error fan Pitchmaster axis 1=0",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_02_113": {
- "subsystem": "PitchSystem",
- "name": "SC_ErrorFanPitchmasterAxis2",
- "en": "Error fan Pitchmaster axis 2",
- "cn": "2号PM的风扇故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_PM2FanError",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_Error fan Pitchmaster axis 2=0",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_02_114": {
- "subsystem": "PitchSystem",
- "name": "SC_ErrorFanPitchmasterAxis3",
- "en": "Error fan Pitchmaster axis 3",
- "cn": "3号PM的风扇故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_PM3FanError",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_Error fan Pitchmaster axis 3=0",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_02_115": {
- "subsystem": "PitchSystem",
- "name": "SC_BackupSwitchopenaxis1",
- "en": "Backup Switch open axis 1",
- "cn": "1号轴控柜超级电容开关-1Q1断开",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_Backup1SwitchOpen",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_BackupSwitchopenaxis 1=0",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "198"
- },
- "04_02_116": {
- "subsystem": "PitchSystem",
- "name": "SC_BackupSwitchopenaxis2",
- "en": "Backup Switch open axis 2",
- "cn": "2号轴控柜超级电容开关-1Q1断开",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_Backup2SwitchOpen",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_BackupSwitchopenaxis 2=0",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "198"
- },
- "04_02_117": {
- "subsystem": "PitchSystem",
- "name": "SC_BackupSwitchopenaxis3",
- "en": "Backup Switch open axis 3",
- "cn": "3号轴控柜超级电容开关-1Q1断开",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_Backup3SwitchOpen",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_BackupSwitchopenaxis 3=0",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "198"
- },
- "04_02_118": {
- "subsystem": "PitchSystem",
- "name": "SC_ContactorCyclesDCSupplyAxis1",
- "en": "Contactor cycles DC supply axis 1",
- "cn": "1号轴控柜内接触器3Q1的吸合次数超过了设计寿命报警",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_AxisBox1ContactorExpireWarning",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_Contactor cycles DC supply axis 1=0",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_02_119": {
- "subsystem": "PitchSystem",
- "name": "SC_ContactorCyclesDCSupplyAxis2",
- "en": "Contactor cycles DC supply axis 2",
- "cn": "2号轴控柜内接触器3Q1的吸合次数超过了设计寿命报警",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_AxisBox2ContactorExpireWarning",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_Contactor cycles DC supply axis 2=0",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_02_120": {
- "subsystem": "PitchSystem",
- "name": "SC_ContactorCyclesDCSupplyAxis3",
- "en": "Contactor cycles DC supply axis 3",
- "cn": "3号轴控柜内接触器3Q1的吸合次数超过了设计寿命报警",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_AxisBox3ContactorExpireWarning",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_Contactor cycles DC supply axis 3=0",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_02_123": {
- "subsystem": "PitchSystem",
- "name": "SC_OvertemperatureLBA",
- "en": "Overtemperature center box",
- "cn": "中心柜温度过高故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_CenterBoxOverTemp",
- "trigger_cn": "",
- "set_delay": "T#1S",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_Overtemperature center box(TxPDO8 Byte4.0/Byte60.0 )",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_02_124": {
- "subsystem": "PitchSystem",
- "name": "SC_UndertemperatureLBA",
- "en": "Undertemperature center box",
- "cn": "中心柜温度过低故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_CenterBoxUnderTemp",
- "trigger_cn": "",
- "set_delay": "T#1S",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_Undertemperature center box(TxPDO8 Byte4.1/Byte60.1 )",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_02_125": {
- "subsystem": "PitchSystem",
- "name": "SC_WireBreakTemperatureLBA",
- "en": "Wirebreak temperature sensor center box",
- "cn": "中心柜温度传感器断线故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_CenterBoxTempSensorError",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_Wirebreak temperature sensor center box(TxPDO8 Byte4.2/Byte60.2 )",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_02_126": {
- "subsystem": "PitchSystem",
- "name": "SC_OvertemperatureHub",
- "en": "Overtemperature hub",
- "cn": "轮毂温度过高警告",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_HubOverTemp",
- "trigger_cn": "",
- "set_delay": "T#1S",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_Overtemperature hub(TxPDO8 Byte4.3/Byte60.3 )",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_02_127": {
- "subsystem": "PitchSystem",
- "name": "SC_UndertemperatureHub",
- "en": "Undertemperature hub",
- "cn": "轮毂温度过低警告",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_HubUnderTemp",
- "trigger_cn": "",
- "set_delay": "T#1S",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_Undertemperature hub(TxPDO8 Byte4.4/Byte60.4 )",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_02_128": {
- "subsystem": "PitchSystem",
- "name": "SC_HVRTdetected",
- "en": "HVRT detected",
- "cn": "HVRT level1 警告",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_HVRTLevel1",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_HVRT detected(TxPDO8 Byte4.5/Byte60.5 )",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_02_129": {
- "subsystem": "PitchSystem",
- "name": "SC_HVRTLevel2detected",
- "en": "HVRT Level 2 detected",
- "cn": "HVRT level2 警告",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_HVRTLevel2",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_HVRT Level 2 detected(TxPDO8 Byte4.6/Byte60.6 )",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_02_130": {
- "subsystem": "PitchSystem",
- "name": "SC_HVRTLevel2toolong",
- "en": "HVRT Level 2 too long",
- "cn": "HVRT 故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_PITCH_HVRTError",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "DI_HVRT Level 2 too long(TxPDO8 Byte4.7/Byte60.7 )",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "100"
- },
- "04_02_131": {
- "subsystem": "PitchSystem",
- "name": "SC_PitchInReboot",
- "en": "Pitch is In Reboot",
- "cn": "远程重启变桨系统",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "gbPitchSystemInReboot",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "True",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_02_053": {
- "subsystem": "NacelleSystem",
- "name": "SC_FaultInputPT100_Nacelle",
- "en": "PT100 for nacelle has fault",
- "cn": "机舱温度测量PT100传感器故障",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Bit 6 from the status byte from the nacelle PT100 input becomes TRUE.(giStatePT100_TempNacelle.6=1)",
- "trigger_cn": "机舱PT100传感器输入的状态字节第6位是TRUE或机舱控制柜10min平均温度不在[-100,500]之间。(giStatePT100_TempNacelle.6=1 OR (grTempNacelle_10min >500 OR grTempNacelle_10min <-100))",
- "set_delay": "T#5s",
- "yp": "0",
- "reset_en": "Bit 6 from the status byte from the nacelle PT100 input becomes FALSE.(giStatePT100_TempNacelle.6=0)",
- "reset_cn": "机舱PT100传感器输入的状态字节第6位是FALSE且机舱10min平均温度在[-100,500]之间。(giStatePT100_TempNacelle.6=0 AND (grTempNacelle_10min <500 AND grTempNacelle_10min >-100)",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_02_077": {
- "subsystem": "NacelleSystem",
- "name": "SC_FaultInputPT100_Outdoor",
- "en": "PT100 for outdoor temperature has fault",
- "cn": "舱外环境温度测量PT100传感器故障",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Bit 6 from the status byte from the outdoor temperature PT100 input becomes TRUE.(giStatePT100_TempOutdoor.6=1)",
- "trigger_cn": "舱外PT100传感器输入的状态字节第6位是TRUE或舱外1min平均温度不在[-100,500]范围内。。(giStatePT100_TempOutdoor.6=1 OR (grTempOutdoor_10min >500 OR grTempOutdoor_10min<-100))",
- "set_delay": "T#5s",
- "yp": "0",
- "reset_en": "Bit 6 from the status byte from the outdoor temperature PT100 input becomes FALSE.(giStatePT100_TempOutdoor.6=0)",
- "reset_cn": "舱外PT100传感器输入的状态字节第6位是FALSE且舱外1min平均温度在[-100,500]范围内。。(giStatePT100_TempOutdoor.6=0 AND(grTempOutdoor_10min <500 AND grTempOutdoor_10min>-100))",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_02_089": {
- "subsystem": "NacelleSystem",
- "name": "SC_FaultAI_SensorWindDirection",
- "en": "Wind direction sensor has fault",
- "cn": "风向标故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Bit 6 from the Wind direction input becomes TRUE.(giStateAIWindDirection.6=1)",
- "trigger_cn": "风向传感器输入的状态字节第6位是TRUE。(giStateAIWindDirection.6=1)",
- "set_delay": "T#5s",
- "yp": "100",
- "reset_en": "Bit 6 from the Wind direction input becomes FALSE.(giStateAIWindDirection.6=0)",
- "reset_cn": "风向传感器输入的状态字节第6位是FALSE。(giStateAIWindDirection.6=0)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_02_111": {
- "subsystem": "NacelleSystem",
- "name": "OC_HeaterWindSensors_ON",
- "en": "Heater for wind sensors is set to on",
- "cn": "风速仪和风向标的加热器开启",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "PLC output for controlling the wind sensors heater becomes TRUE.(DQ_NacelleHeaterWindSensors=1)",
- "trigger_cn": "PLC控制风速风向传感器的输出为TRUE。(DQ_NacelleHeaterWindSensors=1)",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "PLC output for controlling the wind sensors heater becomes FALSE.(DQ_NacelleHeaterWindSensors=0)",
- "reset_cn": "PLC控制风速风向传感器的输出为FALSE。(DQ_NacelleHeaterWindSensors=0 AND bSpecResCond=1)",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "02_03_001": {
- "subsystem": "NacelleSystem",
- "name": "SC_TempNacelle_high",
- "en": "Nacelle temperature is too high",
- "cn": "机舱温度过高警告",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "3",
- "repeat_period": "T#24h",
- "trigger_en": "The 10min-mean-value of the temperature exceeds the value given by parameter.(grTempNacelle_10min >PAR_rTempHigh_Nacelle)",
- "trigger_cn": "机舱10分钟平均温度高于设定值。(grTempNacelle_10min >PAR_rTempHigh_Nacelle)",
- "set_delay": "T#1m",
- "yp": "0",
- "reset_en": "The 10min-mean-value of temperature falls below the value given by parameter minus a hysteresis value OR get reset signal of status code coming from Nacelle, Tower or Remote Command.(grTempNacelle_10min <(PAR_rTempHigh_Nacelle - PAR_rTempHysteresisUpperTemp) OR gbMAIN_ResetStatusCodes=1) AND bSpecResCond=1",
- "reset_cn": "机舱温度(10分钟平均值)小于设定值减去一个滞后值或收到reset信号。(grTempNacelle_10min <(PAR_rTempHigh_Nacelle - PAR_rTempHysteresisUpperTemp) OR gbMAIN_ResetStatusCodes=1) AND bSpecResCond=1",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_03_002": {
- "subsystem": "NacelleSystem",
- "name": "SC_TempNacelle_low",
- "en": "Nacelle temperature is too low",
- "cn": "机舱温度过低警告",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "3",
- "repeat_period": "T#24h",
- "trigger_en": "The 10min-mean-value of the temperature falls below the value given by parameter.(grTempNacelle_10min < PAR_rTempLow_Nacelle)",
- "trigger_cn": "机舱10分钟平均温度低于设定值。(grTempNacelle_10min < PAR_rTempLow_Nacelle)",
- "set_delay": "T#1m",
- "yp": "0",
- "reset_en": "The 10min-mean-value of temperature increases above the value given by parameter plus a hysteresis value OR get reset signal of status code coming from Nacelle, Tower or Remote Command.(grTempNacelle_10min > (PAR_rTempLow_Nacelle + PAR_rTempHysteresisLowerTemp) OR gbMAIN_ResetStatusCodes) AND bSpecResCond=1",
- "reset_cn": "机舱温度(10分钟平均值)大于设定值加上一个滞后值或收到reset信号。(grTempNacelle_10min > (PAR_rTempLow_Nacelle + PAR_rTempHysteresisLowerTemp) OR gbMAIN_ResetStatusCodes) AND bSpecResCond=1",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_03_003": {
- "subsystem": "NacelleSystem",
- "name": "SC_TempNacelle_max",
- "en": "Nacelle temperature exceeds maximum value",
- "cn": "机舱温度过高故障",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The 10min-mean-value of the temperature exceeds the maximum value.(grTempNacelle_10min > PAR_rTempMAX_Nacelle)",
- "trigger_cn": "机舱10分钟平均温度高于最大值。(grTempNacelle_10min > PAR_rTempMAX_Nacelle)",
- "set_delay": "T#1m",
- "yp": "0",
- "reset_en": "The 10min-mean-value of temperature falls below the value given by parameter minus a hysteresis value OR get reset signal of status code coming from Nacelle, Tower or Remote Command.(grTempNacelle_10min < (PAR_rTempMAX_Nacelle - PAR_rTempHysteresisUpperTemp) OR gbMAIN_ResetStatusCodes)AND bSpecResCond=1",
- "reset_cn": "机舱温度(10分钟平均值)小于最大值减去一个滞后值或收到reset信号。(grTempNacelle_10min < (PAR_rTempMAX_Nacelle - PAR_rTempHysteresisUpperTemp) OR gbMAIN_ResetStatusCodes)AND bSpecResCond=1",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_03_004": {
- "subsystem": "NacelleSystem",
- "name": "SC_TempNacelle_min",
- "en": "Nacelle temperature exceeds minimum value",
- "cn": "机舱温度过低故障",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The 10min-mean-value of the temperature falls below the minimum value.(grTempNacelle_10min < PAR_rTempMIN_Nacelle)",
- "trigger_cn": "机舱10分钟平均温度低于最小值。(grTempNacelle_10min < PAR_rTempMIN_Nacelle)",
- "set_delay": "T#1m",
- "yp": "0",
- "reset_en": "The 10min-mean-value of temperature increases above the value given by parameter plus a hysteresis value OR get reset signal of status code coming from Nacelle, Tower or Remote Command.(grTempNacelle_10min > (PAR_rTempMIN_Nacelle + PAR_rTempHysteresisLowerTemp) OR gbMAIN_ResetStatusCodes) AND bSpecResCond=1",
- "reset_cn": "机舱温度(10分钟平均值)大于最小值加上一个滞后值或收到reset信号。(grTempNacelle_10min > (PAR_rTempMIN_Nacelle + PAR_rTempHysteresisLowerTemp) OR gbMAIN_ResetStatusCodes) AND bSpecResCond=1",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "50"
- },
- "02_03_005": {
- "subsystem": "NacelleSystem",
- "name": "SC_RepFaultTempNacelle",
- "en": "The faults, nacelle temperature is too high or too low, have repeated.",
- "cn": "机舱温度过高或过低警告重复出现",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The faults, nacelle temperature is too high or too low, have repeated.(gbRepeat_02_03_001=1 OR gbRepeat_02_03_002=1)",
- "trigger_cn": "机舱温度过低或过高故障重复出现。(gbRepeat_02_03_001=1 OR gbRepeat_02_03_002=1)",
- "set_delay": "T#1m",
- "yp": "0",
- "reset_en": "The faults, nacelle temperature is too high or too low, have not repeated.(gbRepeat_02_03_001=1 OR gbRepeat_02_03_002=1)",
- "reset_cn": "机舱温度过低和过高故障重复出现情况消除。(gbRepeat_02_03_001=0 AND gbRepeat_02_03_002=0)",
- "reset_mode": "M",
- "type": "A",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_04_018": {
- "subsystem": "NacelleSystem",
- "name": "SC_VibrationOmniDirectionLevel1",
- "en": "Tower omni directional acceleration exceeds the level1 omni directional vibration limit",
- "cn": "塔架水平方向的加速度高于1级振动门限值",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "3",
- "repeat_period": "T#1h",
- "trigger_en": "TurbineOperationMode is greater than startmode, delayed by 5s after selftest4, the current value for vibration (square root from Y-direction and Z-direction) exceeds the the level1 omni directional vibration limit.(giTurbineOperationMode > CON_iStartMode AND grFilteredVibrationOmniDirection_PCH > PAR_rAccelLimit1OmniDirection)",
- "trigger_cn": "风机运行大于启动模式,并在自检4后延时5s,塔架水平合方向的加速度高于1级水平合方向振动门限值。(giTurbineOperationMode > CON_iStartMode AND grFilteredVibrationOmniDirection_PCH > PAR_rAccelLimit1OmniDirection)",
- "set_delay": "T#2s",
- "yp": "0",
- "reset_en": "TurbineOperationMode is less than startmode, the current value for vibration (square root from Y-direction and Z-direction) is below the the level1 omni directional vibration limit.(giTurbineOperationMode > CON_iStartMode AND grFilteredVibrationOmniDirection_PCH > PAR_rAccelLimit1OmniDirection)",
- "reset_cn": "风机运行小于等于启动模式,塔架水平合方向的加速度低于1级水平合方向振动门限值。(giTurbineOperationMode > CON_iStartMode AND grFilteredVibrationOmniDirection_PCH > PAR_rAccelLimit1OmniDirection)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "51"
- },
- "02_04_019": {
- "subsystem": "NacelleSystem",
- "name": "SC_VibrationOmniDirectionLevel2",
- "en": "Tower omni directional acceleration exceeds the level2 omni directional vibration limit",
- "cn": "塔架水平方向的加速度高于2级振动门限值",
- "powerup_delay": "T#0s",
- "disable_level": "51",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "TurbineOperationMode is greater than startmode, delayed by 5s after selftest4, the current value for vibration (square root from Y-direction and Z-direction) exceeds the the level2 omni directional vibration limit.(giTurbineOperationMode > CON_iStartMode AND grFilteredVibrationOmniDirection_PCH > PAR_rAccelLimit1OmniDirection)",
- "trigger_cn": "风机运行大于启动模式,并在自检4后延时5s,塔架水平合方向的加速度高于2级水平合方向振动门限值。(giTurbineOperationMode > CON_iStartMode AND grFilteredVibrationOmniDirection_PCH > PAR_rAccelLimit1OmniDirection)",
- "set_delay": "T#2s",
- "yp": "0",
- "reset_en": "TurbineOperationMode is less than startmode, the current value for vibration (square root from Y-direction and Z-direction) is below the the level2 omni directional vibration limit.(giTurbineOperationMode > CON_iStartMode AND grFilteredVibrationOmniDirection_PCH > PAR_rAccelLimit1OmniDirection)",
- "reset_cn": "风机运行小于等于启动模式,塔架水平合方向的加速度低于2级水平合方向振动门限值。(giTurbineOperationMode > CON_iStartMode AND grFilteredVibrationOmniDirection_PCH > PAR_rAccelLimit1OmniDirection)",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "100"
- },
- "02_04_020": {
- "subsystem": "NacelleSystem",
- "name": "SC_RepFaultVibrationYAxis",
- "en": "The fault of tower omni directional level1 vibration has repeated",
- "cn": "阵风过大保护性停机",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The statuscode for \"SC_VibrationOmniDirectionLevel1\" in a given time periode becomes more times TRUE than allowed maximum number.(gbRepeat_02_04_018=1)",
- "trigger_cn": "塔架水平合方向1级振动故障(SC_VibrationOmniDirectionLevel1)重复出现。(gbRepeat_02_04_018=1)",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "The statuscode for \"SC_VibrationOmniDirectionLevel1\" in a given time periode becomes less times TRUE than allowed maximum number.(gbRepeat_02_04_018=0)",
- "reset_cn": "塔架水平合方向1级振动故障不重复出现。(gbRepeat_02_04_018=0)",
- "reset_mode": "M",
- "type": "A",
- "alarm": "True",
- "level": "139-大风停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "139",
- "brake_state_design": "51"
- },
- "02_04_021": {
- "subsystem": "NacelleSystem",
- "name": "SC_VibrationForeaftDirection1",
- "en": "Tower fore-aft directional acceleration exceeds the level1 fore-aft directional vibration limit",
- "cn": "塔架前后方向的加速度高于1级振动门限值",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "3",
- "repeat_period": "T#1h",
- "trigger_en": "TurbineOperationMode is greater than start mode, delayed by 5s after Selftest4, the current value for vibration (square root from Y-direction and Z-direction) exceeds the the level1 fore-aft directional vibration limit.(giBPLevel <= CON_iBrakeProgram_50 AND giTurbineOperationMode <> CON_iSelftest4 AND grFilteredVibrationForeaftDirection_PCH > PAR_rAccelLimit1ForeaftDirection)",
- "trigger_cn": "风机大于启动模式,自检4后延时5s,塔架前后振动方向的加速度高于1级前后方向振动门限值。( giTurbineOperationMode >= CON_iStartMode AND grFilteredVibrationForeaftDirection_PCH > PAR_rAccelLimit1ForeaftDirection)",
- "set_delay": "T#2s",
- "yp": "0",
- "reset_en": "TurbineOperationMode is less than start mode, or seltfest is finished less than 5 seconds or the current value for vibration (square root from Y-direction and Z-direction) falls below the the level1 fore-aft directional vibration limit.",
- "reset_cn": "风机运行小于启动模式,或自检4结束后延时不到5s,或塔架前后振动方向的加速度不高于1级前后方向振动门限值。(giBPLevel <= CON_iBrakeProgram_50 OR giTurbineOperationMode ≠ CON_iSelftest4 OR grFilteredVibrationForeaftDirection_PCH <= PAR_rAccelLimit1ForeaftDirection) AND bSpecResCond=1",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "30-待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "30",
- "brake_state_design": "0"
- },
- "02_04_022": {
- "subsystem": "NacelleSystem",
- "name": "SC_VibrationForeaftDirection2",
- "en": "Tower fore-aft directional acceleration exceeds the level2 fore-aft directional vibration limit",
- "cn": "塔架前后方向的加速度高于2级振动门限值",
- "powerup_delay": "T#0s",
- "disable_level": "50",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "TurbineOperationMode is greater than start mode, delayed by 5s after Selftest4, the current value for vibration (square root from Y-direction and Z-direction) exceeds the the level2 fore-aft directional vibration limit.(giBPLevel <= CON_iBrakeProgram_50 AND giTurbineOperationMode <> CON_iSelftest4 AND grFilteredVibrationForeaftDirection_PCH > PAR_rAccelLimit2ForeaftDirection)",
- "trigger_cn": "风机大于启动模式,自检4后延时5s,塔架前后振动方向的加速度高于2级前后方向振动门限值。(giTurbineOperationMode >= CON_iStartMode AND grFilteredVibrationForeaftDirection_PCH > PAR_rAccelLimit2ForeaftDirection)",
- "set_delay": "T#2s",
- "yp": "0",
- "reset_en": "TurbineOperationMode is greater than start mode, or the current value for vibration (square root from Y-direction and Z-direction) falls below the the level2 omni directional vibration limit.(giTurbineOperationMode < CON_iStartMode OR grFilteredVibrationForeaftDirection_PCH <= PAR_rAccelLimit2ForeaftDirection)",
- "reset_cn": "风机运行小于启动模式,或塔架前后振动方向的加速度不高于2级前后方向振动门限值。(giBPLevel > CON_iBrakeProgram_50 OR giTurbineOperationMode = CON_iSelftest4 OR grFilteredVibrationForeaftDirection_PCH <= PAR_rAccelLimit2ForeaftDirection)",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "100"
- },
- "02_04_023": {
- "subsystem": "NacelleSystem",
- "name": "SC_RepFaultVibrationZAxis",
- "en": "The fault of tower fore-aft directional level1 vibration has repeated",
- "cn": "阵风过大保护性停机",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The statuscode for \"SC_VibrationForeaftDirection1\" in a given time periode becomes more times TRUE than allowed maximum number。(gbRepeat_02_04_021=1)",
- "trigger_cn": "塔架前后方向1级振动(SC_VibrationForeaftDirection1)故障重复出现。(gbRepeat_02_04_021=1)",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "The statuscode for \"SC_VibrationForeaftDirection1\" in a given time periode becomes less times TRUE than allowed maximum number。(gbRepeat_02_04_021=0)",
- "reset_cn": "塔架前后方向1级振动故障不重复出现。(gbRepeat_02_04_021=0)",
- "reset_mode": "M",
- "type": "A",
- "alarm": "True",
- "level": "139-大风停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "139",
- "brake_state_design": "51"
- },
- "02_04_024": {
- "subsystem": "NacelleSystem",
- "name": "OC_VibrationOmniDirection",
- "en": "PCH Vibration in OmniDirecetion over limit",
- "cn": "塔架水平方向的加速度超限",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "PCH Vibration in OmniDirection exceeds limit.(grFilteredVibrationOmniDirection_PCH > PAR_rVibrationOmniDirection)",
- "trigger_cn": "左右方向PCH振动数据超限。grFilteredVibrationOmniDirection_PCH > PAR_rVibrationOmniDirection",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "PCH Vibration in OmniDirection doesnet exceed limit.(grFilteredVibrationOmniDirection_PCH <= PAR_rVibrationOmniDirection)",
- "reset_cn": "左右方向PCH振动数据未超限。grFilteredVibrationOmniDirection_PCH <= PAR_rVibrationOmniDirection",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "30-待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "30",
- "brake_state_design": "0"
- },
- "02_04_025": {
- "subsystem": "NacelleSystem",
- "name": "OC_VibrationForeaftDirection",
- "en": "PCH Vibration in ForeaftDirecetion over limit",
- "cn": "塔架前后方向的加速度超限",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "PCH Vibration in ForeaftDirection exceeds limit.(grFilteredVibrationForeaftDirection_PCH > PAR_rVibrationForeaftDirection)",
- "trigger_cn": "前后方向PCH振动数据超限。grFilteredVibrationForeaftDirection_PCH > PAR_rVibrationForeaftDirection",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "PCH Vibration in ForeaftDirection doesnet exceed limit.(grFilteredVibrationForeaftDirection_PCH <= PAR_rVibrationForeaftDirection)",
- "reset_cn": "前后方向PCH振动数据未超限。grFilteredVibrationForeaftction_PCH <= PAR_rVibrationForeaftDirection",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "30-待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "30",
- "brake_state_design": "0"
- },
- "02_10_111": {
- "subsystem": "NacelleSystem",
- "name": "SC_BlockYawForVibrationHigh",
- "en": "forbidden yaw for Foreaft Vibration High",
- "cn": "前后方向振动值过大禁止偏航一分钟",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "前后方向振动值过大禁止偏航一分钟",
- "set_delay": "T#0s",
- "yp": "100",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "02_11_001": {
- "subsystem": "NacelleSystem",
- "name": "SC_ConstantSignalVane1",
- "en": "Wind vane1 is stuck",
- "cn": "风向标静止不动",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "There is no change in the signal (100ms mean value) for vane direction for a time periode given by the initial values for this Statuscode and monitoring wind sensors is not forbidden. (gbDetectNew100ms=1 AND iLastDirVane1Relative_100ms = iCurrDirVane1Relative_100ms)AND OC_NoMonitoringWindSensors = False",
- "trigger_cn": "并未禁止掉与风向风速传感器相关的SC,检测到新的风向,但100ms前后风向没有改变(gbDetectNew100ms=1 AND iLastDirVane1Relative_100ms = iCurrDirVane1Relative_100ms)AND OC_NoMonitoringWindSensors = False",
- "set_delay": "T#100ms",
- "yp": "100",
- "reset_en": "There is a change in the signal (100ms mean value) for vane direction for a time periode given by the initial values for this Statuscode, OR the wind speed (10 min mean value) will be less than a minimum value given by parameter, or monitoring wind sensors is forbidden(gbDetectNew100ms=0 OR iLastDirVane1Relative_100ms ≠ iCurrDirVane1Relative_100ms OR OC_NoMonitoringWindSensors = 1) OR OC_NoMonitoringWindSensors =TRUE",
- "reset_cn": "检测不到新的风向,或100ms前后风向有改变或10分钟平均风速低于最小值 或者禁用风速风向传感器相关故障字。(gbDetectNew100ms=0 OR iLastDirVane1Relative_100ms ≠ iCurrDirVane1Relative_100ms OR OC_NoMonitoringWindSensors = 1)OR OC_NoMonitoringWindSensors =TRUE",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_11_008": {
- "subsystem": "NacelleSystem",
- "name": "SC_ConstantSignalAnemometer1",
- "en": "Wind anemometer is stuck",
- "cn": "风速仪静止不动",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "There is no change in the signal (100ms mean value) for wind speed for a time periode given by the initial values for this Statuscode and monitoring wind sensors is not forbidden.(gbDetectNew100ms=1 AND iLastWindSpeed_100msMUL10 = iWindSpeed_100msMUL10)AND OC_NoMonitoringWindSensors = False_x000D_",
- "trigger_cn": "并未禁止掉与风向风速传感器相关的SC,,检测到新的风速,但100ms前后风速没有改变。(gbDetectNew100ms=1 AND iLastWindSpeed_100msMUL10 = iWindSpeed_100msMUL10)AND OC_NoMonitoringWindSensors = False",
- "set_delay": "T#1m",
- "yp": "0",
- "reset_en": "There is a change in the signal (100ms mean value) for wind speed for a time periode given by the initial values for this Statuscode, OR the wind speed (10 min mean value) will be less than a minimum value given by parameter,or monitoring wind sensors is forbidden.(gbDetectNew100ms=0 OR iLastWindSpeed_100msMUL10 ≠ iWindSpeed_100msMUL10 OR OC_NoMonitoringWindSensors = 1)OR OC_NoMonitoringWindSensors =TRUE",
- "reset_cn": "检测不到新的风速,或100ms前后风速有改变或10分钟平均风速低于最小值或者禁用风速风向传感器相关故障字。。(gbDetectNew100ms=0 OR iLastWindSpeed_100msMUL10 ≠ iWindSpeed_100msMUL10 OR OC_NoMonitoringWindSensors = 1)OR OC_NoMonitoringWindSensors =TRUE",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_11_009": {
- "subsystem": "NacelleSystem",
- "name": "OC_ConstantWindVaneReadings",
- "en": "Wind vane1 reading is constant",
- "cn": "风向标读数不变",
- "powerup_delay": "T#5m",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "There is no change in the signal (100ms mean value) for vane direction for a time periode given by the initial values for this Statuscode and monitoring wind sensors is not forbidden. (gbDetectNew100ms=1 AND iLastDirVane1Relative_100ms = iCurrDirVane1Relative_100ms)AND OC_NoMonitoringWindSensors = False",
- "trigger_cn": "并未禁止掉与风向风速传感器相关的SC,检测到新的风向,但100ms前后风向没有改变(gbDetectNew100ms=1 AND iLastDirVane1Relative_100ms = iCurrDirVane1Relative_100ms)AND OC_NoMonitoringWindSensors = False",
- "set_delay": "T#20s",
- "yp": "100",
- "reset_en": "There is a change in the signal (100ms mean value) for vane direction for a time periode given by the initial values for this Statuscode, OR the wind speed (10 min mean value) will be less than a minimum value given by parameter, or monitoring wind sensors is forbidden(gbDetectNew100ms=0 OR iLastDirVane1Relative_100ms ≠ iCurrDirVane1Relative_100ms OR OC_NoMonitoringWindSensors = 1) OR OC_NoMonitoringWindSensors =TRUE",
- "reset_cn": "检测不到新的风向,或100ms前后风向有改变或10分钟平均风速低于最小值 或者禁用风速风向传感器相关故障字。(gbDetectNew100ms=0 OR iLastDirVane1Relative_100ms ≠ iCurrDirVane1Relative_100ms OR OC_NoMonitoringWindSensors = 1)OR OC_NoMonitoringWindSensors =TRUE",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_11_010": {
- "subsystem": "NacelleSystem",
- "name": "OC_RestartWindVane",
- "en": "Restart WindVane",
- "cn": "重启风向标",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "2",
- "repeat_period": "T#1m",
- "trigger_en": "IF gbDQ_RestartWindVane THEN SC=TRUE_x000D_",
- "trigger_cn": "当gbDQ_RestartWindVane_x000D_ 置1时,则触发_x000D_",
- "set_delay": "T#0s",
- "yp": "100",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_11_016": {
- "subsystem": "NacelleSystem",
- "name": "SC_TempOutdoor_high",
- "en": "Outdoor temperature is too high",
- "cn": "舱外环境温度过高警告",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "3",
- "repeat_period": "T#24h",
- "trigger_en": "The 10min-mean-value of the temperature exceeds the value given by parameter.(grTempOutdoor_10min >PAR_rTempHigh_Outdoor)",
- "trigger_cn": "室外温度10分钟平均值高于设定值。(grTempOutdoor_10min >PAR_rTempHigh_Outdoor)",
- "set_delay": "T#1m",
- "yp": "0",
- "reset_en": "The 10min-mean-value of temperature falls below the value given by parameter minus a hysteresis value OR get reset signal of status code coming from Nacelle, Tower or Remote Command.((grTempOutdoor_10min <(PAR_rTempHigh_Outdoor - PAR_rTempHysteresisUpperTemp)) OR gbMAIN_ResetStatusCodes=1)",
- "reset_cn": "室外温度(10分钟平均值)小于设定值减去一个滞后值或收到reset信号。((grTempOutdoor_10min <(PAR_rTempHigh_Outdoor - PAR_rTempHysteresisUpperTemp)) OR gbMAIN_ResetStatusCodes=1)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_11_017": {
- "subsystem": "NacelleSystem",
- "name": "SC_TempOutdoor_low",
- "en": "Outdoor temperature is too low",
- "cn": "舱外环境温度过低警告",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "3",
- "repeat_period": "T#24h",
- "trigger_en": "The 10min-mean-value of the temperature falls below the value given by parameter.(grTempOutdoor_10min <PAR_rTempLow_Outdoor)",
- "trigger_cn": "室外10分钟平均温度低于设定值。(grTempOutdoor_10min <PAR_rTempLow_Outdoor)",
- "set_delay": "T#1m",
- "yp": "0",
- "reset_en": "The 10min-mean-value of temperature increases above the value given by parameter plus a hysteresis value OR get reset signal of status code coming from Nacelle, Tower or Remote Command. ((grTempOutdoor_10min >(PAR_rTempLow_Outdoor + PAR_rTempHysteresisLowerTemp)) OR gbMAIN_ResetStatusCodes=1)",
- "reset_cn": "室外温度(10分钟平均值)大于设定值加上一个滞后值或收到reset信号。((grTempOutdoor_10min >(PAR_rTempLow_Outdoor + PAR_rTempHysteresisLowerTemp)) OR gbMAIN_ResetStatusCodes=1)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_11_018": {
- "subsystem": "NacelleSystem",
- "name": "SC_TempOutdoor_MAX",
- "en": "Outdoor temperature exceeds maximum limit",
- "cn": "舱外环境温度过高故障",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The 10min-mean-value of the temperature exceeds the maximum limit value given by parameter.(grTempOutdoor_10min > PAR_rTempMAX_Outdoor)",
- "trigger_cn": "室外10分钟平均温度高于上限值。(grTempOutdoor_10min > PAR_rTempMAX_Outdoor)",
- "set_delay": "T#1m",
- "yp": "0",
- "reset_en": "The 10min-mean-value of temperature falls below the value given by parameter minus a hysteresis value OR get reset signal of status code coming from Nacelle, Tower or Remote Command.(grTempOutdoor_10min < (PAR_rTempMAX_Outdoor - PAR_rTempHysteresisUpperTemp) OR gbMAIN_ResetStatusCodes=1)",
- "reset_cn": "室外温度(10分钟平均值)小于最大值减去一个滞后值或收到reset信号。(grTempOutdoor_10min < (PAR_rTempMAX_Outdoor - PAR_rTempHysteresisUpperTemp) OR gbMAIN_ResetStatusCodes=1)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "159-环境温度停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "159",
- "brake_state_design": "51"
- },
- "02_11_019": {
- "subsystem": "NacelleSystem",
- "name": "SC_TempOutdoor_MIN",
- "en": "Outdoor temperature exceeds minimum limit",
- "cn": "舱外环境温度过低故障",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The 10min-mean-value of the temperature falls below the minimum limit.(grTempOutdoor_10min <PAR_rTempMIN_Outdoor)",
- "trigger_cn": "室外10分钟平均温度高于最低限值。(grTempOutdoor_10min <PAR_rTempMIN_Outdoor)",
- "set_delay": "T#1m",
- "yp": "0",
- "reset_en": "The 10min-mean-value of temperature increases above the value given by parameter plus a hysteresis value OR get reset signal of status code coming from Nacelle, Tower or Remote Command. (grTempOutdoor_10min > (PAR_rTempMIN_Outdoor + PAR_rTempHysteresisLowerTemp))",
- "reset_cn": "室外温度(10分钟平均值)大于最小值加上一个滞后值或收到reset信号。(grTempOutdoor_10min > (PAR_rTempMIN_Outdoor + PAR_rTempHysteresisLowerTemp))",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "159-环境温度停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "159",
- "brake_state_design": "50"
- },
- "02_11_020": {
- "subsystem": "NacelleSystem",
- "name": "SC_RepFault_TempOutdoor",
- "en": "The faults, outdoor temperature is too high or too low, have repeated",
- "cn": "舱外环境温度过高或过低警告重复出现",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "1",
- "repeat_period": "T#0s",
- "trigger_en": "One of the statuscodes for the referred temperature for \"temperature too high\" or \"temperature too low\" in a given time periode becomes more times TRUE than maximum allowed.(gbRepeat_02_11_016=1 OR gbRepeat_02_11_017=1)_x000D_",
- "trigger_cn": "室外温度过高或过低故障重复出现。(gbRepeat_02_11_016=1 OR gbRepeat_02_11_017=1)",
- "set_delay": "T#1m",
- "yp": "0",
- "reset_en": "One of the statuscodes for the referred temperature for \"temperature too high\" or \"temperature too low\" in a given time periode becomes less times TRUE than maximum allowed.(gbRepeat_02_11_016=0 AND gbRepeat_02_11_017=0)",
- "reset_cn": "室外温度过高和过低故障不重复出现。(gbRepeat_02_11_016=0 AND gbRepeat_02_11_017=0)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "159-环境温度停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "159",
- "brake_state_design": "51"
- },
- "02_11_101": {
- "subsystem": "NacelleSystem",
- "name": "SC_ShutDownWindspeed_1sMax",
- "en": "1s average wind speed exceeds maximum limit",
- "cn": "1秒平均风速高于上限值",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "when the wind speed (1 sec mean value) exceeds the maximum allowed value, given by parameter.(grWindSpeed_1sec > PAR_rMaxWindSpeed_1sec)",
- "trigger_cn": "当风速(1秒钟平均值)高于允许的最大值(由参数给出)。(grWindSpeed_1sec > PAR_rMaxWindSpeed_1sec)",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "when the wind speed (1 sec mean value) falls below the maximum recover value, given by another parameter.(grWindSpeed_1sec <= PAR_rMaxRecoverWindSpeed_1sec)",
- "reset_cn": "当风速(1秒钟平均值)减低到最大恢复值以下(由另一参数给出)。(grWindSpeed_1sec <= PAR_rMaxRecoverWindSpeed_1sec)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "139-大风停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "139",
- "brake_state_design": "50"
- },
- "02_11_102": {
- "subsystem": "NacelleSystem",
- "name": "SC_ShutDownWindspeed_30sMax",
- "en": "30s average wind speed exceeds maximum limit",
- "cn": "30秒平均风速高于上限值",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The wind speed (30 sec mean value) exceeds the maximum limit value, given by parameter.(grWindSpeed_30sec > PAR_rMaxWindSpeed_30sec)",
- "trigger_cn": "30秒平均风速高于上限值。(grWindSpeed_30sec > PAR_rMaxWindSpeed_30sec)",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "The wind speed (10 min mean value) falls below a value given by another parameter.(grWindSpeed_30sec <= PAR_rMaxRecoverWindSpeed_30sec)",
- "reset_cn": "30秒平均风速降低到上限值内。(grWindSpeed_30sec <= PAR_rMaxRecoverWindSpeed_30sec)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "139-大风停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "139",
- "brake_state_design": "50"
- },
- "02_11_103": {
- "subsystem": "NacelleSystem",
- "name": "SC_ShutDownWindspeed_10minMax",
- "en": "10min average wind speed exceeds maximum limit",
- "cn": "10分钟平均风速高于上限值",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "when the wind speed (10 min mean value) exceeds the maximum allowed value, given by parameter.(grWindSpeed_10min > PAR_rMaxWindSpeed_10min)",
- "trigger_cn": "当风速(10分钟平均值)高于允许的最大值(由参数给出)。(grWindSpeed_10min > PAR_rMaxWindSpeed_10min)",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "_x000D_ when the wind speed (10 min mean value) falls below the maximum recover value, given by another parameter.(grWindSpeed_10min <= PAR_rMaxRecoverWindSpeed_10min)",
- "reset_cn": "当风速(10分钟钟平均值)降低到最大恢复值以下(由另一参数给出)。(grWindSpeed_10min <= PAR_rMaxRecoverWindSpeed_10min)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "139-大风停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "139",
- "brake_state_design": "50"
- },
- "02_11_104": {
- "subsystem": "NacelleSystem",
- "name": "OC_WaitingForWind",
- "en": "Wind speed is too low to start turbine",
- "cn": "10分钟平均风速低于启动风速",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The wind speed (10 min mean value) falls below the value, given by parameter minus 0.1 m/s as a hysteresis.(grWindSpeed_10min < (PAR_rWindAboveStart - 0.1))",
- "trigger_cn": "10分钟平均风速低于给定值(减去0.1作为滞后值)。(grWindSpeed_10min < (PAR_rWindAboveStart - 0.1))",
- "set_delay": "T#10s",
- "yp": "0",
- "reset_en": "The wind speed (10 min mean value) exceeds the value, given by parameter minus 0.1 m/s as a hysteresis.(grWindSpeed_10min > (PAR_rWindAboveStart - 0.1))",
- "reset_cn": "10分钟平均风速高于给定值(减去0.1作为滞后值)。(grWindSpeed_10min > (PAR_rWindAboveStart - 0.1))",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "02_11_105": {
- "subsystem": "NacelleSystem",
- "name": "OC_MeanWindSpeedAboveActivatingYaw",
- "en": "Wind speed is high enough for wind tracking",
- "cn": "风速条件允许偏航系统进行对风",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The wind speed (5 min mean value) exceeds the value, given by parameter.(grWindSpeed_5min >= PAR_rWindAboveActivateYawTracking)",
- "trigger_cn": "5分钟平均风速条件如果达到设定值。(grWindSpeed_5min >= PAR_rWindAboveActivateYawTracking)",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "The wind speed (5 min mean value) falls below the value, given by parameter.(grWindSpeed_5min < PAR_rWindAboveActivateYawTracking)",
- "reset_cn": "5分钟平均风速条件如果没有达到设定值。(grWindSpeed_5min < PAR_rWindAboveActivateYawTracking)",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "02_11_106": {
- "subsystem": "NacelleSystem",
- "name": "OC_MeanWindSpeedAboveRestartMaxWind",
- "en": "Wind speed is too high to restart turbine (the fault of wind speed too high can not be reset)",
- "cn": "1秒平均风速过高",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The wind speed (10 min mean value) exceeds the value, given by parameter.(grWindSpeed_10min > PAR_rWindRestartAtMaxWind)",
- "trigger_cn": "10分钟平均风速大于设定值。(grWindSpeed_10min > PAR_rWindRestartAtMaxWind)",
- "set_delay": "T#10s",
- "yp": "0",
- "reset_en": "The wind speed (10 min mean value) falls below the value, given by parameter.(grWindSpeed_10min < PAR_rWindRestartAtMaxWind)",
- "reset_cn": "10分钟平均风速小于设定值。(grWindSpeed_10min < PAR_rWindRestartAtMaxWind)",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "02_11_107": {
- "subsystem": "NacelleSystem",
- "name": "OC_NoMonitoringWindSensors",
- "en": "Wind speed is too low to monitor wind sensors",
- "cn": "风速过低,不对风速仪和风向标进行监测",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The 10 min mean value for wind speed will be less than a minimum value given by parameter.(grWindSpeed_10min < PAR_rWindSpeedCheckSensors)",
- "trigger_cn": "10分钟平均风速小于对风速仪和风向仪进行监测的设定值。(grWindSpeed_10min < PAR_rWindSpeedCheckSensors)",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "The 10 min mean value for wind speed will be more than a minimum value given by parameter.(grWindSpeed_10min > PAR_rWindSpeedCheckSensors)",
- "reset_cn": "10分钟平均风速大于对风速仪和风向仪进行监测的设定值。(grWindSpeed_10min > PAR_rWindSpeedCheckSensors)",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "02_11_109": {
- "subsystem": "NacelleSystem",
- "name": "SC_ShutDownWindspeed_10minMin",
- "en": "Wind speed is too low for shutdown",
- "cn": "风速过低停机",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The wind speed (10 min mean value) falls below the minimum allowed value, given by parameter.(grWindSpeed_10min < PAR_rMinWindSpeed_10min)",
- "trigger_cn": "10分钟平均风速低于给定值。(grWindSpeed_10min < PAR_rMinWindSpeed_10min)",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "The wind speed (10 min mean value) grows above a value given by another parameter.(grWindSpeed_10min >= PAR_rMinRecoverWindSpeed_10min)",
- "reset_cn": "10分钟平均风速增加大于另一给定值。(grWindSpeed_10min >= PAR_rMinRecoverWindSpeed_10min)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "129-小风停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "129",
- "brake_state_design": "50"
- },
- "02_11_112": {
- "subsystem": "NacelleSystem",
- "name": "OC_MeanWindSpeedAboveCableUnwindingOK",
- "en": "Wind speed is too high to untwist cable",
- "cn": "风速过高,不能自动解缆",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The wind speed (10 min mean value) exceeds the value, given by parameter.(grWindSpeed_10min > PAR_rMaxWindUntwistCable)",
- "trigger_cn": "10分钟平均风速高于不能解缆设定值。(grWindSpeed_10min > PAR_rMaxWindUntwistCable)",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "The wind speed (10 min mean value) falls below the value, given by parameter.(grWindSpeed_10min < (PAR_rMaxWindUntwistCable - 1.0))",
- "reset_cn": "10分钟平均风速低于不能解缆设定值。(grWindSpeed_10min < (PAR_rMaxWindUntwistCable - 1.0))",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "02_11_113": {
- "subsystem": "NacelleSystem",
- "name": "SC_WindSpeedTooHighForManualModeOrService",
- "en": "Wind speed is too high for manual and service mode",
- "cn": "风速过高,不能手动变桨和手动操作风机",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The wind speed (10 min mean value) exceeds the value, given by parameter.(grWindSpeed_10min > PAR_rMaxWindForManualModeOrService)",
- "trigger_cn": "10分钟平均风速高于不能手工变桨和手工操作风机设定值。(grWindSpeed_10min > PAR_rMaxWindForManualModeOrService)",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "The wind speed (10 min mean value) falls below the value, given by parameter.(grWindSpeed_10min < (PAR_rMaxWindForManualModeOrService - 1.0))",
- "reset_cn": "10分钟平均风速低于不能手工变桨和手工操作风机设定值。(grWindSpeed_10min < (PAR_rMaxWindForManualModeOrService - 1.0))",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "02_14_001": {
- "subsystem": "NacelleSystem",
- "name": "SC_PCH_BadDataDetected",
- "en": "error on communication with pch",
- "cn": "主控系统读得的PCH震动值长时间不刷新",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#30s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_14_002": {
- "subsystem": "NacelleSystem",
- "name": "OC_PCHScaleFactorEqualZero",
- "en": "PCH Scale Factor Equal Zero",
- "cn": "PCH读取的振动值系数为0",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "IF (grCANPCH_ScaleFactorBAND1=0) OR_x000D_ (grCANPCH_ScaleFactorBAND2=0) OR_x000D_ (grCANPCH_ScaleFactorBAND11=0)OR_x000D_ (grCANPCH_ScaleFactorRAW1=0) OR_x000D_ (grCANPCH_ScaleFactorRAW2=0) OR_x000D_ (grCANPCH_ScaleFactorRAW3=0) OR_x000D_ (grCANPCH_ScaleFactorRAW4=0) _x000D_ THEN SC=TRUE;_x000D_",
- "trigger_cn": "如果通过CANopen读取的PCH振动值系数任意一个为0,则触发该SC",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "03_03_101": {
- "subsystem": "NacelleSystem",
- "name": "SC_FaultInputPT100_Cable",
- "en": "StatePT100_TempCable error",
- "cn": "电缆温度PT100故障",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "IF giStatePT100_TempCable.6 =TRUE THEN_x000D_ SC=true",
- "trigger_cn": "如果电缆PT100故障位置1,则触发故障",
- "set_delay": "T#5s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "03_03_102": {
- "subsystem": "NacelleSystem",
- "name": "OC_CableOverTempToDisableOverPower",
- "en": "if temp of Cable is too high then DisableOverPower",
- "cn": "当电缆温度超过某个值后,则限制超发功能",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "IF grCableTemp>PAR_rTempToDisableOverPower THEN_x000D_ SC=TRUE",
- "trigger_cn": "如果电缆温度超过某个值,则触发该SC",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "03_09_004": {
- "subsystem": "NacelleSystem",
- "name": "SC_SELFTEST_PCHTestFailed",
- "en": "PCH SelfTest Failed",
- "cn": "PCH自检失败",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "PCH SelfTest Failed.(gbSelfTest4Failed=1)",
- "trigger_cn": "PCH自检失败。(gbSelfTest4Failed=1)",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "PCH SelfTest succeeds.(gbSelfTest4Failed=0)",
- "reset_cn": "PCH自检成功。(gbSelfTest4Failed=0)",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "100"
- },
- "04_09_001": {
- "subsystem": "NacelleSystem",
- "name": "SC_NacelleFireAlarm",
- "en": "The nacelle fire alarm system is activated",
- "cn": "机舱火警系统触发",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "100",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "175-故障停机(强)",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "175",
- "brake_state_design": "100"
- },
- "04_09_002": {
- "subsystem": "NacelleSystem",
- "name": "SC_NacelleFireAlarmSystemDefect",
- "en": "The nacelle fire alarm system has defect",
- "cn": "机舱火警系统失效",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_09_003": {
- "subsystem": "NacelleSystem",
- "name": "SC_FTWindSensorFail",
- "en": "FT wind sensor has fault",
- "cn": "FT风速风向传感器故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "RS485 Communication Error",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_09_004": {
- "subsystem": "NacelleSystem",
- "name": "SC_FTHeaterMCB",
- "en": "The fuse for the FT sensor heating is blown",
- "cn": "FT加热器空开跳开",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "DI = 0",
- "trigger_cn": "",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_09_005": {
- "subsystem": "NacelleSystem",
- "name": "SC_AnalogWindDirectionHeaterMCB",
- "en": "The fuse for the analog wind direction sensor heating is blown",
- "cn": "风向标加热器空开跳开",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "DI = 0",
- "trigger_cn": "",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_09_006": {
- "subsystem": "NacelleSystem",
- "name": "SC_AnalogWindSpeedHeaterMCB",
- "en": "The fuse for the analog wind speed sensor heating is blown",
- "cn": "风速仪加热器空开跳开",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "DI = 0",
- "trigger_cn": "",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_09_008": {
- "subsystem": "NacelleSystem",
- "name": "SC_MaxDeviationWindDirection",
- "en": "The wind direction measured from different sensors beyond the max deviation for a certain time",
- "cn": "不同传感器测得风向偏差过大",
- "powerup_delay": "T#1m",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "ABS(grCurrDirVane1Relative_1min-grCurrDirVane2Relative_1min)_x000D_ >PAR_rMaxDeviation_WindDirection",
- "trigger_cn": "",
- "set_delay": "T#20s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_09_009": {
- "subsystem": "NacelleSystem",
- "name": "SC_MaxDeviationWindSpeed",
- "en": "The wind speed measured from different sensors beyond the max deviation for a certain time",
- "cn": "不同传感器测得风速偏差过大",
- "powerup_delay": "T#1m",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "ABS(grWindSpeed1_30sec-grWindSpeed2_30sec)>PAR_rMaxDeviation_WindSpeed",
- "trigger_cn": "",
- "set_delay": "T#20s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_09_010": {
- "subsystem": "NacelleSystem",
- "name": "SC_NacelleHumidityHigh",
- "en": "",
- "cn": "机舱湿度过大",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_09_011": {
- "subsystem": "NacelleSystem",
- "name": "SC_ForceMode_NacelleOutletDamper",
- "en": "Force control of nacelle outlet damper is enabled",
- "cn": "机舱出口气流调节器强制模式开启",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#50ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_09_012": {
- "subsystem": "NacelleSystem",
- "name": "SC_NacelleOutletDamperMCB",
- "en": "The nacelle outlet damper MCB tripped",
- "cn": "机舱出口气流调节器空开跳开",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "DI = 0",
- "trigger_cn": "",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_09_013": {
- "subsystem": "NacelleSystem",
- "name": "OC_NacelleOutletDamper_ON",
- "en": "The nacelle outlet damper is open",
- "cn": "机舱出口气流调节器打开",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "DO = 1",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_09_014": {
- "subsystem": "NacelleSystem",
- "name": "SC_ManualMode_NacelleOutletDamper",
- "en": "Manual control of nacelle outlet damper is enabled",
- "cn": "机舱出口气流调节器手动模式开启",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#50ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_09_015": {
- "subsystem": "NacelleSystem",
- "name": "SC_ForceMode_NacelleOutletFan",
- "en": "Force control of nacelle outlet fan 1-2 is enabled",
- "cn": "机舱出口风扇强制模式开启",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#50ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_09_016": {
- "subsystem": "NacelleSystem",
- "name": "SC_NacelleOutletFan1MCB",
- "en": "The nacelle outlet fan 1 MCB tripped",
- "cn": "机舱出口风扇1空开跳开",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "DI = 0",
- "trigger_cn": "",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_09_017": {
- "subsystem": "NacelleSystem",
- "name": "SC_NacelleOutletFan1Overload",
- "en": "The nacelle outlet fan 1 overlaod tripped",
- "cn": "机舱出口风扇1热继跳开",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "DI = 0",
- "trigger_cn": "",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_09_018": {
- "subsystem": "NacelleSystem",
- "name": "SC_NacelleOutletFan2MCB",
- "en": "The nacelle outlet fan 2 MCB tripped",
- "cn": "机舱出口风扇2空开跳开",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "DI = 0",
- "trigger_cn": "",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_09_019": {
- "subsystem": "NacelleSystem",
- "name": "SC_NacelleOutletFan2Overload",
- "en": "The nacelle outlet fan 2 overlaod tripped",
- "cn": "机舱出口风扇2热继跳开",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "DI = 0",
- "trigger_cn": "",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_09_020": {
- "subsystem": "NacelleSystem",
- "name": "OC_NacelleOutletFan1_ON",
- "en": "The nacelle outlet fan 1 is switched on",
- "cn": "机舱出口风扇1开启",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "DO = 1",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_09_021": {
- "subsystem": "NacelleSystem",
- "name": "OC_NacelleOutletFan2_ON",
- "en": "The nacelle outlet fan 2 is switched on",
- "cn": "机舱出口风扇2开启",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "DO = 1",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_09_022": {
- "subsystem": "NacelleSystem",
- "name": "SC_ManualMode_NacelleOutletFan",
- "en": "Manual control of nacelle outlet fan 1-2 is enabled",
- "cn": "机舱出口风扇手动模式开启",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#50ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_09_023": {
- "subsystem": "NacelleSystem",
- "name": "SC_ForceMode_NacelleInletDamper",
- "en": "Force control of nacelle inlet damper 1-2 is enabled",
- "cn": "机舱入口气流调节器强制模式开启",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#50ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_09_024": {
- "subsystem": "NacelleSystem",
- "name": "SC_NacelleInletDamperMCB",
- "en": "The nacelle inlet damper 1-2 MCB tripped",
- "cn": "机舱入口气流调节器空开跳开",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "DI = 0",
- "trigger_cn": "",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_09_025": {
- "subsystem": "NacelleSystem",
- "name": "OC_NacelleInletDamper_ON",
- "en": "The nacelle inlet damper 1-2 are open",
- "cn": "机舱入口气流调节器打开",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "DO = 1",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_09_026": {
- "subsystem": "NacelleSystem",
- "name": "SC_ManualMode_NacelleInletDamper",
- "en": "Manual control of nacelle inlet damper 1-2 is enabled",
- "cn": "机舱入口气流调节器手动模式开启",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#50ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_09_027": {
- "subsystem": "NacelleSystem",
- "name": "SC_ForceMode_NacelleHeater",
- "en": "Force control of nacelle heating is enabled",
- "cn": "机舱加热器强制模式开启",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#50ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_09_028": {
- "subsystem": "NacelleSystem",
- "name": "SC_NacelleHeaterMCB",
- "en": "The nacelle heating MCB tripped",
- "cn": "机舱加热器空开跳开",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "DI = 0",
- "trigger_cn": "",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_09_029": {
- "subsystem": "NacelleSystem",
- "name": "OC_NacelleHeater_ON",
- "en": "The nacelle heating is swithed on",
- "cn": "机舱加热器开启",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "DO = 1",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_09_030": {
- "subsystem": "NacelleSystem",
- "name": "SC_ManualMode_NacelleHeater",
- "en": "Manual control of nacelle heating is enabled",
- "cn": "机舱加热器手动模式开启",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#50ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_09_031": {
- "subsystem": "NacelleSystem",
- "name": "SC_AviationLightMCB",
- "en": "The fuse for the aviation light is blown",
- "cn": "航空灯空开跳开",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "DI = 1",
- "trigger_cn": "",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_09_032": {
- "subsystem": "NacelleSystem",
- "name": "SC_AviationLightStatus",
- "en": "The aviation light system as an eror",
- "cn": "航空灯故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "DI = 1",
- "trigger_cn": "",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_02_009": {
- "subsystem": "Cabinet",
- "name": "SC_TempCabinetNacelle_high",
- "en": "Temperature of Nacelle cabinet is high",
- "cn": "机舱控制柜温度过高警告",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "3",
- "repeat_period": "T#24h",
- "trigger_en": "Temperature(10min-mean-value) of Nacelle cabinet is high.(grTempCabinetNacelle_10min>PAR_rTempHigh_CabinetNacelle)",
- "trigger_cn": "机舱控制柜温度(10分钟平均值)高于设定值。(grTempCabinetNacelle_10min>PAR_rTempHigh_CabinetNacelle)",
- "set_delay": "T#1m",
- "yp": "0",
- "reset_en": "The 10min-mean-value of temperature falls below the value given by parameter minus a hysteresis value OR get reset signal of status code coming from Nacelle, Tower or Remote Command.((grTempCabinetNacelle_10min <(PAR_rTempHigh_CabinetNacelle -PAR_rTempHysteresisUpperTemp)) OR gbMAIN_ResetStatusCodes=1) AND bSpecResCond=1",
- "reset_cn": "机舱控制柜温度(10分钟平均值)小于设定值减去一个滞后值或收到reset信号。((grTempCabinetNacelle_10min <(PAR_rTempHigh_CabinetNacelle -PAR_rTempHysteresisUpperTemp)) OR gbMAIN_ResetStatusCodes=1) AND bSpecResCond=1",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_02_010": {
- "subsystem": "Cabinet",
- "name": "SC_TempCabinetNacelle_low",
- "en": "Temperature of Nacelle cabinet is low",
- "cn": "机舱控制柜温度过低警告",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "3",
- "repeat_period": "T#24h",
- "trigger_en": "Temperature(10min-mean-value) of Nacelle cabinet is low.(grTempCabinetNacelle_10min<PAR_rTempHigh_CabinetNacelle)",
- "trigger_cn": "机舱控制柜温度(10分钟平均值)低于设定值。(grTempCabinetNacelle_10min<PAR_rTempHigh_CabinetNacelle)",
- "set_delay": "T#1m",
- "yp": "0",
- "reset_en": "The 10min-mean-value of temperature increases above the value given by parameter plus a hysteresis value OR get reset signal of status code coming from Nacelle, Tower or Remote Command.((grTempCabinetNacelle_10min >(PAR_rTempHigh_CabinetNacelle +PAR_rTempHysteresisUpperTemp)) OR gbMAIN_ResetStatusCodes=1) AND bSpecResCond=1",
- "reset_cn": "机舱控制柜温度(10分钟平均值)大于设定值加上一个滞后值或收到reset信号。((grTempCabinetNacelle_10min >(PAR_rTempHigh_CabinetNacelle +PAR_rTempHysteresisUpperTemp)) OR gbMAIN_ResetStatusCodes=1) AND bSpecResCond=1",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_02_011": {
- "subsystem": "Cabinet",
- "name": "SC_TempCabinetNacelle_MAX",
- "en": "Temperature of Nacelle cabinet exceeds the maximum value",
- "cn": "机舱控制柜温度过高故障",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "When Ethercat is OK and Temperature(10min-mean-value) of Nacelle cabinet exceeds the maximum value.(grTempCabinetNacelle_10min>PAR_rTempMAX_CabinetNacelle)",
- "trigger_cn": "Ethercat通讯正常,并且机舱控制柜温度(10分钟平均值)高于最大上限值.(grTempCabinetNacelle_10min>PAR_rTempMAX_CabinetNacelle)",
- "set_delay": "T#1m",
- "yp": "0",
- "reset_en": "The 10min-mean-value of temperature falls below the maximum value minus a hysteresis value OR get reset signal of status code coming from Nacelle, Tower or Remote Command or Ethercat is disconnect._x000D_ ((grTempCabinetNacelle_10min <(PAR_rTempMAX_CabinetNacelle -PAR_rTempHysteresisUpperTemp)) OR gbMAIN_ResetStatusCodes=1) OR gbEthercat_OK = false",
- "reset_cn": "机舱控制柜温度(10分钟平均值)小于设定值减去一个滞后值或收到reset信号或者Ethercat通讯断开。((grTempCabinetNacelle_10min <(PAR_rTempMAX_CabinetNacelle -PAR_rTempHysteresisUpperTemp)) OR gbMAIN_ResetStatusCodes=1) OR gbEthercat_OK = false",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_02_012": {
- "subsystem": "Cabinet",
- "name": "SC_TempCabinetNacelle_MIN",
- "en": "Temperature of Nacelle cabinet exceeds the minimum value",
- "cn": "机舱控制柜温度过低故障",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Temperature(10min-mean-value) of Nacelle cabinet exceeds the minimum value.(grTempCabinetNacelle_10min<PAR_rTempMIN_CabinetNacelle)",
- "trigger_cn": "机舱控制柜温度(10分钟平均值)高于最小下限值.(grTempCabinetNacelle_10min<PAR_rTempMIN_CabinetNacelle)",
- "set_delay": "T#1m",
- "yp": "0",
- "reset_en": "The 10min-mean-value of temperature increases above the minimum value plus a hysteresis value OR get reset signal of status code coming from Nacelle, Tower or Remote Command.((grTempCabinetNacelle_10min >(PAR_rTempMIN_CabinetNacelle +PAR_rTempHysteresisUpperTemp)) OR gbMAIN_ResetStatusCodes=1) AND bSpecResCond=1",
- "reset_cn": "机舱控制柜温度(10分钟平均值)大于设定值加上一个滞后值或收到reset信号。((grTempCabinetNacelle_10min >(PAR_rTempMIN_CabinetNacelle +PAR_rTempHysteresisUpperTemp)) OR gbMAIN_ResetStatusCodes=1) AND bSpecResCond=1",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_02_013": {
- "subsystem": "Cabinet",
- "name": "SC_RepFaultTempCabinetNacelle",
- "en": "nacelle cabinet temperature is low or high repeatedly",
- "cn": "机舱控制柜温度过高或过低警告重复出现",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "nacelle cabinet temperature is low or high repeatedly.(gbRepeat_02_02_009=1 OR gbRepeat_02_02_010=1)",
- "trigger_cn": "机舱控制柜频繁出现温度过高或过低的情况。(gbRepeat_02_02_009=1 OR gbRepeat_02_02_010=1)",
- "set_delay": "T#1m",
- "yp": "0",
- "reset_en": "Change in nacelle cabinet temperature is normal.(gbRepeat_02_02_009=0 AND gbRepeat_02_02_010=0 AND bSpecResCond=1)",
- "reset_cn": "机舱控制柜的温度变化恢复到正常。(gbRepeat_02_02_009=0 AND gbRepeat_02_02_010=0 AND bSpecResCond=1)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_02_052": {
- "subsystem": "Cabinet",
- "name": "SC_FaultInputPT100_CabinetNacelle",
- "en": "PT100 for nacelle cabinet has fault",
- "cn": "机舱控制柜温度测量PT100传感器故障",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Bit 6 from the status byte from the nacelle cabinet PT100 input becomes TRUE.(giStatePT100_TempCabinetNacelle.6=1)",
- "trigger_cn": "机舱控制柜PT100传感器输入的状态字节第6位是TRUE或机舱控制柜10min平均温度不在[-100,500]之间。(giStatePT100_TempCabinetNacelle.6=1 OR (grTempCabinetNacelle_10min >500 OR grTempCabinetNacelle_10min <-100))",
- "set_delay": "T#5s",
- "yp": "0",
- "reset_en": "Bit 6 from the status byte from the nacelle cabinet PT100 input becomes FALSE.(giStatePT100_TempCabinetNacelle.6=0)",
- "reset_cn": "机舱控制柜PT100传感器输入的状态字节第6位是FALSE且机舱控制柜10min平均温度在[-100,500]之间。(giStatePT100_TempCabinetNacelle.6=0 AND (grTempCabinetNacelle_10min <500 AND grTempCabinetNacelle_10min >-100)",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_12_001": {
- "subsystem": "Cabinet",
- "name": "SC_ManualSTOP_NacelleOrTowerBase",
- "en": "Manual stop is commanded from nacelle or turbine base",
- "cn": "机舱或塔底发出停机命令",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Manual stop is commanded from nacelle or turbine base.(gbDI_NacelleWECStop=1 OR gbDI_TowerWECStop=1)",
- "trigger_cn": "机舱或塔底发出停机命令。(gbDI_NacelleWECStop=1 OR gbDI_TowerWECStop=1)",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "No Manual stop is commanded from nacelle and turbine base.(gbDI_NacelleWECStop=0 AND gbDI_TowerWECStop=0)",
- "reset_cn": "机舱和塔底没有发出停机命令。(gbDI_NacelleWECStop=0 AND gbDI_TowerWECStop=0)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "200-用户停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "200",
- "brake_state_design": "51"
- },
- "03_02_002": {
- "subsystem": "ConverterContainer",
- "name": "SC_TowerBaseUPS_Alarm",
- "en": "Towerbase UPS has alarm",
- "cn": "变频柜230V UPS警告",
- "powerup_delay": "T#1s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Towerbase UPS has alarm or a \"diConverter_UPS_low\" signal is TRUE.(gbDI_TowerUPS230V_Alarm = PAR_bUPSAlarmSignal OR diConverter_UPS_low=1)",
- "trigger_cn": "塔底有UPS警告或\"diConverter_UPS_low\"信号为真。gbDI_TowerUPS230V_Alarm = PAR_bUPSAlarmSignal OR diConverter_UPS_low=1)",
- "set_delay": "T#60s",
- "yp": "0",
- "reset_en": "Towerbase UPS has no alarm and a \"diConverter_UPS_low\" signal is FALSE.(gbDI_TowerUPS230V_Alarm ≠ PAR_bUPSAlarmSignal AND diConverter_UPS_low=0)",
- "reset_cn": "塔底无UPS警告且\"diConverter_UPS_low\"信号为假。(gbDI_TowerUPS230V_Alarm ≠ PAR_bUPSAlarmSignal AND diConverter_UPS_low=0)",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "03_02_023": {
- "subsystem": "Cabinet",
- "name": "SC_FaultInputPT100_TempTowerBase",
- "en": "PT100 for tower base temperature has fault",
- "cn": "塔底温度测量PT100传感器故障",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The status byte from the referred PT100 input becomes TRUE.(iStatePT100_TempTowerBase_BOOL=1)",
- "trigger_cn": "测塔底温度的PT100传感器输入的状态是TRUE或塔底10平均温度不在范围[-100,500]。(iStatePT100_TempTowerBase_BOOL=1 OR (grTempTowerBase_10min >500 OR grTempTowerBase_10min<-100))",
- "set_delay": "T#5s",
- "yp": "0",
- "reset_en": "The status byte from the referred PT100 input becomes FALSE.(iStatePT100_TempTowerBase_BOOL=0)",
- "reset_cn": "测塔底温度的PT100传感器输入的状态是FALSE且塔底10平均温度在范围[-100,500]。(iStatePT100_TempTowerBase_BOOL=0 AND (grTempTowerBase_10min <500 AND grTempTowerBase_10min>-100))",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "03_02_024": {
- "subsystem": "Cabinet",
- "name": "SC_TempCabinetTowerBase_high",
- "en": "Temperature of towerbase cabinet is too high",
- "cn": "塔底控制柜温度过高警告",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "3",
- "repeat_period": "T#24h",
- "trigger_en": "The 10min-mean-value of the temperature exceeds the value given by parameter.(grTempCabinetTowerBase_10min > PAR_rTempHigh_CabinetTower)",
- "trigger_cn": "塔底控制柜10分钟平均温度高于过高设定值。(grTempCabinetTowerBase_10min > PAR_rTempHigh_CabinetTower)",
- "set_delay": "T#1m",
- "yp": "0",
- "reset_en": "The 10min-mean-value of temperature falls below the value given by parameter minus a hysteresis value OR get reset signal of status code coming from Nacelle, Tower or Remote Command.((grTempCabinetTowerBase_10min < (PAR_rTempHigh_CabinetTower - PAR_rTempHysteresisUpperTemp)) OR gbMAIN_ResetStatusCodes=1)",
- "reset_cn": "塔底控制柜温度(10分钟平均值)小于设定值减去一个滞后值或收到reset信号。((grTempCabinetTowerBase_10min < (PAR_rTempHigh_CabinetTower - PAR_rTempHysteresisUpperTemp)) OR gbMAIN_ResetStatusCodes=1)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "03_02_025": {
- "subsystem": "Cabinet",
- "name": "SC_TempCabinetTowerBase_low",
- "en": "Temperature of towerbase cabinet is too low",
- "cn": "塔底控制柜温度过低警告",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "3",
- "repeat_period": "T#24h",
- "trigger_en": "The 10min-mean-value of the temperature falls below the value given by parameter. (grTempCabinetTowerBase_10min < PAR_rTempLow_CabinetTower)",
- "trigger_cn": "塔底控制柜10分钟平均温度低于过低设定值。(grTempCabinetTowerBase_10min < PAR_rTempLow_CabinetTower)",
- "set_delay": "T#1m",
- "yp": "0",
- "reset_en": "The 10min-mean-value of temperature increases above the value given by parameter plus a hysteresis value OR get reset signal of status code coming from Nacelle, Tower or Remote Command. ((grTempCabinetTowerBase_10min > (PAR_rTempLow_CabinetTower + PAR_rTempHysteresisLowerTemp)) OR gbMAIN_ResetStatusCodes=1)",
- "reset_cn": "塔底控制柜温度(10分钟平均值)大于设定值加上一个滞后值或收到reset信号。((grTempCabinetTowerBase_10min > (PAR_rTempLow_CabinetTower + PAR_rTempHysteresisLowerTemp)) OR gbMAIN_ResetStatusCodes=1)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "03_02_026": {
- "subsystem": "Cabinet",
- "name": "SC_TempCabinetTowerBase_MAX",
- "en": "Temperature of towerbase cabinet exceeds maximum limit",
- "cn": "塔底控制柜温度过高故障",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The 10min-mean-value of the temperature exceeds the maximum limit value given by parameter.(grTempCabinetTowerBase_10min > PAR_rTempMAX_CabinetTower)",
- "trigger_cn": "塔底控制柜10分钟平均温度高于上限值。(grTempCabinetTowerBase_10min > PAR_rTempMAX_CabinetTower)",
- "set_delay": "T#1m",
- "yp": "0",
- "reset_en": "The 10min-mean-value of temperature falls below the value given by parameter minus a hysteresis value OR get reset signal of status code coming from Nacelle, Tower or Remote Command.(grTempCabinetTowerBase_10min < (PAR_rTempMAX_CabinetTower - PAR_rTempHysteresisUpperTemp) OR gbMAIN_ResetStatusCodes=1)",
- "reset_cn": "塔底控制柜温度(10分钟平均值)小于最大值减去一个滞后值或收到reset信号。(grTempCabinetTowerBase_10min < (PAR_rTempMAX_CabinetTower - PAR_rTempHysteresisUpperTemp) OR gbMAIN_ResetStatusCodes=1)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "03_02_027": {
- "subsystem": "Cabinet",
- "name": "SC_TempCabinetTowerBase_MIN",
- "en": "Temperature of towerbase cabinet exceeds minimum limit",
- "cn": "塔底控制柜温度过低故障",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The 10min-mean-value of the temperature falls below the minimum limit value given by parameter.(grTempCabinetTowerBase_10min < PAR_rTempMIN_CabinetTower)",
- "trigger_cn": "塔底控制柜10分钟平均温度低于下限值。(grTempCabinetTowerBase_10min < PAR_rTempMIN_CabinetTower)",
- "set_delay": "T#1m",
- "yp": "0",
- "reset_en": "The 10min-mean-value of temperature increases above the value given by parameter plus a hysteresis value OR get reset signal of status code coming from Nacelle, Tower or Remote Command. (grTempCabinetTowerBase_10min > (PAR_rTempMIN_CabinetTower + PAR_rTempHysteresisLowerTemp) OR gbMAIN_ResetStatusCodes=1)_x000D_",
- "reset_cn": "塔底控制柜温度(10分钟平均值)大于最小值加上一个滞后值或收到reset信号。(grTempCabinetTowerBase_10min > (PAR_rTempMIN_CabinetTower + PAR_rTempHysteresisLowerTemp) OR gbMAIN_ResetStatusCodes=1)_x000D_",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "50"
- },
- "03_02_028": {
- "subsystem": "Cabinet",
- "name": "SC_RepFaultTempCabinetTowerBase",
- "en": "The faults, towerbase cabinet temperature is too high or low, have repeated",
- "cn": "塔底控制柜温度过高或过低警告重复出现",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "3",
- "repeat_period": "T#24h",
- "trigger_en": "One of the statuscodes for the referred temperature for \"temperature too high\" or \"temperature too low\" in a given time periode becomes more times TRUE than maximum allowed.(gbRepeat_03_02_024=1 OR gbRepeat_03_02_025=1)",
- "trigger_cn": "塔底控制柜温度过高过低故障重复出现次数大于设定值。(gbRepeat_03_02_024=1 OR gbRepeat_03_02_025=1)",
- "set_delay": "T#1m",
- "yp": "0",
- "reset_en": "One of the statuscodes for the referred temperature for \"temperature too high\" and \"temperature too low\" in a given time periode becomes less times than maximum allowed.(gbRepeat_03_02_024=0 AND gbRepeat_03_02_025=0)",
- "reset_cn": "塔底控制柜温度过高过低故障重复出现次数小于设定值。(gbRepeat_03_02_024=0 AND gbRepeat_03_02_025=0)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "51"
- },
- "03_02_039": {
- "subsystem": "Cabinet",
- "name": "SC_FaultInputPT100_TempCabinetTowerBase",
- "en": "PT100 for tower base cabinet temperature has fault",
- "cn": "塔底控制柜温度测量PT100传感器故障",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The status byte from the referred PT100 input becomes TRUE.(iStatePT100_TempCabinetTowerBase_BOOL=1)",
- "trigger_cn": "测塔底控制柜温度的PT100传感器输入的状态是TRUE或塔底控制柜10min平均温度不在范围[-100,500]内。(iStatePT100_TempCabinetTowerBase_BOOL=1 OR(grTempCabinetTowerBase_10min >500 OR grTempCabinetTowerBase_10min<-100))",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "The status byte from the referred PT100 input becomes FALSE.(iStatePT100_TempCabinetTowerBase_BOOL=0)",
- "reset_cn": "测塔底控制柜温度的PT100传感器输入的状态是FALSE且塔底控制柜10min平均温度在范围[-100,500]内。(iStatePT100_TempCabinetTowerBase_BOOL=0 AND(grTempCabinetTowerBase_10min <500 AND grTempCabinetTowerBase_10min>-100))",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "03_08_001": {
- "subsystem": "Cabinet",
- "name": "SC_TurbineInServiceTowerBase",
- "en": "Turbine is requested for service mode by towerbase service switch",
- "cn": "塔底柜维护开关打开,要求风机进入维护模式",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Turbine is requested for service mode by towerbase service switch.(gbDI_TowerSafetyChainWECinService=1)",
- "trigger_cn": "塔底检修开关打开,要求风机进入检修模式。(gbDI_TowerSafetyChainWECinService=1)",
- "set_delay": "T#0s",
- "yp": "30",
- "reset_en": "The towerbase service switch becomes FALSE.(gbDI_TowerSafetyChainWECinService=0)",
- "reset_cn": "塔底检修开关关闭。(gbDI_TowerSafetyChainWECinService=0)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "210-维护",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "210",
- "brake_state_design": "0"
- },
- "04_03_001": {
- "subsystem": "RotorLock",
- "name": "SC_RotorLock_Pin1NotUnlocked",
- "en": "The rotor lock 1 is not released for operation",
- "cn": "风轮锁1不在退出位置",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "gbDI_RotorLock_Pin1Unlocked=0",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "DI_Rotor_1_Unlocked = 1",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "51"
- },
- "04_03_002": {
- "subsystem": "RotorLock",
- "name": "SC_RotorLock_Pin2NotUnlocked",
- "en": "The rotor lock 2 is not released for operation",
- "cn": "风轮锁2不在退出位置",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "gbDI_RotorLock_Pin2Unlocked=0",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "DI_Rotor_2_Unlocked = 1",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "51"
- },
- "04_03_003": {
- "subsystem": "RotorLock",
- "name": "SC_RotorLock_PushOutPressureOK",
- "en": "Rotor lock disable pressure is high enough",
- "cn": "风轮锁退出压力正常",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "grRotorLock_PushOutPressure>PAR_rRotorLockPushOutPressureOK AND gbDI_RotorLock_Pin1Unlocked=0 AND gbDI_RotorLock_Pin2Unlocked=0",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_03_004": {
- "subsystem": "RotorLock",
- "name": "SC_RotorLock_PinPositionError",
- "en": "The rotor lock is not retracted in indiling or production mode",
- "cn": "在空转或发电状态,风轮锁不在退出位置",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "(gbDI_RotorLock_Pin1Unlocked=0 OR gbDI_RotorLock_Pin2Unlocked=0) AND NOT gbDI_ServerKey",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "100"
- },
- "04_03_005": {
- "subsystem": "RotorLock",
- "name": "SC_RotorLock_PushOutPressureLowWarning",
- "en": "During idling or production mode, the rotor lock disable pressure is low",
- "cn": "在空转或发电状态,风轮锁退出压力过低报警",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "grRotorLock_PushOutPressure<PAR_rRotorLockPushOutPressureLowWarning AND NOT gbDI_ServerKey",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "A",
- "alarm": "True",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "165",
- "brake_state_design": "0"
- },
- "04_03_006": {
- "subsystem": "RotorLock",
- "name": "SC_RotorLock_PushOutPressureLowError",
- "en": "During idling or production mode, the rotor lock disable pressure is too low",
- "cn": "在空转或发电状态,风轮锁退出压力过低停机",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "grRotorLock_PushOutPressure<PAR_rRotorLockPushOutPressureLowError AND NOT gbDI_ServerKey",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_03_007": {
- "subsystem": "RotorLock",
- "name": "SC_RotorLock_PushOutPressureSensorFault",
- "en": "",
- "cn": "风轮锁退出压力传感器故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_12_001": {
- "subsystem": "ConverterContainer",
- "name": "SC_CC_690V_Supply_Fault",
- "en": "At least one of the 690V protection relays has tripped",
- "cn": "变频器690V供电故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_12_002": {
- "subsystem": "ConverterContainer",
- "name": "SC_CC_400V_Supply_Fault",
- "en": "At least one of the 400V protection relays has tripped",
- "cn": "变频器400V供电故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_12_003": {
- "subsystem": "ConverterContainer",
- "name": "SC_CC_230V_UPS_Supply_Fault",
- "en": "At least one of the 230V UPS protection relays has tripped",
- "cn": "变频器230V UPS供电故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_12_004": {
- "subsystem": "ConverterContainer",
- "name": "SC_CC_Temp_High",
- "en": "Container temperature measured on one or both PT100's is high (The function shall be performed with only the measurements from the healthy PT100 sensor)",
- "cn": "变频柜温度高报警",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_12_005": {
- "subsystem": "ConverterContainer",
- "name": "SC_CC_Temp_VeryHigh",
- "en": "Container temperature measured on one or both PT100's is very high (The function shall be performed with only the measurements from the healthy PT100 sensor)",
- "cn": "变频柜温度高故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_12_006": {
- "subsystem": "ConverterContainer",
- "name": "SC_CC_Temp_Low",
- "en": "Container temperature measured on one or both PT100's is low (The function shall be performed with only the measurements from the healthy PT100 sensor)",
- "cn": "变频柜温度低故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_12_007": {
- "subsystem": "ConverterContainer",
- "name": "SC_CC_AirCon_Fault",
- "en": "Air condition protection relay has tripped",
- "cn": "变频柜空调故障",
- "powerup_delay": "T#1s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "165",
- "brake_state_design": "0"
- },
- "04_12_008": {
- "subsystem": "ConverterContainer",
- "name": "SC_CC_SmokeDetect",
- "en": "Either smoke detectors are active",
- "cn": "变频柜中烟雾报警器触发",
- "powerup_delay": "T#1s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "175-故障停机(强)",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "175",
- "brake_state_design": "51"
- },
- "04_12_009": {
- "subsystem": "ConverterContainer",
- "name": "SC_FaultInputPT100_CC_One",
- "en": "Exactly one PT100 in CC has fault",
- "cn": "变频柜中一个PT100故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#5s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_12_010": {
- "subsystem": "ConverterContainer",
- "name": "SC_FaultInputPT100_CC_Both",
- "en": "Both PT100 in CC has fault",
- "cn": "变频柜中两个PT100故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#5s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_12_011": {
- "subsystem": "ConverterContainer",
- "name": "SC_Heater_Supply_Coverter1_MCB",
- "en": "MCB for heater supply in converter1 has tripped",
- "cn": "变频器1的加热器供电空开跳开",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_12_012": {
- "subsystem": "ConverterContainer",
- "name": "SC_Heater_Supply_Coverter2_MCB",
- "en": "MCB for heater supply in converter2 has tripped",
- "cn": "变频器2的加热器供电空开跳开",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_12_013": {
- "subsystem": "ConverterContainer",
- "name": "SC_Converters_Alarm",
- "en": "The master converter detect alarm signal",
- "cn": "变频器报告警告",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "165",
- "brake_state_design": "100"
- },
- "04_12_014": {
- "subsystem": "ConverterContainer",
- "name": "SC_Converter_BrakeChopperActive",
- "en": "",
- "cn": "变频器Chopper开启",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_12_015": {
- "subsystem": "ConverterContainer",
- "name": "SC_Converter_DCLinkChargeTimeOut",
- "en": "",
- "cn": "变频器直流母线充电超时",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "PAR_tCVT_DCLinkChargeTimeout",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "50",
- "brake_state_design": "51"
- },
- "03_04_013": {
- "subsystem": "TurbineStateMachine",
- "name": "SC_ReturnOfGrid_RideThrough",
- "en": "Grid is recovered in LVRT",
- "cn": "LVRT模式下电网恢复",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Speed boost after RideThrough, Grid is recovered.(gbSpeedBoostAfterRideThrough=1)",
- "trigger_cn": "低电压穿越后电网恢复。(gbSpeedBoostAfterRideThrough=1)",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "Grid is not recovered in LVRT.(gbSpeedBoostAfterRideThrough=0)",
- "reset_cn": "低电压穿越后电网没有恢复。(gbSpeedBoostAfterRideThrough=0)",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "03_04_014": {
- "subsystem": "TurbineStateMachine",
- "name": "SC_FaultRestartAfterReturnOfGrid",
- "en": "Turbine restart after grid recovery in LVRT",
- "cn": "LVRT模式下电网恢复后风机重新启动",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Turbine restart after grid recovery in LVRT.(gbFaultAtRideThroughMode=1)",
- "trigger_cn": "LVRT模式下电网恢复风机重启。(gbFaultAtRideThroughMode=1)",
- "set_delay": "T#0s",
- "yp": "100",
- "reset_en": "Turbine can not restart after grid recovery in LVRT.(gbFaultAtRideThroughMode=0)",
- "reset_cn": "LVRT模式下电网恢复风机未能重启。(gbFaultAtRideThroughMode=0)",
- "reset_mode": "M",
- "type": "A",
- "alarm": "True",
- "level": "180-电网故障",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "180",
- "brake_state_design": "51"
- },
- "03_04_017": {
- "subsystem": "TurbineStateMachine",
- "name": "SC_VoltageOutOfRange_RideThrough",
- "en": "Grid voltage is out of range in LVRT",
- "cn": "LVRT模式下电网电压超限",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Grid voltage is out of range in LVRT.(diConverter_LowVoltageForRideThrough=1)",
- "trigger_cn": "LVRT模式下电网电压超限。(diConverter_LowVoltageForRideThrough=1)",
- "set_delay": "T#0s",
- "yp": "100",
- "reset_en": "Grid voltage is within range in LVRT.(diConverter_LowVoltageForRideThrough=0)",
- "reset_cn": "LVRT模式下电网电压没有超限。(diConverter_LowVoltageForRideThrough=0)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "03_04_321": {
- "subsystem": "TurbineStateMachine",
- "name": "OC_UserLimitPower",
- "en": "power limitation command from out system",
- "cn": "用户限功率",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "99-用户限功率发电",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "99",
- "brake_state_design": "0"
- },
- "03_04_322": {
- "subsystem": "TurbineStateMachine",
- "name": "OC_SystemLimitPower",
- "en": "power limitation command by system",
- "cn": "主控限功率",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "89-主控限功率发电",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "89",
- "brake_state_design": "0"
- },
- "03_06_136": {
- "subsystem": "TurbineStateMachine",
- "name": "OC_ShutDownOutput",
- "en": "Shut down output during System failure.",
- "cn": "系统故障时关闭输出",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "IF (SC_GridVoltageL1_low OR SC_GridVoltageL2_low OR SC_GridVoltageL3_low) OR_x000D_ OC_PitchRideThroughDetected OR_x000D_ OC_ConverterRideThroughDetected OR_x000D_ SC_VoltageDipFreeRun_RideThrough OR_x000D_ SC_VoltageDipGridConnected_RideThrough OR_x000D_ SC_VoltageOutOfRange_RideThrough OR_x000D_ SC_GridFailureByConverter OR_x000D_ SC_NacelleFuse690VMainSupply OR_x000D_ SC_TowerNHFuse690VMAINSupply OR_x000D_ SC_TowerNHFuse400VMainSupply OR_x000D_ SC_NacelleFuse400VMainSupply OR_x000D_ SC_GridVoltageL1_high OR_x000D_ SC_GridVoltageL2_high OR_x000D_ SC_GridVoltageL3_high OR_x000D_ SC_GridVoltageL1_low OR_x000D_ SC_GridVoltageL2_low OR_x000D_ SC_GridVoltageL3_low",
- "trigger_cn": "如果满足(SC_GridVoltageL1_low OR SC_GridVoltageL2_low OR SC_GridVoltageL3_low) OR_x000D_ OC_PitchRideThroughDetected OR_x000D_ OC_ConverterRideThroughDetected OR_x000D_ SC_VoltageDipFreeRun_RideThrough OR_x000D_ SC_VoltageDipGridConnected_RideThrough OR_x000D_ SC_VoltageOutOfRange_RideThrough OR_x000D_ SC_GridFailureByConverter OR_x000D_ SC_NacelleFuse690VMainSupply OR_x000D_ SC_TowerNHFuse690VMAINSupply OR_x000D_ SC_TowerNHFuse400VMainSupply OR_x000D_ SC_NacelleFuse400VMainSupply OR_x000D_ SC_GridVoltageL1_high OR_x000D_ SC_GridVoltageL2_high OR_x000D_ SC_GridVoltageL3_high OR_x000D_ SC_GridVoltageL1_low OR_x000D_ SC_GridVoltageL2_low OR_x000D_ SC_GridVoltageL3_low 则触发",
- "set_delay": "T#0s",
- "yp": "100",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "03_07_005": {
- "subsystem": "TurbineStateMachine",
- "name": "SC_TestBrakeProgram50",
- "en": "TargetVISU request Brake Program 50",
- "cn": "Scada发出50#刹车测试指令",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "TargetVISU request Brake Program 50.(diTargetVISU_TriggerBP50=1)",
- "trigger_cn": "TargetVISU要求50号刹车程序。(diTargetVISU_TriggerBP50=1)",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "TargetVISU do not request Brake Program 50.(diTargetVISU_TriggerBP50=0)",
- "reset_cn": "TargetVISU没有要求50号刹车程序。(diTargetVISU_TriggerBP50=0)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "210-维护",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "210",
- "brake_state_design": "50"
- },
- "03_07_006": {
- "subsystem": "TurbineStateMachine",
- "name": "SC_TestBrakeProgram51",
- "en": "TargetVISU request Brake Program 51",
- "cn": "Scada发出51#刹车测试指令",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "TargetVISU request Brake Program 51.(diTargetVISU_TriggerBP51=1)",
- "trigger_cn": "TargetVISU要求51号刹车程序。(diTargetVISU_TriggerBP51=1)",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "TargetVISU do not request Brake Program 51.(diTargetVISU_TriggerBP51=0)",
- "reset_cn": "TargetVISU没有要求51号刹车程序。(diTargetVISU_TriggerBP51=0)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "210-维护",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "210",
- "brake_state_design": "51"
- },
- "03_07_007": {
- "subsystem": "TurbineStateMachine",
- "name": "SC_TestBrakeProgram100",
- "en": "TargetVISU request Brake Program 100",
- "cn": "Scada发出100#刹车测试指令",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "TargetVISU request Brake Program 100.(diTargetVISU_TriggerBP100=1)",
- "trigger_cn": "TargetVISU要求100号刹车程序。(diTargetVISU_TriggerBP100=1)",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "TargetVISU do not request Brake Program 100.(diTargetVISU_TriggerBP100=0)",
- "reset_cn": "TargetVISU没有要求100号刹车程序。(diTargetVISU_TriggerBP100=0)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "210-维护",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "210",
- "brake_state_design": "100"
- },
- "03_07_008": {
- "subsystem": "TurbineStateMachine",
- "name": "SC_TestBrakeProgram198",
- "en": "TargetVISU request Brake Program 199",
- "cn": "Scada发出198#刹车测试指令",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "TargetVISU request Brake Program 199.(diTargetVISU_TriggerBP199=1)",
- "trigger_cn": "TargetVISU要求199号刹车程序。(diTargetVISU_TriggerBP199=1)",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "TargetVISU do not request Brake Program 199.(diTargetVISU_TriggerBP199=0)",
- "reset_cn": "TargetVISU没有要求199号刹车程序。(diTargetVISU_TriggerBP199=0)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "210-维护",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "210",
- "brake_state_design": "198"
- },
- "03_07_011": {
- "subsystem": "TurbineStateMachine",
- "name": "SC_TestBrakeProgram200",
- "en": "TargetVISU request Brake Program 150",
- "cn": "Scada发出150#刹车测试指令",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "TargetVISU request Brake Program 150.(diTargetVISU_TriggerBP150=1)",
- "trigger_cn": "TargetVISU要求150号刹车程序。(diTargetVISU_TriggerBP198=1)",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "TargetVISU do not request Brake Program 198.(diTargetVISU_TriggerBP198=0)",
- "reset_cn": "TargetVISU没有要求150号刹车程序。(diTargetVISU_TriggerBP198=0)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "210-维护",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "210",
- "brake_state_design": "200"
- },
- "03_09_001": {
- "subsystem": "TurbineStateMachine",
- "name": "SC_TURBINE_AVAILABLE",
- "en": "Turbine has no brake program",
- "cn": "风机正常运行",
- "powerup_delay": "T#30s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "There is no statuscode active, which activates a brake program.(giBPLevel = CON_iBrakeProgram_0)",
- "trigger_cn": "风机正常运行(无任何刹车程序运行)。(giBPLevel = CON_iBrakeProgram_0)",
- "set_delay": "T#5s",
- "yp": "0",
- "reset_en": "There is a statuscode active, which activates a brake program.(giBPLevel ≠ CON_iBrakeProgram_0)",
- "reset_cn": "风机没有正常运行(有某刹车程序运行)。(giBPLevel ≠ CON_iBrakeProgram_0)",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "69-启动",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "69",
- "brake_state_design": "0"
- },
- "03_09_008": {
- "subsystem": "TurbineStateMachine",
- "name": "OC_ManualTurbineControlActive",
- "en": "Manual control of the turbine is activated by parameter via TargetVISU",
- "cn": "Scada发出手动控制风机指令",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Manual control of the turbine is activated by parameter via TargetVISU.(gbReleaseManualControl=1)",
- "trigger_cn": "TargetVISU要求手动控制风机。(gbReleaseManualControl=1)",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "Manual control of the turbine is not activated by parameter via TargetVISU.(gbReleaseManualControl=0)",
- "reset_cn": "TargetVISU没有要求手动控制风机。(gbReleaseManualControl=0)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "210-维护",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "210",
- "brake_state_design": "0"
- },
- "03_09_011": {
- "subsystem": "TurbineStateMachine",
- "name": "SC_TimeOut_BP51",
- "en": "Brake program 51 lasts too long",
- "cn": "51号刹车模式时间过长",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "WTG is in BP51 Below conditions are fullfilled:(Condition1 AND Condition2 AND Condition3 OR Condition4) ) _x000D_ Condition1:WTG is not in PitchMove mode giTurbineOperationMode <> CON_iPitchMove_x000D_ Condition2:WTG is not in PitchIdel Mode giTurbineOperationMode <> CON_iPitchIdealing_x000D_ Condition3:Generator Speed exceeds given parameter。grGenSpeedForProcess_100ms > PAR_rGenSpeedSetValueBrakeModeVanePos_x000D_ Condition4:1-sec-mean-value of 3 blade angles below given parameter。(grPitchAngle1Blade1_1sec < rTargetPosition)_x000D_ AND (grPitchAngle1Blade2_1sec < rTargetPosition)_x000D_ AND (grPitchAngle1Blade3_1sec < rTargetPosition)_x000D_ Condition5:mean value of 3 blade angle exceeds given parameter_x000D_ grPitchAngle_1sec > rTargetPosition_x000D_ rTargetPosition:= (PAR_rPitchAngleSetValueVanePosition - PAR_rDiffForSetValuePitchReached-4);",
- "trigger_cn": "风机在51号刹车时,满足以下条件:((Condition1 AND Condition2 AND Condition3 OR Condition4) ) _x000D_ Condition1:风机不在变浆模式 giTurbineOperationMode <> CON_iPitchMove_x000D_ Condition2:风机不在PitchIdel模式giTurbineOperationMode <> CON_iPitchIdealing_x000D_ Condition3:发电机速度大于给定参数。grGenSpeedForProcess_100ms > PAR_rGenSpeedSetValueBrakeModeVanePos_x000D_ Condition4:3个桨叶的一秒平均值小于指定值。(grPitchAngle1Blade1_1sec < rTargetPosition)_x000D_ AND (grPitchAngle1Blade2_1sec < rTargetPosition)_x000D_ AND (grPitchAngle1Blade3_1sec < rTargetPosition)_x000D_ Condition5:3个桨叶的平均值大于指定值_x000D_ grPitchAngle_1sec > rTargetPosition_x000D_ rTargetPosition:= (PAR_rPitchAngleSetValueVanePosition - PAR_rDiffForSetValuePitchReached-4);",
- "set_delay": "PAR_tTimeOutBrakeMode51",
- "yp": "0",
- "reset_en": "WTG is not in BP51,or when WTG in BP51,Below conditions are fullfilled:(NOT(Condition1 AND Condition2 AND Condition3 OR Condition4) ) AND Condition5_x000D_ Condition1:WTG is not in PitchMove mode giTurbineOperationMode <> CON_iPitchMove_x000D_ Condition2:WTG is not in PitchIdel Mode giTurbineOperationMode <> CON_iPitchIdealing_x000D_ Condition3:Generator Speed exceeds given parameter。grGenSpeedForProcess_100ms > PAR_rGenSpeedSetValueBrakeModeVanePos_x000D_ Condition4:1-sec-mean-value of 3 blade angles below given parameter。(grPitchAngle1Blade1_1sec < rTargetPosition)_x000D_ AND (grPitchAngle1Blade2_1sec < rTargetPosition)_x000D_ AND (grPitchAngle1Blade3_1sec < rTargetPosition)_x000D_ Condition5:mean value of 3 blade angle exceeds given parameter_x000D_ grPitchAngle_1sec > rTargetPosition_x000D_ rTargetPosition:= (PAR_rPitchAngleSetValueVanePosition - PAR_rDiffForSetValuePitchReached-4);",
- "reset_cn": "风机不在51号刹车,或者风机处于51号刹车时,满足以下条件:(NOT(Condition1 AND Condition2 AND Condition3 OR Condition4) ) AND Condition5_x000D_ Condition1:风机不在变浆模式 giTurbineOperationMode <> CON_iPitchMove_x000D_ Condition2:风机不在PitchIdel模式giTurbineOperationMode <> CON_iPitchIdealing_x000D_ Condition3:发电机速度大于给定参数。grGenSpeedForProcess_100ms > PAR_rGenSpeedSetValueBrakeModeVanePos_x000D_ Condition4:3个桨叶的一秒平均值小于指定值。(grPitchAngle1Blade1_1sec < rTargetPosition)_x000D_ AND (grPitchAngle1Blade2_1sec < rTargetPosition)_x000D_ AND (grPitchAngle1Blade3_1sec < rTargetPosition)_x000D_ Condition5:3个桨叶的平均值大于指定值_x000D_ grPitchAngle_1sec > rTargetPosition_x000D_ rTargetPosition:= (PAR_rPitchAngleSetValueVanePosition - PAR_rDiffForSetValuePitchReached-4);",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "100"
- },
- "03_09_012": {
- "subsystem": "TurbineStateMachine",
- "name": "SC_TimeOut_BP100",
- "en": "Brake program 100 lasts too long",
- "cn": "100号刹车模式时间过长",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "WTG is in BP100, below conditions are fullfilled:(Condition1 OR Condition2 ) _x000D_ Condition1:Generator Speed exceeds given parameter。grGenSpeedForProcess_100ms > PAR_rGenSpeedSetValueBrakeModeVanePos_x000D_ Condition2:1-sec-mean-value of 3 blade angles below given parameter。(grPitchAngle1Blade1_1sec < rTargetPosition)_x000D_ AND (grPitchAngle1Blade2_1sec < rTargetPosition)_x000D_ AND (grPitchAngle1Blade3_1sec < rTargetPosition)_x000D_",
- "trigger_cn": "风机在100号刹车时,满足以下条件:(Condition1 OR Condition2) _x000D_ Condition1:发电机速度大于给定参数grGenSpeedForProcess_100ms > PAR_rGenSpeedSetValueBrakeModeVanePos_x000D_ Condition2:3个桨叶的一秒平均值小于指定值。(grPitchAngle1Blade1_1sec < rTargetPosition)_x000D_ AND (grPitchAngle1Blade2_1sec < rTargetPosition)_x000D_ AND (grPitchAngle1Blade3_1sec < rTargetPosition)_x000D_",
- "set_delay": "PAR_tTimeOutBrakeMode100",
- "yp": "0",
- "reset_en": "WTG is not in BP100 mode, or When WTG is in BP100, below conditions are fullfilled:NOT(Condition1 OR Condition2 ) _x000D_ Condition1:Generator Speed exceeds given parameter。grGenSpeedForProcess_100ms > PAR_rGenSpeedSetValueBrakeModeVanePos_x000D_ Condition2:1-sec-mean-value of 3 blade angles below given parameter。(grPitchAngle1Blade1_1sec < rTargetPosition)_x000D_ AND (grPitchAngle1Blade2_1sec < rTargetPosition)_x000D_ AND (grPitchAngle1Blade3_1sec < rTargetPosition)_x000D_",
- "reset_cn": "风机不在100号刹车,或者风机在100号刹车时,满足以下条件:NOT(Condition1 OR Condition2) _x000D_ Condition1:发电机速度大于给定参数grGenSpeedForProcess_100ms > PAR_rGenSpeedSetValueBrakeModeVanePos_x000D_ Condition2:3个桨叶的一秒平均值小于指定值。(grPitchAngle1Blade1_1sec < rTargetPosition)_x000D_ AND (grPitchAngle1Blade2_1sec < rTargetPosition)_x000D_ AND (grPitchAngle1Blade3_1sec < rTargetPosition)_x000D_",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "198"
- },
- "03_09_013": {
- "subsystem": "TurbineStateMachine",
- "name": "SC_TimeOut_BP50",
- "en": "Brake program 50 lasts too long",
- "cn": "50号刹车模式时间过长",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "PAR_tTimeOutBrakeMode50",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "03_09_105": {
- "subsystem": "TurbineStateMachine",
- "name": "OC_DelayRestartActive",
- "en": "Turbine stays in restart delay from brake program",
- "cn": "风机处于故障后允许复位延迟过程中",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "When a brake program was closed successfull.(giTurbineOperationMode <= CON_iBrakeMode50)",
- "trigger_cn": "在成功的关闭制动过程中。(giTurbineOperationMode <= CON_iBrakeMode50)",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "When a brake program was not closed successfull.(giTurbineOperationMode > CON_iBrakeMode50)",
- "reset_cn": "没有成功的关闭制动过程中。(giTurbineOperationMode > CON_iBrakeMode50)",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "03_09_110": {
- "subsystem": "TurbineStateMachine",
- "name": "OC_ActivatePitchMove",
- "en": "Activate pitch move mode",
- "cn": "变桨自润滑启用",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The difference between the blade angles(100ms) is less than the limit given by parameter, Turbine operation mode is grid operation and pitch move is finished.(grPitchAngle_100ms < (PAR_rEndpositionPitchZeroDegrees + PAR_rPitchMoveLimit) AND giTurbineOperationMode=CON_iGridOperation AND gbPitchMoveFinished=1)",
- "trigger_cn": "100毫秒钟前后桨叶角度差小于设定值,且风机运行在并网发电状态,变桨动作已完成。(grPitchAngle_100ms < (PAR_rEndpositionPitchZeroDegrees + PAR_rPitchMoveLimit) AND giTurbineOperationMode=CON_iGridOperation AND gbPitchMoveFinished=1)",
- "set_delay": "PAR_tMaxTimeWithoutPitchMove",
- "yp": "0",
- "reset_en": "Pitch move is finished, and the difference between the blade angles(100ms) is more than the limit given by parameter, or Turbine operation mode is not grid operation. (gbPitchMoveFinished=1 AND (grPitchAngle_100ms > (PAR_rEndpositionPitchZeroDegrees + PAR_rPitchMoveLimit) OR giTurbineOperationMode≠CON_iGridOperation))",
- "reset_cn": "变桨动作已完成,且100毫秒钟前后桨叶角度差大于设定值或风机不运行在并网发电状态。(gbPitchMoveFinished=1 AND (grPitchAngle_100ms > (PAR_rEndpositionPitchZeroDegrees + PAR_rPitchMoveLimit) OR giTurbineOperationMode≠CON_iGridOperation))",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "03_09_111": {
- "subsystem": "TurbineStateMachine",
- "name": "SC_ForceSelfTestEvery720h",
- "en": "Activate selftest every 720h",
- "cn": "720小时强制自检",
- "powerup_delay": "T#10s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "When turbine operate in grid for 720h, then force turbine stop and have a selftest before turbine started.(gbSelftestAfterGapTime=0)",
- "trigger_cn": "当风机并网运作720小时,需要强迫停止并自检。(gbSelftestAfterGapTime=0)",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "When turbine operate in grid for less than 720h.(gbSelftestAfterGapTime=1)",
- "reset_cn": "当风机并网运作达不到720小时。(gbSelftestAfterGapTime=1)",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "03_09_114": {
- "subsystem": "TurbineStateMachine",
- "name": "SC_TowerResonanceModeTimeOut",
- "en": "Staying in resonance range too long during speed up",
- "cn": "升速过程中处于共振区时间过长",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Turbine operation mode is RunUpToExcitation or TrundleMode, and staying in resonance range too long.((giTurbineOperationMode = CON_iRunUpToExcitation OR giTurbineOperationMode=CON_iTrundleMode) AND PAR_bTowerResonanceMode=1 AND (grGenSpeedForProcess>PAR_rTowerResoGenSpeedDown AND grGenSpeedForProcess<PAR_rTowerResoGenSpeedUp))",
- "trigger_cn": "风机在加速过程,且处于共振区时间过长。((giTurbineOperationMode = CON_iRunUpToExcitation OR giTurbineOperationMode=CON_iTrundleMode) AND PAR_bTowerResonanceMode=1 AND (grGenSpeedForProcess>PAR_rTowerResoGenSpeedDown AND grGenSpeedForProcess<PAR_rTowerResoGenSpeedUp))",
- "set_delay": "PAR_tResonanceModeTimeMax",
- "yp": "0",
- "reset_en": "Turbine operation mode is not RunUpToExcitation and TrundleMode, or not staying in resonance range too long.((giTurbineOperationMode ≠ CON_iRunUpToExcitation AND giTurbineOperationMode≠CON_iTrundleMode) OR PAR_bTowerResonanceMode≠1 OR (grGenSpeedForProcess<PAR_rTowerResoGenSpeedDown OR grGenSpeedForProcess>PAR_rTowerResoGenSpeedUp))",
- "reset_cn": "风机不在加速过程,或处于共振区时间没有过长。((giTurbineOperationMode ≠ CON_iRunUpToExcitation AND giTurbineOperationMode≠CON_iTrundleMode) OR PAR_bTowerResonanceMode≠1 OR (grGenSpeedForProcess<PAR_rTowerResoGenSpeedDown OR grGenSpeedForProcess>PAR_rTowerResoGenSpeedUp))",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "51"
- },
- "03_09_120": {
- "subsystem": "TurbineStateMachine",
- "name": "OC_TurbineHeatingMode",
- "en": "WTG is heating up",
- "cn": "风机暖机模式",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "OC_ControlCabinetHeatingMode_x000D_ OR OC_ConverterHeatingModeHardWire_x000D_ OR OC_ConverterHeatingModeCANBus_x000D_ OR OC_PitchHeatingMode_x000D_ OR OC_GearboxHeatingMode",
- "trigger_cn": "任何一个子系统处于暖机模式",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "no subsystem is in heating mode",
- "reset_cn": "没有子系统处于暖机模式",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "50"
- },
- "04_10_001": {
- "subsystem": "YawSystem",
- "name": "SC_YawLubricationGreasePressureHigh",
- "en": "",
- "cn": "偏航润滑油脂压力过高",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_10_002": {
- "subsystem": "YawSystem",
- "name": "SC_YawLubricationGreaseLevelLow",
- "en": "",
- "cn": "偏航润滑油脂油位过低",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_10_003": {
- "subsystem": "YawSystem",
- "name": "SC_MotorProtection_YawMotor5",
- "en": "The motor protection for yaw motor 5 has tripped",
- "cn": "偏航系统5号电机热保护继电器触发",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The motor protection for yaw motor 5 has tripped.(gbDI_NacelleMotorProtYawMotor5=0)",
- "trigger_cn": "偏航系统5号电机保护系统发生故障。(gbDI_NacelleMotorProtYawMotor5=0)",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "The motor protection for yaw motor 5 is OK.(gbDI_NacelleMotorProtYawMotor5=1)",
- "reset_cn": "偏航系统5号电机保护系统故障清除。(gbDI_NacelleMotorProtYawMotor5=1)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_10_004": {
- "subsystem": "YawSystem",
- "name": "SC_MotorProtection_YawMotor6",
- "en": "The motor protection for yaw motor 6 has tripped",
- "cn": "偏航系统6号电机热保护继电器触发",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The motor protection for yaw motor 6 has tripped.(gbDI_NacelleMotorProtYawMotor6=0)",
- "trigger_cn": "偏航系统6号电机保护系统发生故障。(gbDI_NacelleMotorProtYawMotor6=0)",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "The motor protection for yaw motor 6 is OK.(gbDI_NacelleMotorProtYawMotor6=1)",
- "reset_cn": "偏航系统6号电机保护系统故障清除。(gbDI_NacelleMotorProtYawMotor6=1)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_10_005": {
- "subsystem": "YawSystem",
- "name": "SC_Yaw_Motor_1_MCB",
- "en": "The yaw motor 1 MCB has been activated",
- "cn": "1#偏航电机空开跳开",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_10_006": {
- "subsystem": "YawSystem",
- "name": "SC_Yaw_Motor_2_MCB",
- "en": "The yaw motor 2 MCB has been activated",
- "cn": "2#偏航电机空开跳开",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_10_007": {
- "subsystem": "YawSystem",
- "name": "SC_Yaw_Motor_3_MCB",
- "en": "The yaw motor 3 MCB has been activated",
- "cn": "3#偏航电机空开跳开",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_10_008": {
- "subsystem": "YawSystem",
- "name": "SC_Yaw_Motor_4_MCB",
- "en": "The yaw motor 4 MCB has been activated",
- "cn": "4#偏航电机空开跳开",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_10_009": {
- "subsystem": "YawSystem",
- "name": "SC_Yaw_Motor_5_MCB",
- "en": "The yaw motor 5 MCB has been activated",
- "cn": "5#偏航电机空开跳开",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_10_010": {
- "subsystem": "YawSystem",
- "name": "SC_Yaw_Motor_6_MCB",
- "en": "The yaw motor 6 MCB has been activated",
- "cn": "6#偏航电机空开跳开",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_10_011": {
- "subsystem": "YawSystem",
- "name": "SC_Yaw_Stopped_MaxNum_Failure",
- "en": "",
- "cn": "偏航电机失效数量过大",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#100ms",
- "yp": "100",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "50-偏航警告",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "50",
- "brake_state_design": "0"
- },
- "04_10_012": {
- "subsystem": "YawSystem",
- "name": "SC_YawMotorsHeaterForceMode",
- "en": "",
- "cn": "偏航加热器强制模式开启",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#50ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_10_013": {
- "subsystem": "YawSystem",
- "name": "SC_YawMotorsHeaterManualMode",
- "en": "",
- "cn": "偏航加热器手动模式开启",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#50ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_10_014": {
- "subsystem": "YawSystem",
- "name": "SC_YawForceMode",
- "en": "",
- "cn": "偏航强制模式开启",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#50ms",
- "yp": "30",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_12_016": {
- "subsystem": "ConverterContainer",
- "name": "SC_Converter_MasterSlaveConfigureNotFinished",
- "en": "",
- "cn": "变频器主从配置没有完成",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_16_001": {
- "subsystem": "TurbineStateMachine",
- "name": "SC_TimeOut_Selftest1",
- "en": "Self Test1 Timeout",
- "cn": "自检1运行超时",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "PAR_tTimeoutSelftest1",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_16_002": {
- "subsystem": "TurbineStateMachine",
- "name": "SC_TimeOut_Selftest2",
- "en": "Self Test2 Timeout",
- "cn": "自检2运行超时",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "PAR_tTimeoutSelftest2",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_16_003": {
- "subsystem": "TurbineStateMachine",
- "name": "SC_TimeOut_Selftest3",
- "en": "Self Test3 Timeout",
- "cn": "自检3运行超时",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "PAR_tTimeoutSelftest3",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_16_004": {
- "subsystem": "TurbineStateMachine",
- "name": "SC_TimeOut_Selftest4",
- "en": "Self Test4 Timeout",
- "cn": "自检4运行超时",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "PAR_tTimeoutSelftest4",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_16_005": {
- "subsystem": "TurbineStateMachine",
- "name": "SC_TimeOut_StartMode",
- "en": "Start Mode Timeout",
- "cn": "启动模式运行超时",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "PAR_tTimeoutStartMode",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_16_006": {
- "subsystem": "TurbineStateMachine",
- "name": "SC_TimeOut_CutInMode",
- "en": "CutIn Mode Timeout",
- "cn": "切入并网超时",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "PAR_tTimeoutCutInMode",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_16_007": {
- "subsystem": "TurbineStateMachine",
- "name": "SC_NacellePositionInSector1",
- "en": "",
- "cn": "机舱位置处在扇区1",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "79-无限制发电",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_16_008": {
- "subsystem": "TurbineStateMachine",
- "name": "SC_NacellePositionInSector2",
- "en": "",
- "cn": "机舱位置处在扇区2",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "79-无限制发电",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_16_009": {
- "subsystem": "TurbineStateMachine",
- "name": "SC_NacellePositionInSector3",
- "en": "",
- "cn": "机舱位置处在扇区3",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "79-无限制发电",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_16_010": {
- "subsystem": "TurbineStateMachine",
- "name": "SC_NacellePositionInSector4",
- "en": "",
- "cn": "机舱位置处在扇区4",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "79-无限制发电",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_02_132": {
- "subsystem": "PitchSystem",
- "name": "SC_Blade1PositionCheckAlarm",
- "en": "Blade1 position check alarm",
- "cn": "1号桨叶角度检查偏差过大警告",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "I",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "165",
- "brake_state_design": "0"
- },
- "04_02_133": {
- "subsystem": "PitchSystem",
- "name": "SC_Blade2PositionCheckAlarm",
- "en": "Blade2 position check alarm",
- "cn": "2号桨叶角度检查偏差过大警告",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "I",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "165",
- "brake_state_design": "0"
- },
- "04_02_134": {
- "subsystem": "PitchSystem",
- "name": "SC_Blade3PositionCheckAlarm",
- "en": "Blade3 position check alarm",
- "cn": "3号桨叶角度检查偏差过大警告",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "I",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "165",
- "brake_state_design": "0"
- },
- "04_02_135": {
- "subsystem": "PitchSystem",
- "name": "SC_Pitch230VLineSupplyCBTrip",
- "en": "PitchSystem 230V Supply CB Tripped",
- "cn": "230V信号线供电CB跳开",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "198"
- },
- "04_02_136": {
- "subsystem": "PitchSystem",
- "name": "SC_PitchBackUpTest",
- "en": "PitchSystem in BackUp Test Mode",
- "cn": "远程设定变桨后备电源自检测试",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "30-待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "30",
- "brake_state_design": "198"
- },
- "04_02_137": {
- "subsystem": "PitchSystem",
- "name": "SC_PitchForceMode",
- "en": "PitchSystem in Force Mode",
- "cn": "变桨系统处于强制模式,桨角可任意给定",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "A",
- "alarm": "True",
- "level": "30-待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "30",
- "brake_state_design": "51"
- },
- "04_02_138": {
- "subsystem": "PitchSystem",
- "name": "SC_PitchEncoderSet",
- "en": "PitchSystem Encoder Set Enabled",
- "cn": "变桨系统设置编码器",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "30-待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "30",
- "brake_state_design": "198"
- },
- "04_02_139": {
- "subsystem": "PitchSystem",
- "name": "SC_PitchCANComErrorTooFrequent",
- "en": "PitchSystem CAN communication error tow frequent",
- "cn": "变桨CAN通讯报警频繁",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "03_06_020": {
- "subsystem": "LogSystem",
- "name": "SC_HarddiskOverflow",
- "en": "Number of error trace logs, written to hard disc, overflows",
- "cn": "CF卡中的Tracelog过多",
- "powerup_delay": "T#30s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "When the number of trace logs, written on hard disc exceeds the maximum number given by a parameter.(giNumberOfTraceLogs > PAR_iMaxNumberOfTraceLogs)",
- "trigger_cn": "当跟踪日志,写入硬盘的故障日志数量高于了最大给定值。(giNumberOfTraceLogs > PAR_iMaxNumberOfTraceLogs)",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "When the number of trace logs, written on hard disc falls below the maximum number given by a parameter.(giNumberOfTraceLogs <= PAR_iMaxNumberOfTraceLogs)",
- "reset_cn": "当跟踪日志,写入硬盘的故障日志数量不高于了最大给定值。(giNumberOfTraceLogs < PAR_iMaxNumberOfTraceLogs)",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "03_06_008": {
- "subsystem": "PLCSystem",
- "name": "SC_DivisionByZero",
- "en": "Division by zero is detected",
- "cn": "除数为零错误",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "When a division by zero is detected.(gbDivisionByZero=1)",
- "trigger_cn": "当发现除数为零时。(gbDivisionByZero=1)",
- "set_delay": "T#50ms",
- "yp": "0",
- "reset_en": "When a division by zero is not detected.(gbDivisionByZero=0)",
- "reset_cn": "当没有发现除数为零时。(gbDivisionByZero=0)",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "198"
- },
- "03_06_009": {
- "subsystem": "PLCSystem",
- "name": "SC_MaxCycleTimeMainPLCTask",
- "en": "PLC main task execution exceeds its cycle time",
- "cn": "PLC-Task1任务执行超时",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "When the MAIN Task exceeds its cycle time.(garrTaskInfo[1].bCycleTimeExceeded =1)",
- "trigger_cn": "PLC主任务执行时间高于其执行周期。(garrTaskInfo[1].bCycleTimeExceeded =1)",
- "set_delay": "T#50ms",
- "yp": "0",
- "reset_en": "When the MAIN Task falls below its cycle time.(garrTaskInfo[1].bCycleTimeExceeded =0)",
- "reset_cn": "PLC主任务执行时间不高于其执行周期。(garrTaskInfo[1].bCycleTimeExceeded =0)",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "03_06_012": {
- "subsystem": "PLCSystem",
- "name": "SC_MaxCycleTimeFASTTask",
- "en": "PLC fast task execution exceeds its cycle time",
- "cn": "PLC-Task2任务执行超时",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "PLC fast task execution exceeds its cycle time.(garrTaskInfo[2].bCycleTimeExceeded=1)",
- "trigger_cn": "PLC快速任务执行时间高于其执行周期。(garrTaskInfo[2].bCycleTimeExceeded=1)",
- "set_delay": "T#50ms",
- "yp": "0",
- "reset_en": "PLC fast task execution falls below its cycle time.(garrTaskInfo[2].bCycleTimeExceeded=0)",
- "reset_cn": "PLC快速任务执行时间在其执行周期以内。(garrTaskInfo[2].bCycleTimeExceeded=0)",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_21_008": {
- "subsystem": "PLCSystem",
- "name": "SC_MaxCycleTimeTask3",
- "en": "Task3 Exceed time",
- "cn": "PLC-Task3任务执行超时",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#50ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "03_06_013": {
- "subsystem": "PLCSystem",
- "name": "SC_RepFaultMaxCycleTimeTask",
- "en": "The faults, PLC task execution exceeds cycle time, have repeated",
- "cn": "PLC-Task1或Task2或Task3任务执行超时故障重复出现",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "When one of the statuscodes for \"cycle time exceeded\" in a given time periode becomes more times TRUE than maximum allowed.(gbRepeat_03_06_012=1 OR gbRepeat_03_06_009=1)",
- "trigger_cn": "PLC主任务或快速任务执行时间高于执行周期故障重复出现。(gbRepeat_03_06_012=1 OR gbRepeat_03_06_009=1)",
- "set_delay": "T#50ms",
- "yp": "0",
- "reset_en": "When no statuscodes for \"cycle time exceeded\" in a given time periode becomes more times TRUE than maximum allowed.(gbRepeat_03_06_012=0 AND gbRepeat_03_06_009=0)",
- "reset_cn": "PLC主任务和快速任务执行时间高于执行周期故障没有重复出现。(gbRepeat_03_06_012=0 AND gbRepeat_03_06_009=0)",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "03_06_123": {
- "subsystem": "PLCSystem",
- "name": "OC_PLCPowerUp",
- "en": "PLC is restarting",
- "cn": "PLC正在启动中",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "After restart of the PLC, independant whether by power up or by system start.(gbPLC_FirstCycleDone=1)",
- "trigger_cn": "PLC正在重启(由上电或系统启动)。(gbPLC_FirstCycleDone=1)",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "PLC is not restarting.(gbPLC_FirstCycleDone=0)",
- "reset_cn": "PLC没有处于重启状态。(gbPLC_FirstCycleDone=0)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "30-待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "30",
- "brake_state_design": "51"
- },
- "03_06_124": {
- "subsystem": "PLCSystem",
- "name": "SC_UpdateModeON",
- "en": "PLC update mode is on by remote command",
- "cn": "远程命令PLC程序升级",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "PLC update mode is on by remote command",
- "trigger_cn": "远程命令PLC程序升级",
- "set_delay": "T#0s",
- "yp": "30",
- "reset_en": "Stopping PLC update mode is on by remote command.(RemComOK_StartStopUpdateMode=0)",
- "reset_cn": "远程命令PLC程序升级停止。(RemComOK_StartStopUpdateMode=0)",
- "reset_mode": "M",
- "type": "A",
- "alarm": "False",
- "level": "250-升级",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "250",
- "brake_state_design": "51"
- },
- "03_06_126": {
- "subsystem": "PLCSystem",
- "name": "SC_RebootPLC",
- "en": "PC reboot is commanded remotely(Operating System, TwinCAT, Application)",
- "cn": "远程命令主控制器重启(操作系统,TwinCAT,应用程序)",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "When a reboot of the PC is activated by a high level engineering command.(RemComOK_RebootPC=1)",
- "trigger_cn": "远程高权限命令PC重启(操作系统,TwinCAT,应用程序)。(RemComOK_RebootPC=1)",
- "set_delay": "T#0s",
- "yp": "100",
- "reset_en": "PC reboot is not commanded remotely(Operating System, TwinCAT, Application).(RemComOK_RebootPC=0)",
- "reset_cn": "无远程高权限命令PC重启(操作系统,TwinCAT,应用程序)。(RemComOK_RebootPC=0)",
- "reset_mode": "M",
- "type": "F",
- "alarm": "False",
- "level": "250-升级",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "250",
- "brake_state_design": "51"
- },
- "03_06_133": {
- "subsystem": "PLCSystem",
- "name": "SC_ParOutOfRange",
- "en": "Parameter set is out of range",
- "cn": "参数设定超限",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Parmeter set is out of range(gbParOutOfRange=TRUE)",
- "trigger_cn": "参数设定超限",
- "set_delay": "T#1s",
- "yp": "100",
- "reset_en": "Parameter set is not out of range",
- "reset_cn": "参数设定没有超限",
- "reset_mode": "M",
- "type": "A",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "03_06_135": {
- "subsystem": "PLCSystem",
- "name": "OC_UpdateModeReady",
- "en": "Update Mode is ready",
- "cn": "升级模式准备就绪",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "PLC update mode is on by remote command, the value for generator speed falls below the limit given by parameter, and the difference between the blade angles is more than the limit given by parameter.(RemComOK_StartStopUpdateMode=1 AND (grGenSpeedForProcess_100ms < PAR_rGenSpeedSetValueBrakeModeVanePos) AND (grPitchAngle_1sec >= (PAR_rPitchAngleSetValueVanePosition - PAR_rDiffForSetValuePitchReached))",
- "trigger_cn": "远程命令PLC程序升级,发电机100ms平均速度小于给定值,且1秒钟前后桨叶角度差大于设定值。(RemComOK_StartStopUpdateMode=1 AND (grGenSpeedForProcess_100ms < PAR_rGenSpeedSetValueBrakeModeVanePos) AND (grPitchAngle_1sec >= (PAR_rPitchAngleSetValueVanePosition - PAR_rDiffForSetValuePitchReached))",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "Stopping PLC update mode is on by remote command.(RemComOK_StartStopUpdateMode=0)",
- "reset_cn": "远程命令PLC程序升级停止。(RemComOK_StartStopUpdateMode=0)",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "03_06_018": {
- "subsystem": "PLCSystem",
- "name": "SC_InterruptionEtherCAT",
- "en": "EtherCAT communication has fault",
- "cn": "EtherCAT通讯故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "3",
- "repeat_period": "T#24h",
- "trigger_en": "The EtherCAT communication any fault is detected.(NOT gbEtherCAT_OK)",
- "trigger_cn": "检测到任何EtherCAT通讯错误。(NOT gbEtherCAT_OK)",
- "set_delay": "PAR_tSetDelayForEtherCAT",
- "yp": "0",
- "reset_en": "The EtherCAT communication any fault is not detected.(gbEtherCAT_OK)",
- "reset_cn": "检测不到任何EtherCAT通讯错误。(gbEtherCAT_OK)",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "175-故障停机(强)",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "175",
- "brake_state_design": "100"
- },
- "03_06_035": {
- "subsystem": "PLCSystem",
- "name": "OC_NoCOM_EtherCAT",
- "en": "EtherCAT communication has error",
- "cn": "EtherCAT通讯出错",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "3",
- "repeat_period": "T#60s",
- "trigger_en": "The EtherCAT communication any fault is detected.(gbEtherCAT_OK=0)",
- "trigger_cn": "检测到任何EtherCAT通讯错误。(gbEtherCAT_OK=0)",
- "set_delay": "T#15ms",
- "yp": "0",
- "reset_en": "The EtherCAT communication any error is not detected.(gbEtherCAT_OK=0)",
- "reset_cn": "检测不到任何EtherCAT通讯错误。(gbEtherCAT_OK=1)",
- "reset_mode": "M",
- "type": "A",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "03_06_031": {
- "subsystem": "PLCSystem",
- "name": "SC_RepFault_COM_BKEK_TurbineInternal",
- "en": "The faults of communication with nacelle/towerbase BK1120 or EK1100 have repeated",
- "cn": "塔底EK1100,机舱EK1100或BK1250通讯故障多次出现",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "100"
- },
- "04_21_030": {
- "subsystem": "PLCSystem",
- "name": "SC_RestoreStatisticsFileFailed",
- "en": "Restore Statistics From File Failed",
- "cn": "读取统计量参数文件失败",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "gbRestoreStatisticsFromXMLError",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_21_031": {
- "subsystem": "PLCSystem",
- "name": "SC_RestoreUniqueParFileFailed",
- "en": "Restore Unique Parameter From File Failed",
- "cn": "读取个性化参数文件失败",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "gbRestoreUniquePARFromXMLError",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_21_032": {
- "subsystem": "PLCSystem",
- "name": "SC_RestoreGoldenParFileFailed",
- "en": "Restore Golden Parameter From File Failed",
- "cn": "读取通用性参数文件失败",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "gbRestoreGoldenPARFromXMLError",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_21_033": {
- "subsystem": "PLCSystem",
- "name": "SC_StoreStatisticsFileFailed",
- "en": "Store Statistics To File Failed",
- "cn": "存储统计量参数文件失败",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "gbStoreStatisticsToXMLError",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_21_034": {
- "subsystem": "PLCSystem",
- "name": "SC_StoreUniqueParFileFailed",
- "en": "Store Unique Parameter To File Failed",
- "cn": "存储个性化参数文件失败",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "gbStoreUniquePARToXMLError",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_21_035": {
- "subsystem": "PLCSystem",
- "name": "SC_StoreGoldenParFileFailed",
- "en": "Store Golden Parameter To File Failed",
- "cn": "存储通用性参数文件失败",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "gbStoreGoldenPARToXMLError",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_21_017": {
- "subsystem": "PLCSystem",
- "name": "SC_NoCOM_EK1501Nacelle",
- "en": "Nacelle EK1501 Communication Error",
- "cn": "机舱EK1501通讯故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "3",
- "repeat_period": "T#60s",
- "trigger_en": "di_bWcState_Nacelle_EK1501_1",
- "trigger_cn": "",
- "set_delay": "T#15ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_21_018": {
- "subsystem": "PLCSystem",
- "name": "SC_NoCOM_BK1120Nacelle",
- "en": "Nacelle BK1120 Communication Error",
- "cn": "机舱BK1120通讯故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "3",
- "repeat_period": "T#60s",
- "trigger_en": "di_bWcState_Nacelle_BK1120_1 OR di_bWcState_Nacelle_BK1120_2",
- "trigger_cn": "",
- "set_delay": "T#15ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_21_021": {
- "subsystem": "PLCSystem",
- "name": "SC_NoCOM_EK1252Nacelle",
- "en": "Nacelle EK1252 Communication Error",
- "cn": "机舱EK1252通讯故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "3",
- "repeat_period": "T#60s",
- "trigger_en": "di_bWcState_Nacelle_EL1252",
- "trigger_cn": "",
- "set_delay": "T#15ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_21_024": {
- "subsystem": "PLCSystem",
- "name": "SC_NoCOM_BK1250TowerBase",
- "en": "TowerBase BK1250 Communication Error",
- "cn": "塔底BK1250通讯故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "3",
- "repeat_period": "T#60s",
- "trigger_en": "di_bWcState_Tower_BK1250",
- "trigger_cn": "",
- "set_delay": "T#15ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_21_026": {
- "subsystem": "PLCSystem",
- "name": "SC_NoCOM_EK1501TowerBase",
- "en": "TowerBase EK1501 Communication Error",
- "cn": "塔底EK1501通讯故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "3",
- "repeat_period": "T#60s",
- "trigger_en": "di_bWcState_Tower_EK1501_1 OR di_bWcState_Tower_EK1501_2",
- "trigger_cn": "",
- "set_delay": "T#15ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_21_028": {
- "subsystem": "PLCSystem",
- "name": "SC_NoCOM_EK1501Converter",
- "en": "Converter EK1501 Communication Error",
- "cn": "变频器EK1501通讯故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "3",
- "repeat_period": "T#60s",
- "trigger_en": "di_bWcState_Converter_EK1501",
- "trigger_cn": "",
- "set_delay": "T#15ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "03_06_023": {
- "subsystem": "PLCSystem",
- "name": "SC_NoCOM_BK1250Nacelle",
- "en": "Communication with nacelle BK1120 bus coupler has fault",
- "cn": "机舱BK1250通讯故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "3",
- "repeat_period": "T#60s",
- "trigger_en": "di_bWcState_Nacelle_BK1250",
- "trigger_cn": "",
- "set_delay": "T#15ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "03_06_025": {
- "subsystem": "PLCSystem",
- "name": "SC_NoCOM_EK1100Nacelle",
- "en": "Communication with nacelle EK1100 coupler has fault",
- "cn": "机舱EK1100通讯故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "3",
- "repeat_period": "T#60s",
- "trigger_en": "di_bWcState_Nacelle_EK1100",
- "trigger_cn": "",
- "set_delay": "T#15ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "03_06_036": {
- "subsystem": "PLCSystem",
- "name": "SC_NoCOM_EL6751Nacelle",
- "en": "The communication with PCH sensor has fault",
- "cn": "机舱EL6751通讯故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "di_bWcState_Pitch_CAN_EL6751 OR di_bWcState_PCH_CAN_EL6751",
- "trigger_cn": "",
- "set_delay": "T#15ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "03_06_030": {
- "subsystem": "PLCSystem",
- "name": "SC_NoCOM_EL6731Pitch",
- "en": "Communication with nacelle EL6731 bus coupler has fault",
- "cn": "机舱EL6731通讯故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "3",
- "repeat_period": "T#60s",
- "trigger_en": "di_bWcState_Pitch_Profibus_EL6731",
- "trigger_cn": "",
- "set_delay": "T#15ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "03_06_028": {
- "subsystem": "PLCSystem",
- "name": "SC_NoCOM_EK1100TowerBase",
- "en": "Communication with towerbase EK1100 coupler has fault",
- "cn": "塔底EK1100通讯故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "3",
- "repeat_period": "T#60s",
- "trigger_en": "di_bWcState_Tower_EK1100",
- "trigger_cn": "",
- "set_delay": "T#15ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "03_06_029": {
- "subsystem": "PLCSystem",
- "name": "SC_NoCOM_EL6751Converter",
- "en": "Communication with nacelle EL6751 bus coupler has fault",
- "cn": "变频器EL6751通讯故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "3",
- "repeat_period": "T#60s",
- "trigger_en": "di_bWcState_Conveter_CAN_EL6751_1 OR di_bWcState_Conveter_CAN_EL6751_2",
- "trigger_cn": "",
- "set_delay": "T#15ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_21_015": {
- "subsystem": "PLCSystem",
- "name": "SC_NoCOM_EK1501GCC",
- "en": "GCC EK1501 Communication Error",
- "cn": "GCC-EK1501通讯故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "3",
- "repeat_period": "T#60s",
- "trigger_en": "di_bWcState_GCC_EK1501",
- "trigger_cn": "",
- "set_delay": "T#15ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_21_016": {
- "subsystem": "PLCSystem",
- "name": "SC_NoCOM_BK1250GCC",
- "en": "GCC BK1250 Communication Error",
- "cn": "GCC-BK1250通讯故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "3",
- "repeat_period": "T#60s",
- "trigger_en": "di_bWcState_GCC_BK1250",
- "trigger_cn": "",
- "set_delay": "T#15ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_01_014": {
- "subsystem": "SafetySystem",
- "name": "SC_SoftSafetyChain_Tripped",
- "en": "",
- "cn": "硬件安全链失效,软件安全链动作",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "100",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "200"
- },
- "04_05_045": {
- "subsystem": "Gearbox",
- "name": "SC_FaultAI_GearOilDiffPressureInlineFilter",
- "en": "",
- "cn": "齿轮箱过滤器压差传感器故障",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_05_047": {
- "subsystem": "Gearbox",
- "name": "SC_GBXOilInletPressure_MAX_Stop",
- "en": "",
- "cn": "齿轮箱入口压力过高故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_05_046": {
- "subsystem": "Gearbox",
- "name": "SC_RepFaultGBXOilInletPressure_Stop",
- "en": "",
- "cn": "齿轮箱入口压力过高或过低故障重复出现",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "A",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_09_033": {
- "subsystem": "NacelleSystem",
- "name": "SC_FaultAI_NacelleWindSpeed",
- "en": "",
- "cn": "Thies风向标故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_09_034": {
- "subsystem": "NacelleSystem",
- "name": "SC_FaultAI_Nacelle_Humidity",
- "en": "",
- "cn": "机舱湿度传感器故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_09_035": {
- "subsystem": "NacelleSystem",
- "name": "SC_WindIrisData_NotValid",
- "en": "",
- "cn": "激光雷达数据无效",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_09_036": {
- "subsystem": "NacelleSystem",
- "name": "OC_WindIrisForControl",
- "en": "",
- "cn": "当前采用激光雷达进行偏航控制",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_04_014": {
- "subsystem": "Drivetrain",
- "name": "SC_FaultAI_RotorSpeedFromOverspeedRelay",
- "en": "",
- "cn": "过速传感器故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_21_036": {
- "subsystem": "PLCSystem",
- "name": "SC_RestoreStorageFileFailed",
- "en": "Restore Storage Variables From File Failed",
- "cn": "读取掉电保存变量文件失败",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "gbRestoreGoldenPARFromXMLError",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_21_037": {
- "subsystem": "PLCSystem",
- "name": "SC_StoreStorageFileFailed",
- "en": "Store Storage Variables To File Failed",
- "cn": "存储掉电保存变量文件失败",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "gbStoreStatisticsToXMLError",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_12_018": {
- "subsystem": "ConverterContainer",
- "name": "SC_TorqeuForceMode",
- "en": "",
- "cn": "扭矩强制模式开启,扭矩可以随意设定",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_07_001": {
- "subsystem": "HSBrakeSystem",
- "name": "SC_BrakePressureHighUnderProduction",
- "en": "",
- "cn": "发电时刹车压力高故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "F",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "100"
- },
- "04_07_002": {
- "subsystem": "HSBrakeSystem",
- "name": "SC_HSBrakeIsWorking",
- "en": "",
- "cn": "高速刹车投入中",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_13_005": {
- "subsystem": "Cabinet",
- "name": "SC_FaultInputAirPressure",
- "en": "Air Pressure Sensor Fault",
- "cn": "大气压力传感器故障",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_15_001": {
- "subsystem": "MeasurementSystem",
- "name": "SC_PCH_HubBlade1_PeakAlert",
- "en": "The alert vibration level for the hub blade 1 peak as been triggered",
- "cn": "桨叶1振动峰值过高警告",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#10ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_15_002": {
- "subsystem": "MeasurementSystem",
- "name": "SC_PCH_HubBlade1_PeakDanger",
- "en": "The danger vibration level for the hub blade 1 peak as been triggered",
- "cn": "桨叶1振动峰值过高危险警告",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#10ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "100"
- },
- "04_15_003": {
- "subsystem": "MeasurementSystem",
- "name": "SC_PCH_HubBlade1_PPAlert",
- "en": "The alert vibration level for the hub blade 1 PP as been triggered",
- "cn": "桨叶1峰-峰值过高警告",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#10ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_15_004": {
- "subsystem": "MeasurementSystem",
- "name": "SC_PCH_HubBlade1_PPDanger",
- "en": "The danger vibration level for the hub blade 1 PP as been triggered",
- "cn": "桨叶1峰-峰值过高危险警告",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#10ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "100"
- },
- "04_15_005": {
- "subsystem": "MeasurementSystem",
- "name": "SC_PCH_HubBlade2_PeakAlert",
- "en": "The alert vibration level for the hub blade 2 peak as been triggered",
- "cn": "桨叶2振动峰值过高警告",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#10ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_15_006": {
- "subsystem": "MeasurementSystem",
- "name": "SC_PCH_HubBlade2_PeakDanger",
- "en": "The danger vibration level for the hub blade 2 peak as been triggered",
- "cn": "桨叶2振动峰值过高危险警告",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#10ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "100"
- },
- "04_15_007": {
- "subsystem": "MeasurementSystem",
- "name": "SC_PCH_HubBlade2_PPAlert",
- "en": "The alert vibration level for the hub blade 2 PP as been triggered",
- "cn": "桨叶2峰-峰值过高警告",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#10ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_15_008": {
- "subsystem": "MeasurementSystem",
- "name": "SC_PCH_HubBlade2_PPDanger",
- "en": "The danger vibration level for the hub blade 2 PP as been triggered",
- "cn": "桨叶2峰-峰值过高危险警告",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#10ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "100"
- },
- "04_15_009": {
- "subsystem": "MeasurementSystem",
- "name": "SC_PCH_HubBlade3_PeakAlert",
- "en": "The alert vibration level for the hub blade 3 peak as been triggered",
- "cn": "桨叶3振动峰值过高警告",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#10ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_15_010": {
- "subsystem": "MeasurementSystem",
- "name": "SC_PCH_HubBlade3_PeakDanger",
- "en": "The danger vibration level for the hub blade 3 peak as been triggered",
- "cn": "桨叶3振动峰值过高危险警告",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#10ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "100"
- },
- "04_15_011": {
- "subsystem": "MeasurementSystem",
- "name": "SC_PCH_HubBlade3_PPAlert",
- "en": "The alert vibration level for the hub blade 3 PP as been triggered",
- "cn": "桨叶3峰-峰值过高警告",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#10ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_15_012": {
- "subsystem": "MeasurementSystem",
- "name": "SC_PCH_HubBlade3_PPDanger",
- "en": "The danger vibration level for the hub blade 3 PP as been triggered",
- "cn": "桨叶3峰-峰值过高危险警告",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#10ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "100"
- },
- "04_15_013": {
- "subsystem": "MeasurementSystem",
- "name": "SC_PCH_HubFFTBlade1_Alert",
- "en": "The alarm vibration level for the hub FFT blade 1 as been triggered",
- "cn": "桨叶1频谱强度异常警告",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#10ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_15_014": {
- "subsystem": "MeasurementSystem",
- "name": "SC_PCH_HubFFTBlade1_Danger",
- "en": "The alarm vibration level for the hub FFT blade 1 as been triggered",
- "cn": "桨叶1频谱强度异常危险警告",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "3",
- "repeat_period": "T#3h",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#10ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "100"
- },
- "04_15_015": {
- "subsystem": "MeasurementSystem",
- "name": "SC_PCH_HubFFTBlade2_Alert",
- "en": "The alarm vibration level for the hub FFT blade 2 as been triggered",
- "cn": "桨叶2频谱强度异常警告",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#10ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_15_016": {
- "subsystem": "MeasurementSystem",
- "name": "SC_PCH_HubFFTBlade2_Danger",
- "en": "The alarm vibration level for the hub FFT blade 2 as been triggered",
- "cn": "桨叶2频谱强度异常危险警告",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "3",
- "repeat_period": "T#3h",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#10ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "100"
- },
- "04_15_017": {
- "subsystem": "MeasurementSystem",
- "name": "SC_PCH_HubFFTDangerRepeat",
- "en": "Blades FFT danger alarms repeat.",
- "cn": "桨叶频谱危险警告反复出现",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#10ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_15_018": {
- "subsystem": "MeasurementSystem",
- "name": "SC_PCH_HubBadDataDetected",
- "en": "Error on communication with blade pch",
- "cn": "主控系统读得的叶片PCH震动值长时间不刷新",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#30s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_15_019": {
- "subsystem": "MeasurementSystem",
- "name": "OC_PCH_HubScaleFactorEqualZero",
- "en": "PCH Scale Factor Equal Zero",
- "cn": "叶片PCH读取的振动值系数为0",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_08_101": {
- "subsystem": "Generator",
- "name": "SC_FaultPofibusWCSG",
- "en": "Fault, Profibus communication of main control system with water cooling system for generator",
- "cn": "主控系统与发电机水冷系统Profibus通讯故障",
- "powerup_delay": "T#2m",
- "disable_level": "100",
- "repeat_n": "3",
- "repeat_period": "T#60s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_08_102": {
- "subsystem": "Generator",
- "name": "SC_EmergencyModeOfWCSG",
- "en": "Emergency shutdown of water cooling system for generator , activated by pressing the button",
- "cn": "发电机水冷系统急停被拍下触发了紧急停机",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "3",
- "repeat_period": "T#60s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_08_103": {
- "subsystem": "Generator",
- "name": "SC_PumpOverLoadOfWCSG",
- "en": "Pump overloaded, water cooling system for generator",
- "cn": "发电机水冷系统循环泵过载",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "3",
- "repeat_period": "T#60s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_08_104": {
- "subsystem": "Generator",
- "name": "SC_TempHighOfWCSG",
- "en": "Overtemperature, water cooling system for generator",
- "cn": "发电机水冷系统过温",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "3",
- "repeat_period": "T#60s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_08_105": {
- "subsystem": "Generator",
- "name": "SC_PreHighOfWCSG",
- "en": "Too high pressure, water cooling system for generator",
- "cn": "发电机水冷系统过压",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "3",
- "repeat_period": "T#60s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_08_106": {
- "subsystem": "Generator",
- "name": "SC_PreLowOfWCSG",
- "en": "Too low pressure, water cooling system for generator",
- "cn": "发电机水冷系统压力过低",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "3",
- "repeat_period": "T#60s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_08_107": {
- "subsystem": "Generator",
- "name": "SC_NotReadyOfWCSG",
- "en": "Water cooling system for generator not ready to operate",
- "cn": "发电机水冷系统没有做好运行准备",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "3",
- "repeat_period": "T#60s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_08_108": {
- "subsystem": "Generator",
- "name": "SC_FaultStatusOfWCSG",
- "en": "Fault mode, water cooling system for generator",
- "cn": "发电机水冷系统故障模式",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "3",
- "repeat_period": "T#60s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_08_109": {
- "subsystem": "Generator",
- "name": "SC_TempLowOfWCSG",
- "en": "Too low temperature, water cooling system for generator",
- "cn": "发电机水冷系统温度过低",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "3",
- "repeat_period": "T#60s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_08_110": {
- "subsystem": "Generator",
- "name": "SC_TempSignalErrorOfWCSG",
- "en": "Temperature signal error, water cooling system for generator",
- "cn": "发电机水冷系统温度信号错误",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "3",
- "repeat_period": "T#60s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_08_111": {
- "subsystem": "Generator",
- "name": "SC_PreSignalErrorOfWCSG",
- "en": "Pressure signal error, water cooling system for generator",
- "cn": "发电机水冷系统压力信号错误",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "3",
- "repeat_period": "T#60s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_08_112": {
- "subsystem": "Generator",
- "name": "SC_ServiceModeOfWCSG",
- "en": "Local mode, water cooling system for generator",
- "cn": "发电机水冷系统本地模式",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "3",
- "repeat_period": "T#60s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_08_113": {
- "subsystem": "Generator",
- "name": "SC_OverLoadFanOfWCSG",
- "en": "Radiator overloaded, water cooling system for generator",
- "cn": "发电机水冷系统散热器过载",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "3",
- "repeat_period": "T#60s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_08_116": {
- "subsystem": "Generator",
- "name": "OC_GenWaterCoolValveTimeOut",
- "en": "generator valve running out of control",
- "cn": "发电机水冷三通阀长时间不打开或不闭合",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "( NOT gbDI_GLGenWaterCool_ValveOpen AND gbDQ_GLGenWaterCool_ValveOpen ) OR_x000D_ (NOT gbDI_GLGenWaterCool_ValveClose AND gbDQ_GLGenWaterCool_ValveClose)",
- "trigger_cn": "( NOT gbDI_GLGenWaterCool_ValveOpen AND gbDQ_GLGenWaterCool_ValveOpen ) OR(NOT gbDI_GLGenWaterCool_ValveClose AND gbDQ_GLGenWaterCool_ValveClose)",
- "set_delay": "T#1m",
- "yp": "0",
- "reset_en": "No receive open or close signal of valve for 1min",
- "reset_cn": "发电机水冷三通阀超过1分钟没有打开或者闭合",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_08_117": {
- "subsystem": "Generator",
- "name": "SC_GenWaterCoolPumpAlarm",
- "en": "generator water cool pump or heater switch off",
- "cn": "发电机水冷主循环泵或电加热器或三通阀开关跳闸",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#3s",
- "yp": "0",
- "reset_en": "NOT gbDI_GLGenWaterCool_PumpHeaterValve_PowerSupply",
- "reset_cn": "NOT gbDI_GLGenWaterCool_PumpHeaterValve_PowerSupply",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_08_118": {
- "subsystem": "Generator",
- "name": "SC_GLGenWaterCoolInletPT100Fault",
- "en": "generator Inlet temp TT01 error",
- "cn": "发电机水冷供水温度传感器TT01 故障",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "sensor error",
- "reset_cn": "传感器故障",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_08_119": {
- "subsystem": "Generator",
- "name": "OC_GLGenWaterCoolOutletTemp",
- "en": "generator Outlet temp TT02 error",
- "cn": "发电机水冷回水温度传感器TT02 故障",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "sensor error",
- "reset_cn": "传感器故障",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_08_120": {
- "subsystem": "Generator",
- "name": "OC_GLGenWaterCoolInletPre",
- "en": "generator inlet pressure PT01 error",
- "cn": "发电机水冷供水压力变送器PT01 故障",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "sensor error",
- "reset_cn": "传感器故障",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_08_121": {
- "subsystem": "Generator",
- "name": "OC_GLGenWaterCoolOutletPre",
- "en": "generator outlet Pressure PT02 error",
- "cn": "发电机水冷回水压力变送器PT02 故障",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "sensor error",
- "reset_cn": "传感器故障",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_08_122": {
- "subsystem": "Generator",
- "name": "SC_GLGenWaterCoolInletTempHigh2",
- "en": "generator inlet temp high 2 level",
- "cn": "发电机水冷供水温度过高故障",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "grGLGenWaterCool_InletTemp_1min>PAR_WCSInletPreHigh2",
- "reset_cn": "grGLGenWaterCool_InletTemp_1min>PAR_WCSInletPreHigh2",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_08_123": {
- "subsystem": "Generator",
- "name": "OC_GLGenWaterCoolInletTempHigh1",
- "en": "generator inlet temp high level 1",
- "cn": "发电机水冷供水温度过高警告",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "grGLGenWaterCool_InletTemp_1min>PAR_WCSInletPreHigh1",
- "reset_cn": "grGLGenWaterCool_InletTemp_1min>PAR_WCSInletPreHigh1",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_08_124": {
- "subsystem": "Generator",
- "name": "SC_GLGenWaterCoolOutletTempHigh",
- "en": "generator outlet temp high",
- "cn": "发电机水冷回水温度高",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "grGLGenWaterCool_OutletTemp_1min>PAR_rWCSGENInletTempHigh2",
- "reset_cn": "grGLGenWaterCool_OutletTemp_1min>PAR_rWCSGENInletTempHigh2",
- "reset_mode": "M",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_08_125": {
- "subsystem": "Generator",
- "name": "SC_GLGenWaterCoolInletPreHigh2",
- "en": "generator inlet pressure high level 2",
- "cn": "发电机水冷供水压力过高故障",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "grGLGenWaterCool_InletPre>PAR_WCSInletPreHigh2",
- "reset_cn": "grGLGenWaterCool_InletPre>PAR_WCSInletPreHigh2",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_08_126": {
- "subsystem": "Generator",
- "name": "OC_GLGenWaterCoolInletPreHigh1",
- "en": "generator inlet pressure high level 1",
- "cn": "发电机水冷供水压力过高警告",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "grGLGenWaterCool_InletPre>PAR_WCSInletPreHigh1",
- "reset_cn": "grGLGenWaterCool_InletPre>PAR_WCSInletPreHigh1",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_08_127": {
- "subsystem": "Generator",
- "name": "OC_GLGenWaterCoolInletPreLow1",
- "en": "generator inlet pressure low level 2",
- "cn": "发电机水冷供水压力过低警告",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "grGLGenWaterCool_InletPre<PAR_WCSInletPreLow1",
- "reset_cn": "grGLGenWaterCool_InletPre<PAR_WCSInletPreLow1",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_08_128": {
- "subsystem": "Generator",
- "name": "SC_GLGenWaterCoolInletPreLow2",
- "en": "generator inlet pressure low level 1",
- "cn": "发电机水冷供水压力过低故障",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "grGLGenWaterCool_InletPre<PAR_WCSInletPreLow2",
- "reset_cn": "grGLGenWaterCool_InletPre<PAR_WCSInletPreLow2",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_08_129": {
- "subsystem": "Generator",
- "name": "OC_GLGenWaterCoolOutletPreLow1",
- "en": "generator outlet pressure low level 2",
- "cn": "发电机水冷回水压力过低警告",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "grGLGenWaterCool_OutletPre<PAR_WCSOutletPreLow1",
- "reset_cn": "grGLGenWaterCool_OutletPre<PAR_WCSOutletPreLow1",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_08_130": {
- "subsystem": "Generator",
- "name": "SC_GLGenWaterCoolOutletPreLow2",
- "en": "generator outlet pressure low level 1",
- "cn": "发电机水冷回水压力过低故障",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "grGLGenWaterCool_OutletPre<PAR_WCSOutletPreLow2",
- "reset_cn": "grGLGenWaterCool_OutletPre<PAR_WCSOutletPreLow2",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_08_131": {
- "subsystem": "Generator",
- "name": "OC_GLGenWaterCoolInletTempLow",
- "en": "generator inlet temp low",
- "cn": "发电机水冷供水温度低",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "grGLGenWaterCool_InletTemp_1min<PAR_WCSInletTempLow",
- "reset_cn": "grGLGenWaterCool_InletTemp_1min<PAR_WCSInletTempLow",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_08_132": {
- "subsystem": "Generator",
- "name": "OC_GenWaterCoolFan1Alarm",
- "en": "generator water cool fan 1 or 2 or 3 switch off",
- "cn": "发电机水冷空散电机1或2或3开关跳闸",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "NOT DI_GLGenWaterCool_FansPowerSupply",
- "reset_cn": "NOT DI_GLGenWaterCool_FansPowerSupply",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_08_133": {
- "subsystem": "Generator",
- "name": "SC_GenWaterCoolInOutPressureDiffHigh",
- "en": "Water pressure Difference between inlet and outlet of GEN-WCS is too high",
- "cn": "发电机水冷入口、出口压差过大故障",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "发电机水冷进出口压力差过大",
- "set_delay": "T#5s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_08_134": {
- "subsystem": "Generator",
- "name": "SC_GenWaterCoolInOutPressureDiffLow",
- "en": "Water pressure Difference between inlet and outlet of GEN-WCS is too low",
- "cn": "发电机水冷入口、出口压差过低故障",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "发电机水冷进出口压力差过小",
- "set_delay": "T#5s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_08_135": {
- "subsystem": "Generator",
- "name": "OC_GenWaterCoolInOutPressureDetect",
- "en": "Water pressure Difference between inlet and outlet of GEN-WCS is ready for heater start",
- "cn": "发电机水冷系统压力建立,达到加热器启动条件",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "发电机进出口压力达到启动加热器条件",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "02_08_136": {
- "subsystem": "Generator",
- "name": "SC_GenWaterCoolHeaterOnTooLong",
- "en": "GEN-WCS heating mode timeout",
- "cn": "发电机水冷加热器加热时间过长",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "发电机水冷加热器加热时间过长",
- "set_delay": "PAR_tGenWaterCoolHeaterOnWorking",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_06_017": {
- "subsystem": "Generator",
- "name": "OC_GENGLPumpControlManualMode",
- "en": "Generator GL Pump Enter in ManualMode",
- "cn": "发电机高澜水冷系统泵控制进入手动模式",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#50ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_06_018": {
- "subsystem": "Generator",
- "name": "OC_GENGLPumpControlForceMode",
- "en": "Generator GL Pump Enter in ForceMode",
- "cn": "发电机高澜水冷系统泵控制进入强制模式",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#50ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_06_019": {
- "subsystem": "Generator",
- "name": "OC_GENGLHeaterControlManualMode",
- "en": "Generator GL Heater Enter in ManualMode",
- "cn": "发电机高澜水冷系统加热器控制进入手动模式",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#50ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_06_020": {
- "subsystem": "Generator",
- "name": "OC_GENGLHeaterControlForceMode",
- "en": "Generator GL Heater Enter in ForceMode",
- "cn": "发电机高澜水冷系统加热器控制进入强制模式",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#50ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_06_021": {
- "subsystem": "Generator",
- "name": "OC_GENGLValveControlManualMode",
- "en": "Generator GL Valve Enter in ManualMode",
- "cn": "发电机高澜水冷系统三通阀控制进入手动模式",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#50ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_06_022": {
- "subsystem": "Generator",
- "name": "OC_GENGLValveControlForceMode",
- "en": "Generator GL Valve Enter in ForceMode",
- "cn": "发电机高澜水冷系统三通阀控制进入强制模式",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#50ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_06_023": {
- "subsystem": "Generator",
- "name": "OC_GENGLFan1ControlManualMode",
- "en": "Generator GL Fan 1 Enter in ManualMode",
- "cn": "发电机高澜水冷系统风扇1控制进入手动模式",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#50ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_06_024": {
- "subsystem": "Generator",
- "name": "OC_GENGLFan1ControlForceMode",
- "en": "Generator GL Fan 1 Enter in ForceMode",
- "cn": "发电机高澜水冷系统风扇1控制进入强制模式",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#50ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_06_025": {
- "subsystem": "Generator",
- "name": "OC_GENGLFan2ControlManualMode",
- "en": "Generator GL Fan 2 Enter in ManualMode",
- "cn": "发电机高澜水冷系统风扇2控制进入手动模式",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#50ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_06_026": {
- "subsystem": "Generator",
- "name": "OC_GENGLFan2ControlForceMode",
- "en": "Generator GL Fan 2 Enter in ForceMode",
- "cn": "发电机高澜水冷系统风扇2控制进入强制模式",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#50ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_06_027": {
- "subsystem": "Generator",
- "name": "OC_GENGLFan3ControlManualMode",
- "en": "Generator GL Fan 3 Enter in ManualMode",
- "cn": "发电机高澜水冷系统风扇3控制进入手动模式",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#50ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_06_028": {
- "subsystem": "Generator",
- "name": "OC_GENGLFan3ControlForceMode",
- "en": "Generator GL Fan 3 Enter in ForceMode",
- "cn": "发电机高澜水冷系统风扇3控制进入强制模式",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#50ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_06_029": {
- "subsystem": "Generator",
- "name": "OC_GENGLPumpON",
- "en": "Generator GL Pump is on",
- "cn": "发电机高澜水冷系统泵开启",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_06_030": {
- "subsystem": "Generator",
- "name": "OC_GENGLHeaterON",
- "en": "Generator GL Heater is On",
- "cn": "发电机高澜水冷系统加热器开启",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_06_031": {
- "subsystem": "Generator",
- "name": "OC_GENValveON",
- "en": "Generator GL Valve is On",
- "cn": "发电机高澜水冷系统三通阀开启",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_06_032": {
- "subsystem": "Generator",
- "name": "OC_GLFan1ON",
- "en": "Generator GL Fan1 is On",
- "cn": "发电机高澜水冷系统风扇1开启",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_06_033": {
- "subsystem": "Generator",
- "name": "OC_GLFan2ON",
- "en": "Generator GL Fan2 is On",
- "cn": "发电机高澜水冷系统风扇2开启",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_06_034": {
- "subsystem": "Generator",
- "name": "OC_GLFan3ON",
- "en": "Generator GL Fan3 is On",
- "cn": "发电机高澜水冷系统风扇3开启",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "03_02_102": {
- "subsystem": "ConverterContainer",
- "name": "SC_MotorProtection_WCSC",
- "en": "Air switch activated, water cooling system for converter",
- "cn": "变频器水冷系统保护空开触发",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "03_05_008": {
- "subsystem": "ConverterContainer",
- "name": "SC_ConverterNoFeedBackForSwitchON_CB",
- "en": "No Main circuit breaker closure feedback is received",
- "cn": "断路器长时间不响应闭合命令",
- "powerup_delay": "T#10s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The turbine operation mode is \"Standby\", the signal \"DCLinkRelease\" is TRUE, and the feddback signal from the MCB stay at \"FALSE\".(giTurbineOperationMode = CON_iStandby) AND dqConverter_DCLinkRelease=1.",
- "trigger_cn": "风机运行在待机模式下,主控向变频器发出主断路器合闸指令,但没有收到主断路器合闸的反馈信号。(giTurbineOperationMode = CON_iStandby) AND dqConverter_DCLinkRelease=1.",
- "set_delay": "PAR_tDelayCircuitBrakerClose",
- "yp": "0",
- "reset_en": "_x000D_ The turbine operation mode is not \"Standby\", or the signal \"DCLinkRelease\" is FALSE or the feddback signal from the MCB stay at \"TRUE\".(giTurbineOperationMode ≠ CON_iStandby) OR dqConverter_DCLinkRelease=0.",
- "reset_cn": "风机不运行在待机模式,或能够收到主断路器合闸的反馈信号。(giTurbineOperationMode ≠ CON_iStandby) OR dqConverter_DCLinkRelease=0.",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "03_05_028": {
- "subsystem": "ConverterContainer",
- "name": "SC_ConverterCrowbarActive",
- "en": "Converter crowbar protection is active",
- "cn": "变频器过压保护被触发",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The crowbar protection signal from the converter (via serial communication) becomes TRUE.(diConverter_CrowbarActive=1)",
- "trigger_cn": "变频器过压保护的信号为TRUE。(diConverter_CrowbarActive=1)",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "The crowbar protection signal from the converter (via serial communication) becomes FALSE.(diConverter_CrowbarActive=0)",
- "reset_cn": "变频器过压保护的信号为FALSE。(diConverter_CrowbarActive=0)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "03_05_051": {
- "subsystem": "ConverterContainer",
- "name": "OC_CVTWaterCoolInletPreHigh1",
- "en": "converter inlet pressure high 1 level",
- "cn": "变频器水冷供水压力高报警",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "grGLConvWaterCool_InletPre>PAR_WCSInletPreHigh1",
- "reset_cn": "grGLConvWaterCool_InletPre>PAR_WCSInletPreHigh1",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "03_05_052": {
- "subsystem": "ConverterContainer",
- "name": "OC_CVTWaterCoolInletPreLow1",
- "en": "converter inlet pressure low 1 level",
- "cn": "变频器水冷供水压力低报警",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "grGLConvWaterCool_InletPre<PAR_WCSInletPreLow1",
- "reset_cn": "grGLConvWaterCool_InletPre<PAR_WCSInletPreLow1",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "03_05_053": {
- "subsystem": "ConverterContainer",
- "name": "SC_CVTWaterCoolInletPreLow2",
- "en": "converter inlet pressure low 2 level",
- "cn": "变频器水冷供水压力低故障",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "grGLConvWaterCool_InletPre<PAR_WCSInletPreLow2",
- "reset_cn": "grGLConvWaterCool_InletPre<PAR_WCSInletPreLow2",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "03_05_054": {
- "subsystem": "ConverterContainer",
- "name": "OC_CVTWaterCoolOutletPreLow1",
- "en": "converter outlet pressure low 1 level",
- "cn": "变频器水冷回水压力低报警",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "grGLConvWaterCool_OutletPre<PAR_WCSOutletPreLow1",
- "reset_cn": "grGLConvWaterCool_OutletPre<PAR_WCSOutletPreLow1",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "03_05_055": {
- "subsystem": "ConverterContainer",
- "name": "SC_CVTWaterCoolOutletPreLow2",
- "en": "converter outlet pressure low 2 level",
- "cn": "变频器水冷回水压力低故障",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "grGLConvWaterCool_OutletPre<PAR_WCSOutletPreLow2",
- "reset_cn": "grGLConvWaterCool_OutletPre<PAR_WCSOutletPreLow2",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "03_05_056": {
- "subsystem": "ConverterContainer",
- "name": "OC_CVTWaterCoolInletTempLow",
- "en": "converter inlet temp low",
- "cn": "变频器水冷供水温度低",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "grGLConvWaterCool_InletTemp_1min<PAR_WCSInletTempLow",
- "reset_cn": "grGLConvWaterCool_InletTemp_1min<PAR_WCSInletTempLow",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "03_05_057": {
- "subsystem": "ConverterContainer",
- "name": "OC_CVTWaterCoolFanAlarm",
- "en": "converter fan and valve switch off",
- "cn": "变频器水冷空散电机或三通阀开关跳闸(空冷器电机跳闸)",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "NOT gbDI_GLConvWaterCool_MotorValvePowerSupply",
- "reset_cn": "NOT gbDI_GLConvWaterCool_MotorValvePowerSupply",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "03_05_058": {
- "subsystem": "ConverterContainer",
- "name": "SC_CVTWaterCoolInletPreHigh2",
- "en": "converter inlet pressure high 2 level",
- "cn": "变频器水冷供水压力高故障",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "grGLConvWaterCool_InletPre>PAR_WCSInletPreHigh2",
- "reset_cn": "grGLConvWaterCool_InletPre>PAR_WCSInletPreHigh2",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "03_05_059": {
- "subsystem": "ConverterContainer",
- "name": "OC_CVTWaterCoolValveTimeOut",
- "en": "converter valve running out of control",
- "cn": "变频器水冷三通阀长时间不打开或不闭合",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "(NOT gbDI_GLCVTWaterCool_ValveOpen AND gbDQ_GLCVTWaterCool_ValveOpen) OR_x000D_ (NOT gbDI_GLCVTWaterCool_ValveClose AND gbDQ_GLCVTWaterCool_ValveClose)",
- "trigger_cn": "(NOT gbDI_GLCVTWaterCool_ValveOpen AND gbDQ_GLCVTWaterCool_ValveOpen) OR_x000D_ (NOT gbDI_GLCVTWaterCool_ValveClose AND gbDQ_GLCVTWaterCool_ValveClose)",
- "set_delay": "T#1m",
- "yp": "0",
- "reset_en": "No receive open or close signal of valve for 1min",
- "reset_cn": "三通阀超过1分钟没有打开或者闭合",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "03_05_060": {
- "subsystem": "ConverterContainer",
- "name": "SC_ConverterHeatingModeTimeOut",
- "en": "converter HeatingMode is TimeOut",
- "cn": "变频器处于暖机模式时间过长",
- "powerup_delay": "T#1s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "OC_ConverterHeatingMode is true",
- "trigger_cn": "",
- "set_delay": "PAR_tConverterHeatingModeTimeout",
- "yp": "0",
- "reset_en": "converter heating mode time out",
- "reset_cn": "变频器处于暖机模式时间过长",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "100"
- },
- "03_05_061": {
- "subsystem": "ConverterContainer",
- "name": "SC_CVTWaterCoolInOutPressureDiffHigh",
- "en": "Water pressure Difference between inlet and outlet of CVT-WCS is too high",
- "cn": "变频器水冷入口、出口压差过大",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "变频器水冷进出口压力差过大",
- "set_delay": "T#5s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "03_05_062": {
- "subsystem": "ConverterContainer",
- "name": "SC_CVTWaterCoolInOutPressureDiffLow",
- "en": "Water pressure Difference between inlet and outlet of CVT-WCS is too low",
- "cn": "变频器水冷入口、出口压差太低",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "变频器水冷进出口压力差过小",
- "set_delay": "T#5s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "03_05_063": {
- "subsystem": "ConverterContainer",
- "name": "SC_CVTWaterCoolHeaterOnTooLong",
- "en": "CVT-WCS heating mode timeout",
- "cn": "变频器水冷加热器加热时间过长",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "变频器水冷加热器加热时间过长",
- "set_delay": "PAR_tCVTWaterCoolHeaterOnWorking",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "03_05_113": {
- "subsystem": "ConverterContainer",
- "name": "OC_ConverterHeatingModeHardWire",
- "en": "The Converter Heating Mode On signal from Hardwire.",
- "cn": "变频器暖机模式",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "gbDI_TowerConverterHeatingActive and gbCANConverterDisturbed",
- "trigger_cn": "变频器处于冲硬线传过来信号的暖机模式",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "gbDI_TowerConverterHeatingActive and gbCANConverterDisturbed",
- "reset_cn": "gbDI_TowerConverterHeatingActive and gbCANConverterDisturbed",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "30-待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "30",
- "brake_state_design": "50"
- },
- "03_05_115": {
- "subsystem": "ConverterContainer",
- "name": "OC_ConverterHeatingModeCanBus",
- "en": "The Converter Heating Mode On signal from CanBus.",
- "cn": "变频器暖机模式",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "diConverter_HeatingMode and Not diConverter_ReadyToCutIn",
- "trigger_cn": "变频器处于从Canbus通讯传递过来的暖机模式",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "diConverter_HeatingMode and Not diConverter_ReadyToCutIn",
- "reset_cn": "diConverter_HeatingMode and Not diConverter_ReadyToCutIn",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "30-待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "30",
- "brake_state_design": "50"
- },
- "03_05_116": {
- "subsystem": "ConverterContainer",
- "name": "OC_CVTWaterCoolInOutPressureDetect",
- "en": "Water pressure Difference between inlet and outlet of CVT-WCS is ready for heater start",
- "cn": "变频器水冷系统压力建立,达到加热器启动条件",
- "powerup_delay": "T#0S",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "变频器进出口压力达到启动加热器条件",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_12_017": {
- "subsystem": "ConverterContainer",
- "name": "SC_FaultOvervoltageProtectionConverter",
- "en": "",
- "cn": "变频柜主电源防雷器故障",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#5s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "03_05_029": {
- "subsystem": "ConverterContainer",
- "name": "SC_FaultPofibusWCSC",
- "en": "Fault, Profibus communication with water cooling system for converter",
- "cn": "与变频器水冷系统PROFIBUS通讯故障",
- "powerup_delay": "T#2m",
- "disable_level": "100",
- "repeat_n": "3",
- "repeat_period": "T#60s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "03_05_030": {
- "subsystem": "ConverterContainer",
- "name": "SC_EmergencyModeOfWCSC",
- "en": "Emergency stop button depressed, water cooling system for converter",
- "cn": "变频器水冷系统急停被拍下",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "3",
- "repeat_period": "T#60s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "03_05_031": {
- "subsystem": "ConverterContainer",
- "name": "SC_PumpOverLoadOfWCSC",
- "en": "Pump overloaded, water cooling system for converter",
- "cn": "变频器水冷系统循环泵过载",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "3",
- "repeat_period": "T#60s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "03_05_032": {
- "subsystem": "ConverterContainer",
- "name": "SC_TempHighOfWCSC",
- "en": "Overtemperature, water cooling system for converter",
- "cn": "变频器水冷系统过温",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "3",
- "repeat_period": "T#60s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "03_05_033": {
- "subsystem": "ConverterContainer",
- "name": "SC_PreHighOfWCSC",
- "en": "Too high pressure, water cooling system for converter",
- "cn": "变频器水冷系统过压",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "3",
- "repeat_period": "T#60s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "03_05_034": {
- "subsystem": "ConverterContainer",
- "name": "SC_PreLowOfWCSC",
- "en": "Too low pressure, water cooling system for converter",
- "cn": "变频器水冷系统压力过低",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "3",
- "repeat_period": "T#60s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "03_05_035": {
- "subsystem": "ConverterContainer",
- "name": "SC_NotReadyOfWCSC",
- "en": "Water cooling system for converter not ready",
- "cn": "变频器水冷系统没有准备好",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "3",
- "repeat_period": "T#60s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "03_05_036": {
- "subsystem": "ConverterContainer",
- "name": "SC_FaultStatusOfWCSC",
- "en": "Fault mode, water cooling system for converter",
- "cn": "变频器水冷系统故障模式",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "3",
- "repeat_period": "T#60s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "03_05_037": {
- "subsystem": "ConverterContainer",
- "name": "SC_TempLowOfWCSC",
- "en": "Too low temperature, water cooling system for converter",
- "cn": "变频器水冷系统温度过低",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "3",
- "repeat_period": "T#60s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "03_05_038": {
- "subsystem": "ConverterContainer",
- "name": "SC_TempSignalErrorOfWCSC",
- "en": "Temperature signal error, water cooling system for converter",
- "cn": "变频器水冷系统温度信号错误",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "3",
- "repeat_period": "T#60s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "03_05_039": {
- "subsystem": "ConverterContainer",
- "name": "SC_PreSignalErrorOfWCSC",
- "en": "Pressure signal error, water cooling system for converter",
- "cn": "变频器水冷系统压力信号错误",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "3",
- "repeat_period": "T#60s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "03_05_040": {
- "subsystem": "ConverterContainer",
- "name": "SC_ServiceModeOfWCSC",
- "en": "Service mode, water cooling system for converter",
- "cn": "变频器水冷系统维护模式",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "3",
- "repeat_period": "T#60s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "210-维护",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "210",
- "brake_state_design": "0"
- },
- "03_05_041": {
- "subsystem": "ConverterContainer",
- "name": "SC_OverLoadFanOfWCSC",
- "en": "Radiator overloaded, water cooling system for converter",
- "cn": "变频器水冷系统散热器过载",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "3",
- "repeat_period": "T#60s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "03_05_042": {
- "subsystem": "ConverterContainer",
- "name": "SC_CVTWaterCoolPumpAlarm",
- "en": "converter water cool pump error",
- "cn": "变频器水冷主循环泵或电加热器故障",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#3s",
- "yp": "0",
- "reset_en": "NOT gbDI_GLConvWaterCool_PumpHeaterPowerSupply",
- "reset_cn": "NOT gbDI_GLConvWaterCool_PumpHeaterPowerSupply",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "03_05_043": {
- "subsystem": "ConverterContainer",
- "name": "SC_CVTWaterCoolInletTemp",
- "en": "converter water cool inlet temp TT01 ERROR",
- "cn": "变频器水冷供水温度传感器TT01 故障",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "sensor error",
- "reset_cn": "传感器故障",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "03_05_044": {
- "subsystem": "ConverterContainer",
- "name": "OC_CVTWaterCoolOutletTemp",
- "en": "converter water cool outlet temp error",
- "cn": "变频器水冷回水温度传感器TT02 故障",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "sensor error",
- "reset_cn": "传感器故障",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "03_05_045": {
- "subsystem": "ConverterContainer",
- "name": "OC_CVTWaterCoolInletPre",
- "en": "converter water cool inlet pressure error",
- "cn": "变频器水冷供水压力变送器PT01 故障",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "sensor error",
- "reset_cn": "传感器故障",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "03_05_046": {
- "subsystem": "ConverterContainer",
- "name": "OC_CVTWaterCoolOutletPre",
- "en": "converter water cool outlet pressure error",
- "cn": "变频器水冷回水压力变送器PT02 故障",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "sensor error",
- "reset_cn": "传感器故障",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "03_05_047": {
- "subsystem": "ConverterContainer",
- "name": "SC_CVTWaterCoolInletTempHigh2",
- "en": "converter water cool inlet temp high 2 level",
- "cn": "变频器水冷供水温度高故障",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "grGLConvWaterCool_InletTemp_1min>PAR_WCSInletPreHigh2",
- "reset_cn": "grGLConvWaterCool_InletTemp_1min>PAR_WCSInletPreHigh2",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "03_05_048": {
- "subsystem": "ConverterContainer",
- "name": "OC_CVTWaterCoolInletTempHigh1",
- "en": "converter water cool inlet temp high 1 level",
- "cn": "变频器水冷供水温度高报警",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "grGLConvWaterCool_InletTemp_1min>PAR_WCSInletPreHigh1",
- "reset_cn": "grGLConvWaterCool_InletTemp_1min>PAR_WCSInletPreHigh1",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "03_05_049": {
- "subsystem": "ConverterContainer",
- "name": "SC_CVTWaterCoolOutletTempHigh",
- "en": "converter outlet temp high",
- "cn": "变频器水冷回水温度高",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "grGLConvWaterCool_OutletTemp>PAR_WCSInletPreHigh2",
- "reset_cn": "grGLConvWaterCool_OutletTemp>PAR_WCSInletPreHigh2",
- "reset_mode": "M",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_04_009": {
- "subsystem": "Drivetrain",
- "name": "SC_Sensor1RotorImpulsesDefect",
- "en": "Rotor speed sensor1 has defect",
- "cn": "低速端#1接近开关故障",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "(No brake program is active)The 1sec mean value for rotor speed is higher than a value given by parameter and no new impulse from the speed sensor will be detected.(grRotorSpeedPDM_1sec > PAR_rGenSpeedStartCompareRotGen / PAR_rGearboxRatio AND giBPLevel = 0 AND bImpActive=1) bImpActive will turn to be true when rotor pulse remains 1 or 0 for 2 seconds.",
- "trigger_cn": "当没有刹车程序被激活,风机一秒钟平均速度值高于设定值,且传感器没有检测到新的动力。(grRotorSpeedPDM_1sec > PAR_rGenSpeedStartCompareRotGen / PAR_rGearboxRatio AND giBPLevel = 0 AND bImpActive=1)。当低速段测速脉冲不变时(恒为1或者恒为0持续2s),bImpActive为true。",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "(No brake program is active)The 1sec mean value for rotor speed is lower than a value given by parameter or new impulse from the speed sensor will be detected.(grRotorSpeedPDM_1sec <= PAR_rGenSpeedStartCompareRotGen / PAR_rGearboxRatio OR giBPLevel ≠0 OR bImpActive=0) bImpActive will turn to be true when rotor pulse remains 1 or 0 for 2 seconds.",
- "reset_cn": "当有刹车程序被激活,或风机一秒钟平均速度值不高于设定值,或传感器检测到新的动力。(grRotorSpeedPDM_1sec <= PAR_rGenSpeedStartCompareRotGen / PAR_rGearboxRatio OR giBPLevel ≠0 OR bImpActive=0) 当低速段测速脉冲不变时(恒为1或者恒为0持续2s),bImpActive为true。",
- "reset_mode": "M",
- "type": "F",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_04_010": {
- "subsystem": "Drivetrain",
- "name": "SC_Sensor2RotorImpulsesDefect",
- "en": "Rotor speed sensor2 has defect",
- "cn": "低速端#2接近开关故障",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "(No brake program is active)The 1sec mean value for rotor speed is higher than a value given by parameter and no new impulse from the speed sensor will be detected.(grRotorSpeedPDM_1sec > PAR_rGenSpeedStartCompareRotGen / PAR_rGearboxRatio AND giBPLevel = 0 AND bImpActive=1)",
- "trigger_cn": "当没有刹车程序被激活,风机一秒钟平均速度值高于设定值,且传感器没有检测到新的动力。(grRotorSpeedPDM_1sec > PAR_rGenSpeedStartCompareRotGen / PAR_rGearboxRatio AND giBPLevel = 0 AND bImpActive=1)",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "(No brake program is active)The 1sec mean value for rotor speed is higher than a value given by parameter and new impulse from the speed sensor will be detected.(grRotorSpeedPDM_1sec > PAR_rGenSpeedStartCompareRotGen / PAR_rGearboxRatio AND giBPLevel = 0 AND bImpActive=0)",
- "reset_cn": "当没有刹车程序被激活,风机一秒钟平均速度值高于设定值,且传感器检测到新的动力。(grRotorSpeedPDM_1sec > PAR_rGenSpeedStartCompareRotGen / PAR_rGearboxRatio AND giBPLevel = 0 AND bImpActive=0)",
- "reset_mode": "M",
- "type": "F",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_04_012": {
- "subsystem": "Drivetrain",
- "name": "SC_OverspeedRelayDetectFail",
- "en": "Fault, overspeed relay",
- "cn": "低速端转速与过速继电器测速不匹配",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_02_001": {
- "subsystem": "Cabinet",
- "name": "SC_TempNacelleCabinetOutOfSpec",
- "en": "Temperature in nacelle cabinet is out of spec",
- "cn": "机舱柜恒温器测得温度高于设定值",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Temperature in nacelle cabinet holds within spec.(gbDI_NacelleTempCabinetOutOfSpec=0)",
- "trigger_cn": "机舱控制柜温度超标。(gbDI_NacelleTempCabinetOutOfSpec=0)",
- "set_delay": "T#1m",
- "yp": "100",
- "reset_en": "Temperature in nacelle cabinet is out of spec.(gbDI_NacelleTempCabinetOutOfSpec=1 AND bSpecResCond=1)",
- "reset_cn": "机舱控制柜温度在设定值内。(gbDI_NacelleTempCabinetOutOfSpec=1 AND bSpecResCond=1)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_02_003": {
- "subsystem": "Cabinet",
- "name": "SC_NacelleUPS24VPLC_Alarm",
- "en": "Nacelle 24V UPS has alarm",
- "cn": "机舱柜24V UPS报警",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Nacelle 24V UPS has no alarm.(gbDI_NacelleUPS24VPLC_Alarm=0)",
- "trigger_cn": "机舱无24V UPS报警。(gbDI_NacelleUPS24VPLC_Alarm=0)",
- "set_delay": "T#15s",
- "yp": "0",
- "reset_en": "Nacelle 24V UPS alarm is clear._x000D_ gbDI_NacelleUPS24VPLC_Alarm=1 AND",
- "reset_cn": "机舱24V UPS报警解除。(gbDI_NacelleUPS24VPLC_Alarm=1 )",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_02_004": {
- "subsystem": "Cabinet",
- "name": "SC_TowerThermostatsProtBreak",
- "en": "The TowerThermostats_x000D_ protection tripped.",
- "cn": "塔底温控器电源空开跳开",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The protection for Tower Thermostats has tripped.(gbDI_TowerThermostatsProt=0)",
- "trigger_cn": "塔底温控器保护开关被触发",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "The protection for Tower ThermostatsProt is OK.(gbDI_NacelleMotorProtGearOilPump=1 )",
- "reset_cn": "温控器供电开关OK(gbDI_TowerThermostatsProt=1 )",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "brake_state_design": "51"
- },
- "02_02_005": {
- "subsystem": "Cabinet",
- "name": "SC_NacelleThermostatsProtBreak",
- "en": "The NacelleThermostats_x000D_ protection tripped.",
- "cn": "机舱温控器电源空开跳开",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The protection for Nacelle Thermostats has tripped.(gbDI_NacelleThermostatsProt=0)",
- "trigger_cn": "机舱温控器保护开关被触发",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "The protection for Nacelle ThermostatsProt is OK.(gbDI_NacelleMotorProtGearOilPump=1 )",
- "reset_cn": "温控器供电开关OK(gbDI_NacelleThermostatsProt=1 )",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "brake_state_design": "51"
- },
- "02_02_006": {
- "subsystem": "Cabinet",
- "name": "SC_NacelleUPS24VPLC_BatteryMode",
- "en": "Nacelle 24V UPS is in battery mode(no power supply at the UPS input is available)",
- "cn": "机舱柜24V UPS处于电池模式",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Nacelle 24V UPS is in battery mode.(gbDI_NacelleUPS24VPLC_BatteryMode=0)",
- "trigger_cn": "机舱24V UPS处于电池模式。(gbDI_NacelleUPS24VPLC_BatteryMode=0)",
- "set_delay": "T#1m",
- "yp": "0",
- "reset_en": "Nacelle 24V UPS is out of battery mode.(gbDI_NacelleUPS24VPLC_BatteryMode=1 )",
- "reset_cn": "输入电源可用、机舱24V UPS脱离电池模式。(gbDI_NacelleUPS24VPLC_BatteryMode=1)",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "51"
- },
- "02_02_008": {
- "subsystem": "Cabinet",
- "name": "SC_FaultOvervoltageProtectionCabinetNacelle",
- "en": "Nacelle overvoltage protection components has tripped.",
- "cn": "机舱柜690V电源防雷器,机舱柜400V电源防雷器或塔底柜230V电源防雷器发生故障",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Nacelle overvoltage protection components has tripped.(gbDI_NacelleOvervoltageProtection690V=0 OR gbDI_NacelleOvervoltageProtection400V=0 OR gbDI_TowerOvervoltageProtection230V=0)",
- "trigger_cn": "机舱690V、400V或230V过压保护装置发生故障。(gbDI_NacelleOvervoltageProtection690V=0 OR gbDI_NacelleOvervoltageProtection400V=0 OR gbDI_TowerOvervoltageProtection230V=0)",
- "set_delay": "T#5s",
- "yp": "0",
- "reset_en": "Nacelle overvoltage protection components is reconnected.(gbDI_NacelleOvervoltageProtection690V=1 AND gbDI_NacelleOvervoltageProtection400V=1 AND gbDI_TowerOvervoltageProtection230V=1 AND bSpecResCond=1)",
- "reset_cn": "机舱690V、400V和230V过压保护装置均无故障。(gbDI_NacelleOvervoltageProtection690V=1 AND gbDI_NacelleOvervoltageProtection400V=1 AND gbDI_TowerOvervoltageProtection230V=1 AND bSpecResCond=1))",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_02_020": {
- "subsystem": "Cabinet",
- "name": "SC_NacelleFuse690VMainSupply",
- "en": "The fuse for nacelle main 690V power supply has tripped.",
- "cn": "机舱柜690V电源熔断器故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The fuse for nacelle main 690V power supply has tripped.(gbDI_NacelleNHFuse690VMainSupply=0)",
- "trigger_cn": "机舱690V主电源保险丝发生故障。(gbDI_NacelleNHFuse690VMainSupply=0)",
- "set_delay": "T#100ms",
- "yp": "100",
- "reset_en": "The fuse for nacelle main 690V power supply is OK.(gbDI_NacelleNHFuse690VMainSupply=1 )",
- "reset_cn": "机舱690V主电源保险丝故障解除。(gbDI_NacelleNHFuse690VMainSupply=1)",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "02_02_021": {
- "subsystem": "Cabinet",
- "name": "SC_NacelleFuse400VMainSupply",
- "en": "The fuse for nacelle main 400V power supply has tripped.",
- "cn": "机舱柜400V电源熔断器故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The fuse for nacelle main 400V power supply has tripped.(gbDI_NacelleNHFuse400VMainSupply=0)",
- "trigger_cn": "机舱400V主电源保险丝发生故障。(gbDI_NacelleNHFuse690VMainSupply=0)",
- "set_delay": "T#100ms",
- "yp": "100",
- "reset_en": "The fuse for nacelle main 400V power supply is OK.(gbDI_NacelleNHFuse400VMainSupply=1 AND bSpecResCond=1)",
- "reset_cn": "机舱400V主电源保险丝故障解除。(gbDI_NacelleNHFuse400VMainSupply=1 AND bSpecResCond=1)",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "100"
- },
- "02_02_026": {
- "subsystem": "Cabinet",
- "name": "SC_NacelleFuseHeaterSlipring",
- "en": "The fuse for power supply for the slipring heater has tripped.",
- "cn": "机舱柜中电气滑环加热器保护空开跳开",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The fuse for power supply for the slipring heater has tripped.(gbDI_NacelleFuseHeaterSlipring=0)",
- "trigger_cn": "滑环加热器电源的保险丝发生故障。(gbDI_NacelleFuseHeaterSlipring=0)",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "The fuse for power supply for the slipring heater is OK.(gbDI_NacelleFuseHeaterSlipring=1)",
- "reset_cn": "滑环加热器电源的保险丝故障解除。(gbDI_NacelleFuseHeaterSlipring=1)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_02_033": {
- "subsystem": "Cabinet",
- "name": "SC_NacelleFuse230VCabClimatisation",
- "en": "The fuse for 230V power supply for the nacelle cabinet air condition devices has tripped.",
- "cn": "机舱柜加热器230V保护空开跳开",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The fuse for 230V power supply for the nacelle cabinet air condition devices has tripped.(gbDI_NacelleFuse230VCabAirCondition=0)",
- "trigger_cn": "机舱机柜散热器230V电源保险丝发生故障。(gbDI_NacelleFuse230VCabAirCondition=0)",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "The fuse for 230V power supply for the nacelle cabinet air condition devices is OK.(gbDI_NacelleFuse230VCabAirCondition=1)",
- "reset_cn": "机舱机柜散热器230V电源保险丝故障解除。(gbDI_NacelleFuse230VCabAirCondition=1)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_02_039": {
- "subsystem": "Cabinet",
- "name": "SC_NacelleFuse400VAC_24VDC",
- "en": "The fuse for the nacelle 400V AC / 24V DC power supply has tripped.",
- "cn": "机舱柜中AC400V转DC24V电源模块的供电保护空开跳开",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The fuse for the nacelle 400V AC / 24V DC power supply has tripped.(gbDI_NacelleFuse400VAC_24VDC=0)",
- "trigger_cn": "机舱400VAC转24VDC电源保险丝发生故障。(gbDI_NacelleFuse400VAC_24VDC=0)",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "The fuse for the nacelle 400V AC / 24V DC power supply is OK.(gbDI_NacelleFuse400VAC_24VDC=1)",
- "reset_cn": "机舱400VAC转24VDC电源保险丝故障解除。(gbDI_NacelleFuse400VAC_24VDC=1)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "02_02_120": {
- "subsystem": "Cabinet",
- "name": "OC_NacelleHeaterCabinetON",
- "en": "Heater for nacelle cabinet is set to on",
- "cn": "机舱柜加热器设定打开",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "PLC output for controlling the cabinet heater becomes TRUE.(DQ_NacelleHeaterCabinet=1)",
- "trigger_cn": "PLC控制机舱控制柜加热器的输出为TRUE。(DQ_NacelleHeaterCabinet=1)",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "PLC output for controlling the cabinet heater becomes FALSE.(DQ_NacelleHeaterCabinet=0)",
- "reset_cn": "PLC控制机舱控制柜加热器的输出为FALSE。(DQ_NacelleHeaterCabinet=0)",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "02_02_129": {
- "subsystem": "Cabinet",
- "name": "OC_Nacelle_24VPLC_BatteryCharge",
- "en": "UPS for PLC power supply works in the battery charging mode",
- "cn": "机舱柜中24V UPS处于充电模式",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "UPS for PLC power supply works in the battery charging mode.(gbDI_NacelleUPS24VPLC_BatteryCharge=1)",
- "trigger_cn": "PLC的UPS电源处在充电模式。(gbDI_NacelleUPS24VPLC_BatteryCharge=1)",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "UPS for PLC power supply does not work in the battery charging mode.(gbDI_NacelleUPS24VPLC_BatteryCharge=0)",
- "reset_cn": "PLC的UPS电源脱离充电模式。(gbDI_NacelleUPS24VPLC_BatteryCharge=0)",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "02_12_002": {
- "subsystem": "Cabinet",
- "name": "SC_TurbineInServiceNacelle",
- "en": "Turbine is commanded for service from nacelle",
- "cn": "机舱发出风机进入检修或变桨检修命令",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Turbine is commanded for service from nacelle.(gbDI_SafetyChainNacelleWECinServiceGeneral=1 OR gbDI_NacelleWECinServiceManualPitch=1)",
- "trigger_cn": "机舱或机舱安全链发出风机检修命令。(gbDI_SafetyChainNacelleWECinServiceGeneral=1 OR gbDI_NacelleWECinServiceManualPitch=1)",
- "set_delay": "T#0s",
- "yp": "30",
- "reset_en": "Turbine is not commanded for service from nacelle.(gbDI_SafetyChainNacelleWECinServiceGeneral=0 AND gbDI_NacelleWECinServiceManualPitch=0)",
- "reset_cn": "机舱和机舱安全链发出风机检修命令。(gbDI_SafetyChainNacelleWECinServiceGeneral=0 AND gbDI_NacelleWECinServiceManualPitch=0)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "210-维护",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "210",
- "brake_state_design": "0"
- },
- "02_12_006": {
- "subsystem": "Cabinet",
- "name": "SC_ResetStatusCodesFromNacelleOrTowerBase",
- "en": "Statue code resetting is commanded from nacelle or turbine base",
- "cn": "机舱或塔底发出复位状态字命令",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Statue code resetting is commanded from nacelle or turbine base.(gbDI_NacelleResetStatusCodes=1 OR gbDI_TowerResetStatusCodes=1)",
- "trigger_cn": "机舱或塔底发出状态字复位命令。(gbDI_NacelleResetStatusCodes=1 OR gbDI_TowerResetStatusCodes=1)",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "Statue code resetting is not commanded from nacelle and turbine base.(gbDI_NacelleResetStatusCodes=0 AND gbDI_TowerResetStatusCodes=0)",
- "reset_cn": "机舱和塔底没有发出状态字复位命令。(gbDI_NacelleResetStatusCodes=0 AND gbDI_TowerResetStatusCodes=0)",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "03_02_001": {
- "subsystem": "Cabinet",
- "name": "SC_TempTowerBaseCabinetOutOfSpec",
- "en": "Temperature of towerbase cabinet is out of specification",
- "cn": "塔底柜恒温器测得温度高于设定值",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The environmental temperature for the cabinets is out of the specified range.(hardware input becomes FALSE)(gbDI_TowerTempCabinetOutOfSpec=0)",
- "trigger_cn": "塔底控制柜环境温度高于设计值。(相应的硬件输入为FALSE)(gbDI_TowerTempCabinetOutOfSpec=0)",
- "set_delay": "T#1m",
- "yp": "100",
- "reset_en": "The environmental temperature for the cabinets is within the specified range.(hardware input becomes TRUE)(gbDI_TowerTempCabinetOutOfSpec=1)",
- "reset_cn": "塔底控制柜环境温度在设计值内。(相应的硬件输入为TRUE)(gbDI_TowerTempCabinetOutOfSpec=1)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "03_02_004": {
- "subsystem": "Cabinet",
- "name": "SC_TowerNHFuse690VMAINSupply",
- "en": "The fuse for tower main supply 690V has tripped",
- "cn": "塔底柜690V电源熔断器故障",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The fuse for main power supply 690V has tripped(corresponding hardware input becomes FALSE).(gbDI_TowerNHFuse690VMainSupply=0)",
- "trigger_cn": "塔底主电源690V的保险丝跳闸(相应的硬件输入为False)。(gbDI_TowerNHFuse690VMainSupply=0)",
- "set_delay": "T#100ms",
- "yp": "100",
- "reset_en": "The fuse for main power supply 690V is OK(corresponding hardware input becomes TRUE).(gbDI_TowerNHFuse690VMainSupply=1)",
- "reset_cn": "塔底主电源690V的保险丝正常(相应的硬件输入为TRUE)。(gbDI_TowerNHFuse690VMainSupply=1)",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "100"
- },
- "03_02_006": {
- "subsystem": "Cabinet",
- "name": "SC_FaultOvervoltageProtectionTowerBase",
- "en": "Towerbase overvoltage protection system has tripped",
- "cn": "塔底柜690V,400V或变频柜主电源防雷器故障",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "One of the tower overvoltage protection components has tripped.(gbDI_TowerOvervoltageProtection690V=0 OR gbDI_TowerOvervoltageProtection400V=0 OR gbDI_TowerOvervoltageProtectionConverter=1)",
- "trigger_cn": "塔底的过电压保护元件之一跳闸。(gbDI_TowerOvervoltageProtection690V=0 OR gbDI_TowerOvervoltageProtection400V=0 OR gbDI_TowerOvervoltageProtectionConverter=1)",
- "set_delay": "T#5s",
- "yp": "0",
- "reset_en": "The tower overvoltage protection components have not tripped.(gbDI_TowerOvervoltageProtection690V=1 AND gbDI_TowerOvervoltageProtection400V=1 AND gbDI_TowerOvervoltageProtectionConverter=0)",
- "reset_cn": "塔底的过电压保护元件均无跳闸。(gbDI_TowerOvervoltageProtection690V=1 AND gbDI_TowerOvervoltageProtection400V=1 AND gbDI_TowerOvervoltageProtectionConverter=0)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "03_02_007": {
- "subsystem": "Cabinet",
- "name": "SC_TowerNHFuse400VMainSupply",
- "en": "The fuse for tower main supply 400V has tripped",
- "cn": "塔底柜400V电源熔断器故障",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The fuse for tower main supply 400V has tripped.(gbDI_TowerNHFuse400VMainSupply=0)",
- "trigger_cn": "塔底400V电源保险丝故障。(gbDI_TowerNHFuse400VMainSupply=0)",
- "set_delay": "T#100ms",
- "yp": "100",
- "reset_en": "The fuse for tower main supply 400V is OK.(gbDI_TowerNHFuse400VMainSupply=1)",
- "reset_cn": "塔底400V电源保险丝恢复正常。(gbDI_TowerNHFuse400VMainSupply=1)",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "100"
- },
- "03_02_011": {
- "subsystem": "Cabinet",
- "name": "SC_TowerFuse230VCabClimatisation",
- "en": "The fuse for tower 230V power supply has tripped",
- "cn": "塔底柜加热器或散热风扇的230V电源保护空开跳开",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The fuse for 230V tower power supply for the components for Cabinet Climatisation has tripped(corresponding hardware input becomes FALSE).(gbDI_TowerFuse230VCabinetClimatisation=0)",
- "trigger_cn": "塔底230V电源保险丝跳闸(相应的硬件输入为FALSE)。(gbDI_TowerFuse230VCabinetClimatisation=0)",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "The fuse for 230V tower power supply for the components for Cabinet Climatisation is OK(corresponding hardware input becomes TRUE).(gbDI_TowerFuse230VCabinetClimatisation=1)",
- "reset_cn": "塔底230V电源保险丝正常(相应的硬件输入为TRUE)。(gbDI_TowerFuse230VCabinetClimatisation=0)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "03_02_034": {
- "subsystem": "Cabinet",
- "name": "SC_TowerUPS24VPLC_Alarm",
- "en": "Warning, 24V UPS at tower base",
- "cn": "塔底24V UPS报警",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#10s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "03_02_035": {
- "subsystem": "Cabinet",
- "name": "SC_TowerUPS24VPLC_BatteryMode",
- "en": "Battery mode, 24V UPS at tower base",
- "cn": "塔底24V UPS电池模式",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "03_02_036": {
- "subsystem": "Cabinet",
- "name": "OC_TowerUPS24VPLC_BatteryCharge",
- "en": "Battery charging mode, 24V UPS at tower base",
- "cn": "塔底24V UPS电池充电模式",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "03_08_005": {
- "subsystem": "Cabinet",
- "name": "SC_TurbineInRepairTowerBase",
- "en": "turbine in repair mode by switch in towerbase",
- "cn": "塔底柜检修开关打开,要求风机进入检修模式",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "30",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "220-维修",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "220",
- "brake_state_design": "0"
- },
- "03_08_105": {
- "subsystem": "Cabinet",
- "name": "SC_TowerBrakeForClimbingActivated",
- "en": "Stopping turbine for a safe climbing of tower is requested by towerbase cabinet door button",
- "cn": "塔底柜的攀爬开关打开,要求停机安全爬塔",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The digital input at the tower base for stopping the turbine for a safe climbing of the tower is TRUE and the access rights are not allocated for the nacelle.(gbDI_TowerBrakeForClimbON=1 AND DI_SafetyChainNacelleWECinServiceGeneral=0 AND DI_NacelleWECinServiceManualPitch=0)",
- "trigger_cn": "塔底控制柜按钮为了安全爬塔要求停机。(gbDI_TowerBrakeForClimbON=1 AND DI_SafetyChainNacelleWECinServiceGeneral=0 AND DI_NacelleWECinServiceManualPitch=0)",
- "set_delay": "T#0s",
- "yp": "30",
- "reset_en": "The digital input at the tower base for stopping the turbine for a safe climbing of the tower is FALSE or the access rights are allocated for the nacelle.(gbDI_TowerBrakeForClimbON=0 OR DI_SafetyChainNacelleWECinServiceGeneral=1 OR DI_NacelleWECinServiceManualPitch=1)",
- "reset_cn": "塔底控制柜按钮没有按下停机。(gbDI_TowerBrakeForClimbON=0 OR DI_SafetyChainNacelleWECinServiceGeneral=1 OR DI_NacelleWECinServiceManualPitch=1)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "210-维护",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "210",
- "brake_state_design": "51"
- },
- "04_13_001": {
- "subsystem": "Cabinet",
- "name": "OC_CT_HeaterManualMode",
- "en": "",
- "cn": "塔底控制柜加热器手动模式开启",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "RemCmdACK_bEnableHeaterTowerCabinetManualControlMode",
- "trigger_cn": "",
- "set_delay": "T#50ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "True",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_13_002": {
- "subsystem": "Cabinet",
- "name": "OC_CT_HeaterForceMode",
- "en": "",
- "cn": "塔底控制柜加热器强制模式开启",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "RemCmdACK_bEnableHeaterTowerCabinetForceControlMode",
- "trigger_cn": "",
- "set_delay": "T#50ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "True",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_13_003": {
- "subsystem": "Cabinet",
- "name": "OC_CN_HeaterManualMode",
- "en": "",
- "cn": "机舱控制柜加热器手动模式开启",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "RemCmdACK_bEnableHeaterNacelleCabinetManualControlMode",
- "trigger_cn": "",
- "set_delay": "T#50ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "True",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_13_004": {
- "subsystem": "Cabinet",
- "name": "OC_CN_HeaterForceMode",
- "en": "",
- "cn": "机舱控制柜加热器强制模式开启",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "RemCmdACK_bEnableHeaterNacelleCabinetForceControlMode",
- "trigger_cn": "",
- "set_delay": "T#50ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "True",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "03_02_040": {
- "subsystem": "Cabinet",
- "name": "SC_TowerFuse24VMediaConvPlusBCSafetyChain",
- "en": "The fuse of tower 24V power supply for media converter has tripped",
- "cn": "塔底以太网交换器24V电源保险丝故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The fuse of tower 24V power supply for media converter has tripped(hardware input becomes FALSE).(gbDI_TowerFuse24V_MediaConvPlusBCSafetyChain=0)",
- "trigger_cn": "塔底以太网交换器24V电源保险丝故障(相应的应减少输入为FALSE)。(gbDI_TowerFuse24V_MediaConvPlusBCSafetyChain=0)",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "The fuse of tower 24V power supply for media converter is OK(hardware input becomes TRUE).(gbDI_TowerFuse24V_MediaConvPlusBCSafetyChain=1)",
- "reset_cn": "塔底以太网交换器24V电源保险丝故障解除(相应的应减少输入为TRUE)。(gbDI_TowerFuse24V_MediaConvPlusBCSafetyChain=1)",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "03_02_100": {
- "subsystem": "Cabinet",
- "name": "OC_TowerHeaterCabinet_ON",
- "en": "Towerbase cabinet heater turns on",
- "cn": "塔底控制柜加热器打开",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "PLC output for control of TowerBase Cabinet Heater becomes TRUE.(gbDI_TowerHeaterCabinetON=1 OR DQ_TowerHeaterCabinetTowerBase=1)",
- "trigger_cn": "塔底控制柜加热器控制输出为TRUE。(gbDI_TowerHeaterCabinetON=1 OR DQ_TowerHeaterCabinetTowerBase=1)",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "PLC output for control of TowerBase Cabinet Heater becomes FALSE.(gbDI_TowerHeaterCabinetON=0 AND DQ_TowerHeaterCabinetTowerBase=0)",
- "reset_cn": "塔底控制柜加热器控制输出为FALSE。(gbDI_TowerHeaterCabinetON=0 AND DQ_TowerHeaterCabinetTowerBase=0)",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "03_02_109": {
- "subsystem": "Cabinet",
- "name": "OC_ControlCabinetHeatingMode",
- "en": "Either nacelle or tower base control cabinet is heating up",
- "cn": "控制柜暖机模式",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "NOT gbDI_TowerSingleShotRelayON_x000D_ AND (gbDI_NacelleHeaterCabinetON OR gbDI_TowerHeaterCabinetON)_x000D_ AND (grTempCabinetNacelle_10min<PAR_rTempMIN_CabinetNacelle OR grTempCabinetTowerBase_10min <_x000D_ PAR_rTempMIN_CabinetTower",
- "trigger_cn": "控制器首次上电,机舱柜或塔底柜正在加热中",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "Both nacelle and towerbase control cabinet temp higher than minimum parameter",
- "reset_cn": "机舱柜和塔底柜温度高于下限值",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "30-待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "30",
- "brake_state_design": "50"
- },
- "03_02_110": {
- "subsystem": "Cabinet",
- "name": "SC_CabinetHeatingModeTimeout",
- "en": "Cabinet heating mode time out",
- "cn": "控制柜暖机超时",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "OC_ControlCabinetHeatingMode is TRUE",
- "trigger_cn": "控制柜暖机模式持续时间过长",
- "set_delay": "T#30m",
- "yp": "0",
- "reset_en": "OC_ControlCabinetHeatingMode is FALSE",
- "reset_cn": "退出控制柜暖机模式",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "03_03_001": {
- "subsystem": "Cabinet",
- "name": "SC_TempTowerBase_high",
- "en": "Towerbase temperature is too high",
- "cn": "塔底温度过高警告",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "3",
- "repeat_period": "T#24h",
- "trigger_en": "The 10min-mean-value of the temperature exceeds the value given by parameter.(grTempTowerBase_10min > PAR_rTempHigh_TowerBase)",
- "trigger_cn": "塔底10分钟平均温度高于过高设定值。(grTempTowerBase_10min > PAR_rTempHigh_TowerBase)",
- "set_delay": "T#1m",
- "yp": "0",
- "reset_en": "The 10min-mean-value of temperature falls below the value given by parameter minus a hysteresis value OR get reset signal of status code coming from Nacelle, Tower or Remote Command.((grTempTowerBase_10min < (PAR_rTempHigh_TowerBase - PAR_rTempHysteresisUpperTemp)) OR gbMAIN_ResetStatusCodes=1)",
- "reset_cn": "塔底温度(10分钟平均值)小于设定值减去一个滞后值或收到reset信号。((grTempTowerBase_10min < (PAR_rTempHigh_TowerBase - PAR_rTempHysteresisUpperTemp)) OR gbMAIN_ResetStatusCodes=1)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "03_03_002": {
- "subsystem": "Cabinet",
- "name": "SC_TempTowerBase_low",
- "en": "Towerbase temperature is too low",
- "cn": "塔底温度过低警告",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "3",
- "repeat_period": "T#24h",
- "trigger_en": "The 10min-mean-value of the temperature falls below the value given by parameter.(grTempTowerBase_10min < PAR_rTempLow_TowerBase)",
- "trigger_cn": "塔底10分钟平均温度低于过低设定值。(grTempTowerBase_10min < PAR_rTempLow_TowerBase)",
- "set_delay": "T#1m",
- "yp": "0",
- "reset_en": "The 10min-mean-value of temperature increases above the value given by parameter plus a hysteresis value OR get reset signal of status code coming from Nacelle, Tower or Remote Command. ((grTempTowerBase_10min > (PAR_rTempLow_TowerBase + PAR_rTempHysteresisLowerTemp)) OR gbMAIN_ResetStatusCodes=1)",
- "reset_cn": "塔底温度(10分钟平均值)大于设定值加上一个滞后值或收到reset信号。((grTempTowerBase_10min > (PAR_rTempLow_TowerBase + PAR_rTempHysteresisLowerTemp)) OR gbMAIN_ResetStatusCodes=1)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "03_03_003": {
- "subsystem": "Cabinet",
- "name": "SC_TempTowerBase_MAX",
- "en": "Towerbase temperature exceeds maximum limit",
- "cn": "塔底温度过高故障",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The 10min-mean-value of the temperature exceeds the maximum limit value given by parameter.(grTempTowerBase_10min > PAR_rTempMAX_TowerBase)",
- "trigger_cn": "塔底10分钟平均温度高于上限值。(grTempTowerBase_10min > PAR_rTempMAX_TowerBase)",
- "set_delay": "T#1m",
- "yp": "0",
- "reset_en": "The 10min-mean-value of temperature falls below the value given by parameter minus a hysteresis value OR get reset signal of status code coming from Nacelle, Tower or Remote Command.((grTempTowerBase_10min < (PAR_rTempMAX_TowerBase - PAR_rTempHysteresisUpperTemp)) OR gbMAIN_ResetStatusCodes=1)",
- "reset_cn": "塔底温度(10分钟平均值)小于上限值减去一个滞后值或收到reset信号。((grTempTowerBase_10min < (PAR_rTempMAX_TowerBase - PAR_rTempHysteresisUpperTemp)) OR gbMAIN_ResetStatusCodes=1)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "03_03_004": {
- "subsystem": "Cabinet",
- "name": "SC_TempTowerBase_MIN",
- "en": "Towerbase temperature exceeds minimum limit",
- "cn": "塔底温度过低故障",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "The 10min-mean-value of the temperature falls below the minimum limit value given by parameter.(grTempTowerBase_10min < PAR_rTempMIN_TowerBase)",
- "trigger_cn": "塔底10分钟平均温度低于下限值。(grTempTowerBase_10min < PAR_rTempMIN_TowerBase)",
- "set_delay": "T#1m",
- "yp": "0",
- "reset_en": "The 10min-mean-value of temperature increases above the value given by parameter plus a hysteresis value OR get reset signal of status code coming from Nacelle, Tower or Remote Command. ((grTempTowerBase_10min > (PAR_rTempMIN_TowerBase + PAR_rTempHysteresisLowerTemp)) OR gbMAIN_ResetStatusCodes=1)",
- "reset_cn": "塔底温度(10分钟平均值)大于下限值加上一个滞后值或收到reset信号。((grTempTowerBase_10min > (PAR_rTempMIN_TowerBase + PAR_rTempHysteresisLowerTemp)) OR gbMAIN_ResetStatusCodes=1)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "50"
- },
- "03_03_007": {
- "subsystem": "Cabinet",
- "name": "SC_RepFaultTempTowerBase",
- "en": "The faults, towerbase temperature is too high or low, have repeated",
- "cn": "塔底温度过高过低警告重复出现",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "One of the statuscodes for the referred temperature for \"temperature too high\" or \"temperature too low\" in a given time periode becomes more times TRUE than maximum allowed.(gbRepeat_03_03_001=1 OR gbRepeat_03_03_002=1)",
- "trigger_cn": "塔底温度过高过低故障重复出现次数大于设定值。(gbRepeat_03_03_001=1 OR gbRepeat_03_03_002=1)",
- "set_delay": "T#1m",
- "yp": "0",
- "reset_en": "One of the statuscodes for the referred temperature for \"temperature too high\" or \"temperature too low\" in a given time periode becomes less times TRUE than maximum allowed.(gbRepeat_03_03_001=0 AND gbRepeat_03_03_002=0)",
- "reset_cn": "塔底温度过高过低故障重复出现次数不大于设定值。(gbRepeat_03_03_001=0 AND gbRepeat_03_03_002=0)",
- "reset_mode": "M",
- "type": "A",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "50"
- },
- "03_07_010": {
- "subsystem": "Cabinet",
- "name": "SC_TowerDoorSwitchSignalOpen",
- "en": "TowerDoorSwitchSignalOpen",
- "cn": "塔筒门被打开",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "gbDI_bTowerDoorSwitchSignal=0 AND PAR_bTowerDoorSwitchSignal=1",
- "trigger_cn": "gbDI_bTowerDoorSwitchSignal=0 AND PAR_bTowerDoorSwitchSignal=1",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "gbDI_bTowerDoorSwitchSignal=1 OR PAR_bTowerDoorSwitchSignal=0",
- "reset_cn": "gbDI_bTowerDoorSwitchSignal=1 OR PAR_bTowerDoorSwitchSignal=0",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "01_05_013": {
- "subsystem": "Pitchsystem",
- "name": "SC_Blade1_PilotContactNotConnected",
- "en": "Blade1 pilot contact is not connected",
- "cn": "1号电池柜航空插头没有插好",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Blade1 pilot contact is not connected.(di_Blade1_PilotContactNotConnected=1)",
- "trigger_cn": "如果变桨系统报“叶片1的Pilot接触器没有连接”(di_Blade1_PilotContactNotConnected=1)",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "Blade1 pilot contact is reconnected and special individual reset-conditions are fulfilled(di_Blade1_PilotContactNotConnected=O AND bSpecResCond=1)",
- "reset_cn": "叶片1的Pilot接触器重新连接(di_Blade1_PilotContactNotConnected=O AND bSpecResCond=1)",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "01_05_014": {
- "subsystem": "Pitchsystem",
- "name": "SC_Blade1_DCLinkVoltageTooLow",
- "en": "Blade1 DC link voltage is too low",
- "cn": "1号桨PM直流母线电压低",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Blade1 DC link voltage is too low.(di_Blade1_DCLinkVoltageTooLow=1 AND di_Blade2_DCLinkVoltageTooLow=0 AND di_Blade3_DCLinkVoltageTooLow=0)",
- "trigger_cn": "如果变桨系统报“叶片1的直流传输线电压过低,叶片2和叶片3的正常”(di_Blade1_DCLinkVoltageTooLow=1 AND di_Blade2_DCLinkVoltageTooLow=0 AND di_Blade3_DCLinkVoltageTooLow=0)",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "Blade1 DC link voltage is OK and special individual reset-conditions are fulfilled(di_Blade1_DCLinkVoltageTooLow=0 AND di_Blade2_DCLinkVoltageTooLow=0 AND di_Blade3_DCLinkVoltageTooLow=0)AND bSpecResCond=1",
- "reset_cn": "1号桨的直流传输线电压恢复正常。(di_Blade1_DCLinkVoltageTooLow=0 AND di_Blade2_DCLinkVoltageTooLow=0 AND di_Blade3_DCLinkVoltageTooLow=0)AND bSpecResCond=1",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "01_05_017": {
- "subsystem": "Pitchsystem",
- "name": "SC_Blade1_CollectiveWarning",
- "en": "Blade1 Collects Warning",
- "cn": "1号桨的出现警报",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Blade1 Collects Warning.(di_Blade1_SummaryWarning=1)",
- "trigger_cn": "如果变桨系统报“叶片1出现警报”(di_Blade1_SummaryWarning=1)",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "Blade1 Warning is clear and special individual reset-conditions are fulfilled(di_Blade1_SummaryWarning=0 AND bSpecResCond=1)",
- "reset_cn": "叶片1的警报解除(di_Blade1_SummaryWarning=0 AND bSpecResCond=1)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "01_05_018": {
- "subsystem": "Pitchsystem",
- "name": "SC_Blade1_ErrorWithBatteryDrivenSTOP",
- "en": "Blade1 has errors with battery drive",
- "cn": "1号桨故障,触发电池驱动回桨",
- "powerup_delay": "T#0s",
- "disable_level": "50",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Blade1 has errors with battery drive.(di_Blade1_GeneralDriveError=1 OR di_Blade1_OverCurrentBySoftware=1 OR di_Blade1_OverVoltageDCLink=1 OR di_Blade1_RMSOverCurrentMotorProtect=1 OR di_Blade1_OverCurrentConverterProtect=1 OR di_Blade1_OverCurrentConverterProtect=1 OR di_Blade1_WireDisconnectionSSI=1 OR di_Blade1_WireDisconnectionResolver=1 OR di_Blade1_OvertempConverter=1 OR di_Blade1_DCFuseInverter=1 OR di_Blade1_Fuse6f1VoltageTripped=1)",
- "trigger_cn": "如果变桨系统报“叶片1出现电池驱动故障”(di_Blade1_GeneralDriveError=1 OR di_Blade1_OverCurrentBySoftware=1 OR di_Blade1_OverVoltageDCLink=1 OR di_Blade1_RMSOverCurrentMotorProtect=1 OR di_Blade1_OverCurrentConverterProtect=1 OR di_Blade1_OverCurrentConverterProtect=1 OR di_Blade1_WireDisconnectionSSI=1 OR di_Blade1_WireDisconnectionResolver=1 OR di_Blade1_OvertempConverter=1 OR di_Blade1_DCFuseInverter=1)",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "Blade1 battery drive is OK fulfilled(di_Blade1_GeneralDriveError=0 AND di_Blade1_OverCurrentBySoftware=0 AND di_Blade1_OverVoltageDCLink=0 AND di_Blade1_RMSOverCurrentMotorProtect=0 AND di_Blade1_OverCurrentConverterProtect=0 AND di_Blade1_OverCurrentConverterProtect=0 AND di_Blade1_WireDisconnectionSSI=0 AND di_Blade1_WireDisconnectionResolver=0 AND di_Blade1_OvertempConverter=0 AND di_Blade1_DCFuseInverter=0 )",
- "reset_cn": "叶片1的电池驱动正常(di_Blade1_GeneralDriveError=0 AND di_Blade1_OverCurrentBySoftware=0 AND di_Blade1_OverVoltageDCLink=0 AND di_Blade1_RMSOverCurrentMotorProtect=0 AND di_Blade1_OverCurrentConverterProtect=0 AND di_Blade1_OverCurrentConverterProtect=0 AND di_Blade1_WireDisconnectionSSI=0 AND di_Blade1_WireDisconnectionResolver=0 AND di_Blade1_OvertempConverter=0 AND di_Blade1_DCFuseInverter=0 )",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "198"
- },
- "01_05_033": {
- "subsystem": "Pitchsystem",
- "name": "SC_Blade2_PilotContactNotConnected",
- "en": "Blade2 pilot contact is not connected",
- "cn": "2号电池柜航空插头没有插好",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Blade2 pilot contact is not connected.",
- "trigger_cn": "如果变桨系统报“叶片2的Pilot接触器没有连接”(di_Blade2_PilotContactNotConnected=1)",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "Blade2 pilot contact is reconnected and special individual reset-conditions are fulfilled(di_Blade2_PilotContactNotConnected=0 AND bSpecResCond=1)",
- "reset_cn": "叶片2的Pilot接触器重新连接(di_Blade2_PilotContactNotConnected=0 AND bSpecResCond=1)",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "01_05_034": {
- "subsystem": "Pitchsystem",
- "name": "SC_Blade2_DCLinkVoltageTooLow",
- "en": "Blade2 DC link voltage is too low",
- "cn": "2号桨PM直流母线电压低",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Blade2 DC link voltage is too low.(di_Blade2_DCLinkVoltageTooLow=1 AND di_Blade1_DCLinkVoltageTooLow=0 AND di_Blade3_DCLinkVoltageTooLow=0)",
- "trigger_cn": "如果变桨系统报“叶片2的直流传输线电压过低,叶片1和叶片3的正常”。(di_Blade2_DCLinkVoltageTooLow=1 AND di_Blade1_DCLinkVoltageTooLow=0 AND di_Blade3_DCLinkVoltageTooLow=0)",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "Blade2 DC link voltage is OK and special individual reset-conditions are fulfilled(di_Blade2_DCLinkVoltageTooLow=0 OR di_Blade1_DCLinkVoltageTooLow=1 OR di_Blade3_DCLinkVoltageTooLow=1)AND bSpecResCond=1",
- "reset_cn": "叶片2的直流传输线电压恢复正常。(di_Blade2_DCLinkVoltageTooLow=0 AND di_Blade1_DCLinkVoltageTooLow=0 AND di_Blade3_DCLinkVoltageTooLow=0)AND bSpecResCond=1",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "01_05_037": {
- "subsystem": "Pitchsystem",
- "name": "SC_Blade2_CollectiveWarning",
- "en": "Blade2 Collects Warning",
- "cn": "2号桨的出现警报",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Blade2 Collects Warning.(di_Blade2_SummaryWarning=1)",
- "trigger_cn": "如果变桨系统报“叶片2出现警报”(di_Blade2_SummaryWarning=1)",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "Blade2 Warning is clear and special individual reset-conditions are fulfilled(di_Blade2_SummaryWarning=0 AND bSpecResCond=1)",
- "reset_cn": "叶片2的警报解除(di_Blade2_SummaryWarning=0 AND bSpecResCond=1)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "01_05_038": {
- "subsystem": "Pitchsystem",
- "name": "SC_Blade2_ErrorWithBatteryDrivenSTOP",
- "en": "Blade2 has errors with battery drive",
- "cn": "2号桨故障,触发电池驱动回桨",
- "powerup_delay": "T#0s",
- "disable_level": "50",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Blade2 has errors with battery drive.(di_Blade2_GeneralDriveError=1 OR di_Blade2_OverCurrentBySoftware=1 OR di_Blade2_OverVoltageDCLink=1 OR di_Blade2_RMSOverCurrentMotorProtect=1 OR di_Blade2_OverCurrentConverterProtect OR di_Blade2_OverCurrentConverterProtect=1 OR di_Blade2_ErrorCAN_Module=1 OR di_Blade2_WireDisconnectionSSI=1 OR di_Blade2_WireDisconnectionResolver=1 OR di_Blade2_OvertempConverter=1 OR di_Blade2_DCFuseInverter=1)",
- "trigger_cn": "如果变桨系统报“叶片2出现电池驱动故障”(di_Blade2_GeneralDriveError=1 OR di_Blade2_OverCurrentBySoftware=1 OR di_Blade2_OverVoltageDCLink=1 OR di_Blade2_RMSOverCurrentMotorProtect=1 OR di_Blade2_OverCurrentConverterProtect OR di_Blade2_OverCurrentConverterProtect=1 OR di_Blade2_ErrorCAN_Module=1 OR di_Blade2_WireDisconnectionSSI=1 OR di_Blade2_WireDisconnectionResolver=1 OR di_Blade2_OvertempConverter=1 OR di_Blade2_DCFuseInverter=1)",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "Blade2 battery drive is OK and special individual reset-conditions are fulfilled(di_Blade2_GeneralDriveError=0 AND di_Blade2_OverCurrentBySoftware=0 AND di_Blade2_OverVoltageDCLink=0 AND di_Blade2_RMSOverCurrentMotorProtect=0 AND di_Blade2_OverCurrentConverterProtect=0 AND di_Blade2_OverCurrentConverterProtect=0 AND di_Blade2_ErrorCAN_Module=0 AND di_Blade2_WireDisconnectionSSI=0 AND di_Blade2_WireDisconnectionResolver=0 di_Blade2_OvertempConverter=0 AND di_Blade2_DCFuseInverter=0) AND bSpecResCond=1",
- "reset_cn": "叶片2的电池驱动正常(di_Blade2_GeneralDriveError=0 AND di_Blade2_OverCurrentBySoftware=0 AND di_Blade2_OverVoltageDCLink=0 AND di_Blade2_RMSOverCurrentMotorProtect=0 AND di_Blade2_OverCurrentConverterProtect=0 AND di_Blade2_OverCurrentConverterProtect=0 AND di_Blade2_ErrorCAN_Module=0 AND di_Blade2_WireDisconnectionSSI=0 AND di_Blade2_WireDisconnectionResolver=0 di_Blade2_OvertempConverter=0 AND di_Blade2_DCFuseInverter=0) AND bSpecResCond=1",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "198"
- },
- "01_05_053": {
- "subsystem": "Pitchsystem",
- "name": "SC_Blade3_PilotContactNotConnected",
- "en": "Blade3 pilot contact is not connected",
- "cn": "3号电池柜航空插头没有插好",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Blade3 pilot contact is not connected(di_Blade3_PilotContactNotConnected=1)",
- "trigger_cn": "如果变桨系统报“叶片3的Pilot接触器没有连接”(di_Blade3_PilotContactNotConnected=1)",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "Blade3 pilot contact is reconnected and special individual reset-conditions are fulfilled(di_Blade3_PilotContactNotConnected=O AND bSpecResCond=1)",
- "reset_cn": "叶片3的Pilot接触器重新连接(di_Blade3_PilotContactNotConnected=O AND bSpecResCond=1)",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "01_05_054": {
- "subsystem": "Pitchsystem",
- "name": "SC_Blade3_DCLinkVoltageTooLow",
- "en": "Blade3 DC link voltage is too low",
- "cn": "3号桨PM直流母线电压低",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Blade3 DC link voltage is too low.(di_Blade3_DCLinkVoltageTooLow=1 AND di_Blade2_DCLinkVoltageTooLow=0 AND di_Blade1_DCLinkVoltageTooLow=0)",
- "trigger_cn": "_x000D_ 如果变桨系统报“叶片3的直流传输线电压过低,叶片1和叶片2的正常”。(di_Blade3_DCLinkVoltageTooLow=1 AND di_Blade2_DCLinkVoltageTooLow=0 AND di_Blade1_DCLinkVoltageTooLow=0)",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "Blade3 DC link voltage is OK and special individual reset-conditions are fulfilled(di_Blade3_DCLinkVoltageTooLow=0 OR di_Blade2_DCLinkVoltageTooLow=1 OR di_Blade1_DCLinkVoltageTooLow=1) AND bSpecResCond=1",
- "reset_cn": "叶片3的直流传输线电压恢复正常。(di_Blade1_DCLinkVoltageTooLow=0 AND di_Blade2_DCLinkVoltageTooLow=0 AND di_Blade3_DCLinkVoltageTooLow=0)AND bSpecResCond=1",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "01_05_057": {
- "subsystem": "Pitchsystem",
- "name": "SC_Blade3_CollectiveWarning",
- "en": "Blade3 Collects Warning",
- "cn": "3号桨的出现警报",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Blade3 Collects Warning.(di_Blade3_SummaryWarning=1)",
- "trigger_cn": "如果变桨系统报“叶片3出现警报”(di_Blade3_SummaryWarning=1)",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "Blade3 Warning is clear and special individual reset-conditions are fulfilled(di_Blade3_SummaryWarning=1 AND bSpecResCond=1)",
- "reset_cn": "叶片3的警报解除(di_Blade3_SummaryWarning=1 AND bSpecResCond=1)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "01_05_058": {
- "subsystem": "Pitchsystem",
- "name": "SC_Blade3_ErrorWithBatteryDrivenSTOP",
- "en": "Blade3 has errors with battery drive",
- "cn": "3号桨故障,触发电池驱动回桨",
- "powerup_delay": "T#0s",
- "disable_level": "50",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Blade3 has errors with battery drive.(di_Blade3_GeneralDriveError=1 OR di_Blade3_OverCurrentBySoftware=1 OR di_Blade3_OverVoltageDCLink=1 OR di_Blade3_RMSOverCurrentMotorProtect=1 OR di_Blade3_OverCurrentConverterProtect=1 OR di_Blade3_ErrorCAN_Module=1 OR di_Blade3_WireDisconnectionSSI=1 OR di_Blade3_WireDisconnectionResolver=1 OR di_Blade3_OvertempConverter=1 OR di_Blade3_DCFuseInverter=1)",
- "trigger_cn": "如果变桨系统报“叶片3出现电池驱动故障”(di_Blade3_GeneralDriveError=1 OR di_Blade3_OverCurrentBySoftware=1 OR di_Blade3_OverVoltageDCLink=1 OR di_Blade3_RMSOverCurrentMotorProtect=1 OR di_Blade3_OverCurrentConverterProtect=1 OR di_Blade3_ErrorCAN_Module=1 OR di_Blade3_WireDisconnectionSSI=1 OR di_Blade3_WireDisconnectionResolver=1 OR di_Blade3_OvertempConverter=1 OR di_Blade3_DCFuseInverter=1)",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "Blade3 battery drive is OK and special individual reset-conditions are fulfilled(di_Blade3_GeneralDriveError=0 AND di_Blade3_OverCurrentBySoftware=0 AND di_Blade3_OverVoltageDCLink=0 AND di_Blade3_RMSOverCurrentMotorProtect=0 AND di_Blade3_OverCurrentConverterProtect=0 AND di_Blade3_ErrorCAN_Module=0 AND di_Blade3_WireDisconnectionSSI=0 AND di_Blade3_WireDisconnectionResolver=0 AND di_Blade3_OvertempConverter=0 AND di_Blade3_DCFuseInverter=0) AND bSpecResCond=1",
- "reset_cn": "叶片3的电池驱动恢复正常(di_Blade3_GeneralDriveError=0 AND di_Blade3_OverCurrentBySoftware=0 AND di_Blade3_OverVoltageDCLink=0 AND di_Blade3_RMSOverCurrentMotorProtect=0 AND di_Blade3_OverCurrentConverterProtect=0 AND di_Blade3_ErrorCAN_Module=0 AND di_Blade3_WireDisconnectionSSI=0 AND di_Blade3_WireDisconnectionResolver=0 AND di_Blade3_OvertempConverter=0 AND di_Blade3_DCFuseInverter=0) AND bSpecResCond=1",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "198"
- },
- "01_05_061": {
- "subsystem": "pitchsystem",
- "name": "SC_PitchSystem24VTripped",
- "en": "the fault of battery when drive the blade",
- "cn": "变桨系统24V电源故障",
- "powerup_delay": "T#0s",
- "disable_level": "50",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "IF di_Blade1_Fuse6f1VoltageTripped OR di_Blade2_Fuse6f1VoltageTripped OR di_Blade3_Fuse6f1VoltageTripped_x000D_ THEN_x000D_ SC_PitchSystem24VTripped=true",
- "trigger_cn": "当电池驱动桨叶时三个电池的故障位任一个被触发后,该SC被触发",
- "set_delay": "T#5.1s",
- "yp": "0",
- "reset_en": "IF not (di_Blade1_Fuse6f1VoltageTripped OR di_Blade2_Fuse6f1VoltageTripped OR di_Blade3_Fuse6f1VoltageTripped)_x000D_ THEN_x000D_ SC_PitchSystem24VTripped=true",
- "reset_cn": "当电池驱动桨叶时三个电池的故障位都没有被触发后,该SC被复位",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "100"
- },
- "01_05_062": {
- "subsystem": "Pitchsystem",
- "name": "SC_ErrorBatteryChargerAxis1or2or3",
- "en": "Battery charger of Blade1 or Blade2 or Blade3 has error",
- "cn": "变桨系统电池充电回路故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Battery charger of Blade1 or Blade2 or Blade3 has error.(di_Blade1_CBBatteryChargerTripped=1 OR di_Blade1_ErrorBatteryChargerBit_0=1 OR di_Blade1_ErrorBatteryChargerBit_1=1 OR di_Blade2_CBBatteryChargerTripped=1 OR di_Blade2_ErrorBatteryChargerBit_0=1 OR di_Blade2_ErrorBatteryChargerBit_1=1 OR di_Blade3_CBBatteryChargerTripped=1 OR di_Blade3_ErrorBatteryChargerBit_0=1 OR i_Blade3_ErrorBatteryChargerBit_1=1)",
- "trigger_cn": "如果变桨系统报“叶片1或叶片2或叶片3的电池充电器发生故障”(di_Blade1_CBBatteryChargerTripped=1 OR di_Blade1_ErrorBatteryChargerBit_0=1 OR di_Blade1_ErrorBatteryChargerBit_1=1 OR di_Blade2_CBBatteryChargerTripped=1 OR di_Blade2_ErrorBatteryChargerBit_0=1 OR di_Blade2_ErrorBatteryChargerBit_1=1 OR di_Blade3_CBBatteryChargerTripped=1 OR di_Blade3_ErrorBatteryChargerBit_0=1 OR i_Blade3_ErrorBatteryChargerBit_1=1)",
- "set_delay": "PAR_tSetDelayForBatteryChargerFault",
- "yp": "0",
- "reset_en": "Battery charger of Blade1 or Blade2 or Blade3 is OK and special individual reset-conditions are fulfilled(di_Blade1_CBBatteryChargerTripped=0 AND di_Blade1_ErrorBatteryChargerBit_0=0 AND di_Blade1_ErrorBatteryChargerBit_1=0 AND di_Blade2_CBBatteryChargerTripped=0 AND di_Blade2_ErrorBatteryChargerBit_0=0 AND di_Blade2_ErrorBatteryChargerBit_1=0 AND di_Blade3_CBBatteryChargerTripped=0 AND di_Blade3_ErrorBatteryChargerBit_0=0 AND i_Blade3_ErrorBatteryChargerBit_1=0)",
- "reset_cn": "叶片1、叶片2、叶片3的电池充电器故障解除(di_Blade1_CBBatteryChargerTripped=0 AND di_Blade1_ErrorBatteryChargerBit_0=0 AND di_Blade1_ErrorBatteryChargerBit_1=0 AND di_Blade2_CBBatteryChargerTripped=0 AND di_Blade2_ErrorBatteryChargerBit_0=0 AND di_Blade2_ErrorBatteryChargerBit_1=0 AND di_Blade3_CBBatteryChargerTripped=0 AND di_Blade3_ErrorBatteryChargerBit_0=0 AND i_Blade3_ErrorBatteryChargerBit_1=0)",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "01_05_069": {
- "subsystem": "Pitchsystem",
- "name": "SC_Pitch_CollectiveFaultMessage",
- "en": "Pitch system collects fault message",
- "cn": "变桨系统发生2级故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Pitch system collects fault message(di_Pitch_NoFault=0)",
- "trigger_cn": "变桨系统发现故障。(di_Pitch_NoFault=0 )",
- "set_delay": "T#5.1s",
- "yp": "0",
- "reset_en": "Fault messgae is clear and special individual reset-conditions are fulfilled(di_Pitch_NoFault=1 AND bSpecResCond=1)",
- "reset_cn": "故障清除且满足reset条件(di_Pitch_NoFault=1 AND bSpecResCond=1)",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "198"
- },
- "01_05_070": {
- "subsystem": "Pitchsystem",
- "name": "SC_Pitch_ErrorWithBatteryDrivenSTOP",
- "en": "Pitch system CAN or Profibus communication has fault",
- "cn": "变桨系统与主控系统的Profibus通讯或与PM的CAN通讯出现故障",
- "powerup_delay": "T#0s",
- "disable_level": "50",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Pitch system CAN or Profibus communication has fault.(diPitchMotorEncoderIncoherence=1 AND giTurbineOperationMode>=17) OR diPitch_CAN_Node1Error=1 OR diPitch_CAN_Node2Error=1 OR diPitch_CAN_Node3Error=1 OR diPitch_CAN_Node4Error=1 OR diPitch_CAN_Node5Error=1 OR diPitch_CAN_Node6Error=1 OR diPitch_CANbusGlobalError=1 OR diPitch_ProfibusError=1",
- "trigger_cn": "变桨系统在启动之后出现任一CAN通讯或Profibus通讯出现故障.(diPitchMotorEncoderIncoherence=1 AND giTurbineOperationMode>=CON_iStartMode) OR diPitch_CAN_Node1Error=1 OR diPitch_CAN_Node2Error=1 OR diPitch_CAN_Node3Error=1 OR diPitch_CAN_Node4Error=1 OR diPitch_CAN_Node5Error=1 OR diPitch_CAN_Node6Error=1 OR diPitch_CANbusGlobalError=1 OR diPitch_ProfibusError=1",
- "set_delay": "PAR_tSetDelayForCANProfibus",
- "yp": "0",
- "reset_en": "The fault of Pitch system CAN or Profibus communication is clear and special individual reset-conditions are fulfilled.(diPitchMotorEncoderIncoherence=0 OR giTurbineOperationMode>=17) AND diPitch_CAN_Node1Error=0 AND diPitch_CAN_Node2Error=0 AND diPitch_CAN_Node3Error=0 AND diPitch_CAN_Node4Error=0 AND diPitch_CAN_Node5Error=0 AND diPitch_CAN_Node6Error=0 AND diPitch_CANbusGlobalError=0 AND diPitch_ProfibusError=0 AND bSpecResCond=1",
- "reset_cn": "变桨系统在启动之后的CAN通讯或Profibus通讯故障均无。(diPitchMotorEncoderIncoherence=0 OR giTurbineOperationMode>=CON_iStartMode) AND diPitch_CAN_Node1Error=0 AND diPitch_CAN_Node2Error=0 AND diPitch_CAN_Node3Error=0 AND diPitch_CAN_Node4Error=0 AND diPitch_CAN_Node5Error=0 AND diPitch_CAN_Node6Error=0 AND diPitch_CANbusGlobalError=0 AND diPitch_ProfibusError=0 AND bSpecResCond=1",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "200"
- },
- "01_05_076": {
- "subsystem": "Pitchsystem",
- "name": "SC_Pitch_CollectiveWarning",
- "en": "Pitch system collects Warnings",
- "cn": "变桨系统出现警告",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Pitch system collects Warnings.(di_Pitch_CollectiveWarning=1 OR di_Blade1_SummaryWarning=1 OR di_Blade2_SummaryWarning=1 OR di_Blade3_SummaryWarning=1)",
- "trigger_cn": "变桨系统的任一桨叶发出警告.(di_Pitch_CollectiveWarning=1 OR di_Blade1_SummaryWarning=1 OR di_Blade2_SummaryWarning=1 OR di_Blade3_SummaryWarning=1)",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "Warnings of Pitch system are clear.(di_Pitch_CollectiveWarning=0 AND di_Blade1_SummaryWarning=0 AND di_Blade2_SummaryWarning=0 AND di_Blade3_SummaryWarning=0 AND bSpecResCond=1)",
- "reset_cn": "变桨系统的所有桨叶警告解除。(di_Pitch_CollectiveWarning=0 AND di_Blade1_SummaryWarning=0 AND di_Blade2_SummaryWarning=0 AND di_Blade3_SummaryWarning=0 AND bSpecResCond=1)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "01_05_077": {
- "subsystem": "Pitchsystem",
- "name": "SC_Pitch_MainsFailure",
- "en": "Pitch system mains power has fault",
- "cn": "变桨系统400V电网存在故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Pitch system mains power has fault.(diPitch_MainsFailure=1)",
- "trigger_cn": "变桨系统的供电网发生故障。(diPitch_MainsFailure=1)",
- "set_delay": "T#5s",
- "yp": "0",
- "reset_en": "Pitch system mains power fault is clear. diPitch_MainsFailure=0",
- "reset_cn": "变桨系统的供电网故障解除。diPitch_MainsFailure=0",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "01_05_100": {
- "subsystem": "pitchsystem",
- "name": "SC_Blade3_OvertempStartResistorAxis1or2or3",
- "en": "Overtemperature, precharging resistance, blade 1,2 or 3",
- "cn": "1号,2号或3号桨报告预充电电阻过温",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "01_05_104": {
- "subsystem": "PitchSystem",
- "name": "SC_Pitch_CANBusError",
- "en": "Pitch System Internal CAN error",
- "cn": "变桨系统与PM的CAN通讯故障",
- "powerup_delay": "T#0s",
- "disable_level": "50",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Pitch System have CAN Nodes Error.(diPitch_CAN_Node1Error=1 OR diPitch_CAN_Node2Error=1 OR diPitch_CAN_Node3Error=1 OR diPitch_CAN_Node4Error=1 OR diPitch_CAN_Node5Error=1 OR diPitch_CAN_Node6Error=1 OR diPitch_CANbusGlobalError=1)",
- "trigger_cn": "变桨系统内部CAN1-6号某节点发生故障。(diPitch_CAN_Node1Error=1 OR diPitch_CAN_Node2Error=1 OR diPitch_CAN_Node3Error=1 OR diPitch_CAN_Node4Error=1 OR diPitch_CAN_Node5Error=1 OR diPitch_CAN_Node6Error=1 OR diPitch_CANbusGlobalError=1)",
- "set_delay": "PAR_tSetDelayForCANProfibus",
- "yp": "0",
- "reset_en": "Pitch System CAN Nodes Error are clear.(diPitch_CAN_Node1Error=0 AND diPitch_CAN_Node2Error=0 AND diPitch_CAN_Node3Error=0 AND diPitch_CAN_Node4Error=0 AND diPitch_CAN_Node5Error=0 AND diPitch_CAN_Node6Error=0 AND diPitch_CANbusGlobalError=0)",
- "reset_cn": "变桨系统内部CAN1-6号节点均未发生故障。(diPitch_CAN_Node1Error=0 AND diPitch_CAN_Node2Error=0 AND diPitch_CAN_Node3Error=0 AND diPitch_CAN_Node4Error=0 AND diPitch_CAN_Node5Error=0 AND diPitch_CAN_Node6Error=0 AND diPitch_CANbusGlobalError=0)",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "200"
- },
- "01_05_106": {
- "subsystem": "PitchSystem",
- "name": "SC_Pitch_MotorEncIncoherence",
- "en": "Pitch Motor Encoder Incoherence",
- "cn": "变桨系统报告桨叶间角度相差过大(相差2度持续120毫秒)",
- "powerup_delay": "T#0s",
- "disable_level": "50",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Turbine Operation Mode is after startmode, and Pitch Motor Encoder Incoherence.(diPitchMotorEncoderIncoherence=1 AND giTurbineOperationMode >= CON_iStartMode)",
- "trigger_cn": "Turbine Operation Mode is after startmode, and Pitch Motor Encoder Incoherence.(diPitchMotorEncoderIncoherence=1 AND giTurbineOperationMode >= CON_iStartMode)",
- "set_delay": "PAR_tSetDelayForCANProfibus",
- "yp": "0",
- "reset_en": "Pitch Motor Encoder Incoherence is clear.(diPitchMotorEncoderIncoherence=0 OR giTurbineOperationMode < CON_iStartMode)",
- "reset_cn": "变桨系统电机编码器故障解除。(diPitchMotorEncoderIncoherence=0 OR giTurbineOperationMode < CON_iStartMode)",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "198"
- },
- "01_05_107": {
- "subsystem": "Pitchsystem",
- "name": "OC_PitchMaintenanceMode",
- "en": "Pitch system is in maintenance mode",
- "cn": "变桨系统处于维护模式",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Pitch system is in maintenance mode.(DQ_PitchManualMode=1 OR di_Pitch_MaintenanceMode=1 OR di_Blade1_MaintenanceMode=1 OR di_Blade2_MaintenanceMode=1 OR di_Blade3_MaintenanceMode=1)",
- "trigger_cn": "变桨系统处于任一维护模式。(DQ_PitchManualMode=1 OR di_Pitch_MaintenanceMode=1 OR di_Blade1_MaintenanceMode=1 OR di_Blade2_MaintenanceMode=1 OR di_Blade3_MaintenanceMode=1)",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "Pitch system is out of maintenance mode.(DQ_PitchManualMode=0 AND di_Pitch_MaintenanceMode=0 AND di_Blade1_MaintenanceMode=0 AND di_Blade2_MaintenanceMode=0 AND di_Blade3_MaintenanceMode=0 AND bSpecResCond=1)",
- "reset_cn": "变桨系统脱离维护模式。(di_Blade1_DCLinkVoltageTooLow=0 AND di_Blade2_DCLinkVoltageTooLow=0 AND di_Blade3_DCLinkVoltageTooLow=0 AND bSpecResCond=1)",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "210-维护",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "210",
- "brake_state_design": "0"
- },
- "01_05_109": {
- "subsystem": "PitchSystem",
- "name": "OC_PitchHeatingMode",
- "en": "Pitch system is in heating up",
- "cn": "变桨系统暖机模式",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "gbValidData_Profibus_Pitch_x000D_ AND (grTempBlade1_AxisBox_1min<-20 OR grTempBlade2_AxisBox_1min<-20 OR grTempBlade3_AxisBox_1min<-20) AND NOT SC_PitchHeatingModeTimeout",
- "trigger_cn": "变桨系统通讯正常,三个轴控柜温度均小于-20",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "set condition is not true",
- "reset_cn": "触发条件不满足",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "30-待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "30",
- "brake_state_design": "50"
- },
- "01_05_110": {
- "subsystem": "PitchSystem",
- "name": "SC_PitchHeatingModeTimeout",
- "en": "Pitch system heating mode time out.",
- "cn": "变桨系统暖机超时",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "OC_PitchHeatingMode is TRUE",
- "trigger_cn": "变桨系统暖机模式持续时间过长",
- "set_delay": "T#30m",
- "yp": "0",
- "reset_en": "OC_PitchHeatingMode is false",
- "reset_cn": "退出变桨系统暖机模式",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "03_09_030": {
- "subsystem": "PitchSystem",
- "name": "SC_SELFTEST_PitchAccumulatorStatusError1",
- "en": "Selftest of pitch1 accumulator error",
- "cn": "桨叶1电池自检失败",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "when during Selftest1 the accumulator driven pitch move of blade 1 from 0 to 91 degree exceeds PAR_tSELFTEST_PitchBatteryStatusError(gbSelftest2Battery1TestActivated continue TRUE during PAR_tSELFTEST_PitchBatteryStatusError)",
- "trigger_cn": "",
- "set_delay": "PAR_tSELFTEST_PitchBatteryStatusError",
- "yp": "0",
- "reset_en": "Get reset signal of status code coming from Nacelle, Tower or Remote Command.",
- "reset_cn": "收到reset信号。",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "100"
- },
- "03_09_031": {
- "subsystem": "PitchSystem",
- "name": "SC_SELFTEST_PitchAccumulatorStatusError2",
- "en": "Selftest of pitch2 accumulator error",
- "cn": "桨叶2电池自检失败",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "when during Selftest1 the accumulator driven pitch move of blade 1 from 0 to 91 degree exceeds PAR_tSELFTEST_PitchBatteryStatusError (gbSelftest2Battery1TestActivated continue TRUE during PAR_tSELFTEST_PitchBatteryStatusError)",
- "trigger_cn": "",
- "set_delay": "PAR_tSELFTEST_PitchBatteryStatusError",
- "yp": "0",
- "reset_en": "Get reset signal of status code coming from Nacelle, Tower or Remote Command.",
- "reset_cn": "收到reset信号。",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "100"
- },
- "03_09_032": {
- "subsystem": "PitchSystem",
- "name": "SC_SELFTEST_PitchAccumulatorStatusError3",
- "en": "Selftest of pitch3 accumulator error",
- "cn": "桨叶3电池自检失败",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "when during Selftest1 the accumulator driven pitch move of blade 1 from 0 to 91 degree exceeds PAR_tSELFTEST_PitchBatteryStatusError (gbSelftest2Battery1TestActivated continue TRUE during PAR_tSELFTEST_PitchBatteryStatusError)",
- "trigger_cn": "",
- "set_delay": "PAR_tSELFTEST_PitchBatteryStatusError",
- "yp": "0",
- "reset_en": "Get reset signal of status code coming from Nacelle, Tower or Remote Command.",
- "reset_cn": "收到reset信号。",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "100"
- },
- "03_09_117": {
- "subsystem": "PitchSystem",
- "name": "SC_TimeOutPitch2SelfTest",
- "en": "Pitch 2 selftest is over time",
- "cn": "桨叶2电池自检超时",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Pith2 selftest is over tiem(gbPitch2SelftestStart=true)",
- "trigger_cn": "桨叶2自检超过设定时间",
- "set_delay": "T#50s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "100"
- },
- "03_09_118": {
- "subsystem": "PitchSystem",
- "name": "SC_TimeOutPitch3SelfTest",
- "en": "Pitch 3 selftest is over time",
- "cn": "桨叶3电池自检超时",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Pith3 selftest is over tiem(gbPitch3SelftestStart=true)",
- "trigger_cn": "桨叶3自检超过设定时间",
- "set_delay": "T#50s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "100"
- },
- "03_09_116": {
- "subsystem": "PitchSystem",
- "name": "SC_TimeOutPitch1SelfTest",
- "en": "Pitch 1 selftest is over time",
- "cn": "桨叶1电池自检超时",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Pith1 selftest is over tiem(gbPitch1SelftestStart=true)",
- "trigger_cn": "桨叶1自检超过设定时间",
- "set_delay": "T#50s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "100"
- },
- "04_12_019": {
- "subsystem": "ConverterContainer",
- "name": "OC_ConverterSpeedModeSwitchedOn",
- "en": "",
- "cn": "变频器转速模式开启",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "(gbCVT_T_S_Select == TRUE) OR (geCVT_Switch_P_T_n_Pos_Cmd == e_SetValue_Speed)",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "30",
- "brake_state_design": "51"
- },
- "04_12_020": {
- "subsystem": "ConverterContainer",
- "name": "OC_ConverterServiceSwichedOn",
- "en": "",
- "cn": "变频器Service功能开启",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "RemCmdACK_bCVTServiceSwitchOn =1",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "220",
- "brake_state_design": "100"
- },
- "04_12_021": {
- "subsystem": "ConverterContainer",
- "name": "SC_Converter_MCBCloseTimeout",
- "en": "",
- "cn": "变频器合主断路器超时",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "gbCVT_ON=1 AND NOT gbCVT_DCLinkCharged",
- "set_delay": "PAR_tCVT_MCBCloseTimeout",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_12_022": {
- "subsystem": "ConverterContainer",
- "name": "SC_CVT_LVRT_Timeout",
- "en": "",
- "cn": "变频器LVRT超时",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "gbCVT_LVRT_Active=TURE",
- "set_delay": "PAR_tCVT_LVRT_Timeout",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "100"
- },
- "04_12_023": {
- "subsystem": "ConverterContainer",
- "name": "SC_CVT_IGBT_TempHigh",
- "en": "",
- "cn": "IGBT温度高报警",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "grCVT_INU_IGBT_Max_Temp> PAR_rCVT_IGBT_TempHigh OR grCVT_ISU_IGBT_Max_Temp> PAR_rCVT_IGBT_TempHigh",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_12_024": {
- "subsystem": "ConverterContainer",
- "name": "SC_CVT_IGBT_TempVeryHigh",
- "en": "",
- "cn": "IGBT温度高故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "grCVT_INU_IGBT_Max_Temp> PAR_rCVT_IGBT_TempVeryHighOR grCVT_ISU_IGBT_Max_Temp> PAR_rCVT_IGBT_TempVeryHigh",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_12_025": {
- "subsystem": "ConverterContainer",
- "name": "OC_ConverterHeatingModeOn",
- "en": "The Converter Heating Mode On",
- "cn": "变频器暖机模式",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "gbDI_CVT_HeatingRequired ==1 AND gbCVT_Rdy_REF=0",
- "trigger_cn": "在非并网状态下变频器发送加热需求信号",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "gbDI_TowerConverterHeatingActive and gbCANConverterDisturbed",
- "reset_cn": "gbDI_TowerConverterHeatingActive and gbCANConverterDisturbed",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "30-待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "30",
- "brake_state_design": "100"
- },
- "04_12_026": {
- "subsystem": "ConverterContainer",
- "name": "SC_CVT_MinInterval_TwiceCharge_Waiting",
- "en": "",
- "cn": "变频器两次充电最短时间间隔等待中",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "The fall rise of gbCVT_ON",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "30-待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "30",
- "brake_state_design": "51"
- },
- "04_12_027": {
- "subsystem": "ConverterContainer",
- "name": "SC_FaultInput_CVT_Humidity",
- "en": "",
- "cn": "变频器湿度传感器故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "gbStateAI_CVT_Ambient_Humidity=TRUE",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_11_035": {
- "subsystem": "GCC",
- "name": "SC_Transformer_Temp_Sensor_Fault",
- "en": "Transformer Temperature Sensor Fault",
- "cn": "变压器温度传感器失效",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_11_036": {
- "subsystem": "GCC",
- "name": "SC_Transformer_Temp_High_Alarm",
- "en": "Transformer Temperature High Alarm",
- "cn": "变压器温度过高警告",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_11_037": {
- "subsystem": "GCC",
- "name": "SC_Transformer_Temp_Winding_different",
- "en": "Transformer Windings Temperature different",
- "cn": "变压器不同绕组温差过大",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_11_038": {
- "subsystem": "GCC",
- "name": "SC_Transformer_Temp_No_reading",
- "en": "Transformer Temperature No reading",
- "cn": "变压器温度值无读数",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_11_039": {
- "subsystem": "GCC",
- "name": "SC_Transformer_WaterLeak",
- "en": "Transformer Water Leak",
- "cn": "变压器水泄漏",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_11_040": {
- "subsystem": "GCC",
- "name": "SC_Transformer_Door_Open",
- "en": "Transformer Door Open",
- "cn": "变压器柜门打开",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_11_041": {
- "subsystem": "GCC",
- "name": "SC_Transformer_Cooling_Motor_Not_running",
- "en": "Transformer Cooling Fan Motor Not running",
- "cn": "变压器冷却风扇没有运行",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_11_042": {
- "subsystem": "GCC",
- "name": "SC_FaultPT100_GCC_Temp2",
- "en": "",
- "cn": "变压器环境温度PT100故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_11_043": {
- "subsystem": "GCC",
- "name": "SC_UPS_Bypass",
- "en": "UPS Bypass",
- "cn": "UPS被旁路",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_13_006": {
- "subsystem": "Cabinet",
- "name": "SC_TowerToNacelle690PowerSupplyOff",
- "en": "",
- "cn": "塔底到机舱690V供电MCB跳开",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "NOT gbDI_690PowerSupplyTowerBaseMCB",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_13_007": {
- "subsystem": "Cabinet",
- "name": "SC_TowerToNacelle400PowerSupplyOff",
- "en": "",
- "cn": "塔底到机舱400V供电MCB跳开",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "NOT gbDI_400PowerSupplyTowerBaseMCB",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_13_008": {
- "subsystem": "Cabinet",
- "name": "SC_AUXTransformer690PowerSupplyOff",
- "en": "",
- "cn": "控制柜与变压器间690V MCB跳开",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "NOT gbDI_AUXTransformer690PowerSupply",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_13_009": {
- "subsystem": "Cabinet",
- "name": "SC_AUXTransformer400PowerSupplyOff",
- "en": "",
- "cn": "控制柜与变压器间400V MCB跳开",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "NOT gbDI_AUXTransformer400PowerSupply",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_02_140": {
- "subsystem": "PitchSystem",
- "name": "SC_Blade1PositionCheckFault",
- "en": "Blade1 position check alarm",
- "cn": "1号桨叶角度检查偏差过大故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "(grPitchAngleBlade1在 grBlade1ZeroPositionTriggerOn_Ref - PAR_rBladeZeroPositionInsideOffsetAlarm 和 grBlade1ZeroPositionTriggerOff_Ref + PAR_rBladeZeroPositionInsideOffsetAlarm 之间时di_Blade1_ZeroPos为0)或者 (grPitchAngleBlade1在 grBlade1ZeroPositionTriggerOn_Ref + PAR_rBladeZeroPositionOutsideOffsetAlarm 和 grBlade1ZeroPositionTriggerOff_Ref - PAR_rBladeZeroPositionOutsideOffsetAlarm 之外时di_Blade1_ZeroPos为1)",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "I",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_02_141": {
- "subsystem": "PitchSystem",
- "name": "SC_Blade2PositionCheckFault",
- "en": "Blade2 position check alarm",
- "cn": "2号桨叶角度检查偏差过大故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "(grPitchAngleBlade2在 grBlade2ZeroPositionTriggerOn_Ref - PAR_rBladeZeroPositionInsideOffsetAlarm 和 grBlade2ZeroPositionTriggerOff_Ref + PAR_rBladeZeroPositionInsideOffsetAlarm 之间时di_Blade2_ZeroPos为0)或者 (grPitchAngleBlade2在 grBlade2ZeroPositionTriggerOn_Ref + PAR_rBladeZeroPositionOutsideOffsetAlarm 和 grBlade2ZeroPositionTriggerOff_Ref - PAR_rBladeZeroPositionOutsideOffsetAlarm 之外时di_Blade2_ZeroPos为1)",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "I",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_02_142": {
- "subsystem": "PitchSystem",
- "name": "SC_Blade3PositionCheckFault",
- "en": "Blade3 position check alarm",
- "cn": "3号桨叶角度检查偏差过大故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "(grPitchAngleBlade3在 grBlade3ZeroPositionTriggerOn_Ref - PAR_rBladeZeroPositionInsideOffsetAlarm 和 grBlade3ZeroPositionTriggerOff_Ref + PAR_rBladeZeroPositionInsideOffsetAlarm 之间时di_Blade3_ZeroPos为0)或者 (grPitchAngleBlade3在 grBlade3ZeroPositionTriggerOn_Ref + PAR_rBladeZeroPositionOutsideOffsetAlarm 和 grBlade3ZeroPositionTriggerOff_Ref - PAR_rBladeZeroPositionOutsideOffsetAlarm 之外时di_Blade3_ZeroPos为1)",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "I",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_16_011": {
- "subsystem": "TurbineStateMachine",
- "name": "SC_Selftest5_OK",
- "en": "Self Test5 Ok",
- "cn": "自检5完成结果正常",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "监测到giTowerResonanceCode变为1",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_16_012": {
- "subsystem": "TurbineStateMachine",
- "name": "SC_Selftest5_Warning",
- "en": "Self Test5 Warning",
- "cn": "自检5完成结果报警",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "监测到giTowerResonanceCode变为2",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "A",
- "alarm": "True",
- "level": "",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_16_013": {
- "subsystem": "TurbineStateMachine",
- "name": "SC_TowerFrequency_OK",
- "en": "The test result of tower frequency is ok",
- "cn": "塔筒频率连续监测结果正常",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "监测到giTowerResonanceCode变为3",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_16_014": {
- "subsystem": "TurbineStateMachine",
- "name": "SC_TowerFrequencyTest_Warning",
- "en": "The test result of tower frequency is warning",
- "cn": "塔筒频率连续监测结果报警",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "监测到giTowerResonanceCode变为4",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "A",
- "alarm": "True",
- "level": "",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_16_015": {
- "subsystem": "TurbineStateMachine",
- "name": "SC_Selftest5_Timeout",
- "en": "Self Test5 Timeout",
- "cn": "自检5运行超时",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "PAR_tTimeoutSelftest5",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_09_037": {
- "subsystem": "NacelleSystem",
- "name": "SC_PCHFault",
- "en": "",
- "cn": "PCH出现异常",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#10s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "A",
- "alarm": "True",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_09_038": {
- "subsystem": "NacelleSystem",
- "name": "OC_SwitchPCHToGJSensor",
- "en": "",
- "cn": "振动检测由PCH切换到G&J传感器",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_09_039": {
- "subsystem": "NacelleSystem",
- "name": "SC_GJSensorFault",
- "en": "",
- "cn": "G&J传感器出现异常",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#10s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "A",
- "alarm": "True",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_09_040": {
- "subsystem": "NacelleSystem",
- "name": "SC_BothVibrationSensorFault",
- "en": "",
- "cn": "PCH与G&J传感器同时出现异常",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#30s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_09_041": {
- "subsystem": "NacelleSystem",
- "name": "SC_VibrationOmniDirectionLevel1_GJ",
- "en": "",
- "cn": "G&J检测到塔架水平方向的加速度高于1级振动门限值",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "3",
- "repeat_period": "T#1h",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#2s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "51"
- },
- "04_09_042": {
- "subsystem": "NacelleSystem",
- "name": "SC_VibrationOmniDirectionLevel2_GJ",
- "en": "",
- "cn": "G&J检测到塔架水平方向的加速度高于2级振动门限值",
- "powerup_delay": "T#0s",
- "disable_level": "51",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#2s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "100"
- },
- "04_09_043": {
- "subsystem": "NacelleSystem",
- "name": "SC_RepFaultVibrationXAxis_GJ",
- "en": "",
- "cn": "阵风过大保护性停机",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "A",
- "alarm": "True",
- "level": "139-大风停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "139",
- "brake_state_design": "51"
- },
- "04_09_044": {
- "subsystem": "NacelleSystem",
- "name": "SC_VibrationForeaftDirection1_GJ",
- "en": "",
- "cn": "G&J检测到塔架前后方向的加速度高于1级振动门限值",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "3",
- "repeat_period": "T#1h",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#2s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "30-待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "30",
- "brake_state_design": "0"
- },
- "04_09_045": {
- "subsystem": "NacelleSystem",
- "name": "SC_VibrationForeaftDirection2_GJ",
- "en": "",
- "cn": "G&J检测到塔架前后方向的加速度高于2级振动门限值",
- "powerup_delay": "T#0s",
- "disable_level": "50",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#2s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "100"
- },
- "04_09_046": {
- "subsystem": "NacelleSystem",
- "name": "SC_RepFaultVibrationYAxis_GJ",
- "en": "",
- "cn": "阵风过大保护性停机",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "A",
- "alarm": "True",
- "level": "139-大风停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "139",
- "brake_state_design": "51"
- },
- "04_09_047": {
- "subsystem": "NacelleSystem",
- "name": "OC_VibrationOmniDirection_GJ",
- "en": "",
- "cn": "塔架水平方向的加速度超限",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "30-待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "30",
- "brake_state_design": "0"
- },
- "04_09_048": {
- "subsystem": "NacelleSystem",
- "name": "OC_VibrationForeaftDirection_GJ",
- "en": "",
- "cn": "塔架前后方向的加速度超限",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "30-待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "30",
- "brake_state_design": "0"
- },
- "04_09_049": {
- "subsystem": "NacelleSystem",
- "name": "SC_BlockYawForVibrationHigh_GJ",
- "en": "",
- "cn": "G&J传感器检测到前后方向振动值过大禁止偏航一分钟",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "前后方向振动值过大禁止偏航一分钟",
- "set_delay": "T#0s",
- "yp": "100",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "10-其他",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_01_016": {
- "subsystem": "SafetySystem",
- "name": "SC_SafetyChain_SSDSwitch_GJ",
- "en": "Safetychain is open due to SSD switch open",
- "cn": "G&J传感器测得的SSD震动值高于设定值",
- "powerup_delay": "T#15s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "SSD开关断开导致安全链断开。(gbdi_SafetyChainNacelleSSDSwitch=1 AND gbdqCANPCH_SSDTest=0 AND bBlockMonitoring1=0 AND bBlockMonitoring2=0)_x000D_ gbdqCANPCH_SSDTest(主控命令PCH进行SSD自检)从True变为false,触发15秒的bBlockMonitoring1为True_x000D_ gbMAIN_ResetStatusCodes(复位状态字命令)从False变为True,触发15秒的bBlockMonitoring2为True_x000D_",
- "set_delay": "T#0s",
- "yp": "100",
- "reset_en": "Safetychain is closed. (gbdi_SafetyChainNacelleSSDSwitch=0 OR gbdqCANPCH_SSDTest=1 OR bBlockMonitoring1=1 OR bBlockMonitoring2=1) bBlockMonitoring1 will last for 15 seconds when gbdqCANPCH_SSDTest drop from 1 to 0._x000D_ bBlockMonitoring2 will last for 15 seconds when gbMAIN_ResetStatusCodes rises from 0 to 1.",
- "reset_cn": "SSD开关闭合导致安全链闭合。(gbdi_SafetyChainNacelleSSDSwitch=0 OR gbdqCANPCH_SSDTest=1 OR bBlockMonitoring1=1 OR bBlockMonitoring2=1)_x000D_ gbdqCANPCH_SSDTest(主控命令PCH进行SSD自检)从True变为false,触发15秒的bBlockMonitoring1为True_x000D_ gbMAIN_ResetStatusCodes(复位状态字命令)从False变为True,触发15秒的bBlockMonitoring2为True",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "200"
- },
- "04_01_017": {
- "subsystem": "SafetySystem",
- "name": "SC_SafetyChain_SSDMax_GJ",
- "en": "SSD Triggered",
- "cn": "G&J的SSD开关断开导致安全链断开",
- "powerup_delay": "T#30s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "When the signal for SSD switch is less than PAR_rSSDMax.(grSSDValue_PCH_100ms <= PAR_rSSDMax OR gbdqCANPCH_SSDTest=1 OR bBlockMonitoring1=1)_x000D_ bBlockMonitoring1 will last for 15 seconds when gbdqCANPCH_SSDTest drop from 1 to 0.",
- "reset_cn": "以下4点满足一点即可:1.当SSD 100ms平均值小于等于允许的最大值(由参数给出)2.主控发出PCH进行SSD自检的命令3.满足bBlockMonitor1条件4.风机处于自检4。(grSSDValue_PCH_100ms <= PAR_rSSDMax OR gbdqCANPCH_SSDTest=1 OR bBlockMonitoring1=1)OR(giTurbineOperationMode = CON_iSelfTest4)",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "100"
- },
- "04_01_018": {
- "subsystem": "SafetySystem",
- "name": "SC_SafetyChain_VibrationSwitch_GJ",
- "en": "Safetychain is open due to tower vibration switch",
- "cn": "G&J的振动过大继电器断开导致安全链断开",
- "powerup_delay": "T#15s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "Safetychain is open due to tower vibration switch.(gbdqCANPCH_SSDTest=0 AND bBlockMonitoring1=O AND bBlockMonitoring2=0 AND gbdi_SafetyChainNacelleVibrationSwitch=1)",
- "trigger_cn": "塔架振动过大导致安全链断开。(gbdqCANPCH_SSDTest=0 AND bBlockMonitoring1=O AND bBlockMonitoring2=0 AND gbdi_SafetyChainNacelleVibrationSwitch=1)",
- "set_delay": "T#0s",
- "yp": "100",
- "reset_en": "Safetychain is reclosed.((gbdqCANPCH_SSDTest=1 OR bBlockMonitoring1=1 OR bBlockMonitoring2=1) OR gbdi_SafetyChainNacelleVibrationSwitch=0)AND bSpecResCond=1",
- "reset_cn": "安全链重连。((gbdqCANPCH_SSDTest=1 OR bBlockMonitoring1=1 OR bBlockMonitoring2=1) OR gbdi_SafetyChainNacelleVibrationSwitch=0)AND bSpecResCond=1",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "200"
- },
- "04_01_019": {
- "subsystem": "SafetySystem",
- "name": "SC_VibrationRelayActive_GJ",
- "en": "",
- "cn": "G&J振动过大继电器触发",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "100",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "200"
- },
- "04_04_015": {
- "subsystem": "Drivetrain",
- "name": "SC_MainShaftCrack",
- "en": "Main Shaft Crack",
- "cn": "主轴两端转速差过大判断主轴断裂",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#1m",
- "yp": "100",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "200"
- },
- "04_08_028": {
- "subsystem": "CoolingSystem",
- "name": "SC_TCS_Pump1_Overload",
- "en": "",
- "cn": "塔底水冷泵1过载",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "",
- "src": "plc_dict_2014",
- "brake_state_design": "0"
- },
- "04_08_029": {
- "subsystem": "CoolingSystem",
- "name": "SC_TCS_Pump2_Overload",
- "en": "",
- "cn": "塔底水冷泵2过载",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "",
- "src": "plc_dict_2014",
- "brake_state_design": "0"
- },
- "04_08_030": {
- "subsystem": "CoolingSystem",
- "name": "SC_TCS_Pumps_Overload",
- "en": "",
- "cn": "塔底水冷泵全部过载",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "",
- "src": "plc_dict_2014",
- "brake_state_design": "0"
- },
- "04_08_031": {
- "subsystem": "CoolingSystem",
- "name": "SC_TCS_Pump1_MCB",
- "en": "",
- "cn": "塔底水冷泵1MCB跳开",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_08_032": {
- "subsystem": "CoolingSystem",
- "name": "SC_TCS_Pump2_MCB",
- "en": "",
- "cn": "塔底水冷泵2MCB跳开",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_08_033": {
- "subsystem": "CoolingSystem",
- "name": "SC_TCS_Pumps_MCB",
- "en": "",
- "cn": "塔底水冷泵MCB全部跳开",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "100"
- },
- "04_08_034": {
- "subsystem": "CoolingSystem",
- "name": "SC_TCSPump1Failure_NoPressure",
- "en": "",
- "cn": "塔底水冷泵1无压力故障",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#10s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "100"
- },
- "04_08_035": {
- "subsystem": "CoolingSystem",
- "name": "SC_TCSPump2Failure_NoPressure",
- "en": "",
- "cn": "塔底水冷泵2无压力故障",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#10s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "100"
- },
- "04_08_036": {
- "subsystem": "CoolingSystem",
- "name": "SC_TCS_Heater_Overload",
- "en": "",
- "cn": "塔底水冷加热器过载",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "",
- "src": "plc_dict_2014",
- "brake_state_design": "51"
- },
- "04_08_037": {
- "subsystem": "CoolingSystem",
- "name": "SC_TCS_Heater_MCB",
- "en": "",
- "cn": "塔底水冷加热器MCB跳开",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_08_038": {
- "subsystem": "CoolingSystem",
- "name": "SC_TCS_InletWaterTempLow_Warning",
- "en": "",
- "cn": "塔底水冷进水口水温过低警告",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "100"
- },
- "04_08_039": {
- "subsystem": "CoolingSystem",
- "name": "SC_TCS_InletWaterPT100Fault",
- "en": "",
- "cn": "塔底水冷进水口PT100故障",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_08_040": {
- "subsystem": "CoolingSystem",
- "name": "SC_TCS_InsideFan1_Overload",
- "en": "",
- "cn": "塔底水冷塔内风扇1过载",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "",
- "src": "plc_dict_2014",
- "brake_state_design": "0"
- },
- "04_08_041": {
- "subsystem": "CoolingSystem",
- "name": "SC_TCS_InsideFan2_Overload",
- "en": "",
- "cn": "塔底水冷塔内风扇2过载",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "",
- "src": "plc_dict_2014",
- "brake_state_design": "0"
- },
- "04_08_042": {
- "subsystem": "CoolingSystem",
- "name": "SC_TCS_InsideFan1_MCB",
- "en": "",
- "cn": "塔底水冷塔内风扇1MCB跳开",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_08_043": {
- "subsystem": "CoolingSystem",
- "name": "SC_TCS_InsideFan2_MCB",
- "en": "",
- "cn": "塔底水冷塔内风扇2MCB跳开",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_08_044": {
- "subsystem": "CoolingSystem",
- "name": "SC_TCS_TowerTempHigh",
- "en": "",
- "cn": "塔内温度高警告",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_08_045": {
- "subsystem": "CoolingSystem",
- "name": "SC_TCS_TowerTempTooHigh",
- "en": "",
- "cn": "塔内温度过高停机",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "100"
- },
- "04_08_046": {
- "subsystem": "CoolingSystem",
- "name": "SC_TCS_Cooler1FanA_Overload",
- "en": "",
- "cn": "塔底冷却器1风扇A过载",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_08_047": {
- "subsystem": "CoolingSystem",
- "name": "SC_TCS_Cooler1FanB_Overload",
- "en": "",
- "cn": "塔底冷却器1风扇B过载",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_08_048": {
- "subsystem": "CoolingSystem",
- "name": "SC_TCS_Cooler2FanA_Overload",
- "en": "",
- "cn": "塔底冷却器2风扇A过载",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_08_049": {
- "subsystem": "CoolingSystem",
- "name": "SC_TCS_Cooler2FanB_Overload",
- "en": "",
- "cn": "塔底冷却器2风扇B过载",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_08_050": {
- "subsystem": "CoolingSystem",
- "name": "SC_TCS_Cooler3FanA_Overload",
- "en": "",
- "cn": "塔底冷却器3风扇A过载",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_08_051": {
- "subsystem": "CoolingSystem",
- "name": "SC_TCS_Cooler3FanB_Overload",
- "en": "",
- "cn": "塔底冷却器3风扇B过载",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_08_052": {
- "subsystem": "CoolingSystem",
- "name": "SC_TCS_Cooler4FanA_Overload",
- "en": "",
- "cn": "塔底冷却器4风扇A过载",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_08_053": {
- "subsystem": "CoolingSystem",
- "name": "SC_TCS_Cooler4FanB_Overload",
- "en": "",
- "cn": "塔底冷却器4风扇B过载",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_08_054": {
- "subsystem": "CoolingSystem",
- "name": "SC_TCS_Cooler1Fans_MCB",
- "en": "",
- "cn": "塔底冷却器1风扇 MCB跳开",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_08_055": {
- "subsystem": "CoolingSystem",
- "name": "SC_TCS_Cooler2Fans_MCB",
- "en": "",
- "cn": "塔底冷却器2风扇 MCB跳开",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_08_056": {
- "subsystem": "CoolingSystem",
- "name": "SC_TCS_Cooler3Fans_MCB",
- "en": "",
- "cn": "塔底冷却器3风扇 MCB跳开",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_08_057": {
- "subsystem": "CoolingSystem",
- "name": "SC_TCS_Cooler4Fans_MCB",
- "en": "",
- "cn": "塔底冷却器4风扇 MCB跳开",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_08_058": {
- "subsystem": "CoolingSystem",
- "name": "SC_TCSWaterPressureTooLow",
- "en": "",
- "cn": "塔底水冷水压力过低故障",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "100"
- },
- "04_08_059": {
- "subsystem": "CoolingSystem",
- "name": "OC_TCS_Pump1_ON",
- "en": "",
- "cn": "塔底水冷泵1启动",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_08_060": {
- "subsystem": "CoolingSystem",
- "name": "OC_TCS_Pump2_ON",
- "en": "",
- "cn": "塔底水冷泵2启动",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_08_061": {
- "subsystem": "CoolingSystem",
- "name": "OC_TCS_Heater_ON",
- "en": "",
- "cn": "塔底水冷加热器启动",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_08_062": {
- "subsystem": "CoolingSystem",
- "name": "SC_TCS_CVTOutletPT100Fault",
- "en": "",
- "cn": "塔底水冷变频器出口PT100故障",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_08_063": {
- "subsystem": "CoolingSystem",
- "name": "SC_TCS_TrafoOutletPT100Fault",
- "en": "",
- "cn": "塔底水冷变压器出口PT100故障",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_08_064": {
- "subsystem": "CoolingSystem",
- "name": "SC_TCS_OutletPT100Fault",
- "en": "",
- "cn": "塔底水冷被冷却器出口PT100故障",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_08_065": {
- "subsystem": "CoolingSystem",
- "name": "SC_TCS_InsideCoolerInletPT100Fault",
- "en": "",
- "cn": "塔底水冷塔内冷却器入口PT100故障",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_08_066": {
- "subsystem": "CoolingSystem",
- "name": "SC_TCS_PumpManualMode",
- "en": "",
- "cn": "塔底水冷泵开启手动模式",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#50ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_08_067": {
- "subsystem": "CoolingSystem",
- "name": "SC_TCS_PumpForceMode",
- "en": "",
- "cn": "塔底水冷泵开启强制模式",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#50ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_08_068": {
- "subsystem": "CoolingSystem",
- "name": "SC_TCS_FanManualMode",
- "en": "",
- "cn": "塔底水冷系统中有风扇开启了手动模式",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#50ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_08_069": {
- "subsystem": "CoolingSystem",
- "name": "SC_TCS_FanForceMode",
- "en": "",
- "cn": "塔底水冷系统中有风扇开启了强制模式",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#50ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_08_070": {
- "subsystem": "CoolingSystem",
- "name": "SC_TCS_HeaterManualMode",
- "en": "",
- "cn": "塔底水冷加热器开启手动模式",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#50ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_08_071": {
- "subsystem": "CoolingSystem",
- "name": "SC_TCS_HeaterForceMode",
- "en": "",
- "cn": "塔底水冷加热器开启强制模式",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#50ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_08_072": {
- "subsystem": "CoolingSystem",
- "name": "SC_TCS_MixingValveManualMode",
- "en": "",
- "cn": "塔底水冷三通阀开启手动模式",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#50ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_08_073": {
- "subsystem": "CoolingSystem",
- "name": "SC_TCS_MixingValveForceMode",
- "en": "",
- "cn": "塔底水冷加热器开启强制模式",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#50ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_08_074": {
- "subsystem": "CoolingSystem",
- "name": "SC_TCS_PumpInletPreSensorFault",
- "en": "",
- "cn": "塔底水冷泵吸入侧压力传感器故障",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "0"
- },
- "04_08_075": {
- "subsystem": "CoolingSystem",
- "name": "SC_TCS_PumpOutletPreSensorFault",
- "en": "",
- "cn": "塔底水冷泵压力侧压力传感器故障",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "0"
- },
- "04_08_076": {
- "subsystem": "CoolingSystem",
- "name": "SC_TCS_PumpOffAbnormally",
- "en": "",
- "cn": "塔底水冷泵需启动但未启动",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#100ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "100"
- },
- "04_11_044": {
- "subsystem": "GCC",
- "name": "SC_FaultPT100_GCC_Temp3",
- "en": "",
- "cn": "变压器底部温度传感器1故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_11_045": {
- "subsystem": "GCC",
- "name": "SC_FaultPT100_GCC_Temp4",
- "en": "",
- "cn": "变压器底部温度传感器2故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_08_077": {
- "subsystem": "CoolingSystem",
- "name": "SC_FaultOutsideTowerHumidity",
- "en": "",
- "cn": "塔筒外湿度传感器故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_08_078": {
- "subsystem": "CoolingSystem",
- "name": "SC_FaultCabinetFloorHumidity",
- "en": "",
- "cn": "塔底控制柜底部湿度传感器故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_08_079": {
- "subsystem": "CoolingSystem",
- "name": "SC_FaultMixingValvePosition",
- "en": "",
- "cn": "塔底水冷系统三通阀位置传感器故障",
- "powerup_delay": "T#0s",
- "disable_level": "100",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#10ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "100"
- },
- "04_08_080": {
- "subsystem": "CoolingSystem",
- "name": "SC_CCC_Temp_MAX",
- "en": "",
- "cn": "塔底水冷控制柜温度高故障",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_08_081": {
- "subsystem": "CoolingSystem",
- "name": "SC_CCC_Temp_MIN",
- "en": "",
- "cn": "塔底水冷控制柜温度低故障",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_08_082": {
- "subsystem": "CoolingSystem",
- "name": "SC_CCC_Temp_High",
- "en": "",
- "cn": "塔底水冷控制柜温度高警告",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_08_083": {
- "subsystem": "CoolingSystem",
- "name": "SC_CCC_Temp_Low",
- "en": "",
- "cn": "塔底水冷控制柜温度低警告",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_08_084": {
- "subsystem": "CoolingSystem",
- "name": "SC_CCC_690VSupplyTripped",
- "en": "",
- "cn": "塔底水冷系统690V供电跳开",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_08_085": {
- "subsystem": "CoolingSystem",
- "name": "SC_CCC_NoUPS230VSupplyTripped",
- "en": "",
- "cn": "塔底水冷系统230V(无UPS)供电跳开",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#1s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "M",
- "type": "F",
- "alarm": "True",
- "level": "170-故障停机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_08_086": {
- "subsystem": "CoolingSystem",
- "name": "SC_CCC_HeaterOrCoolerPowerTripped",
- "en": "",
- "cn": "塔底水冷控制柜加热器或冷却器供电跳开",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "A",
- "alarm": "False",
- "level": "40-警告待机",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "40",
- "brake_state_design": "0"
- },
- "04_08_087": {
- "subsystem": "CoolingSystem",
- "name": "SC_CCC_FaultPT100Temp",
- "en": "",
- "cn": "塔底水冷控制柜PT100故障",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#0s",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "F",
- "alarm": "True",
- "level": "",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "170",
- "brake_state_design": "51"
- },
- "04_08_088": {
- "subsystem": "CoolingSystem",
- "name": "SC_CCC_HeaterManualMode",
- "en": "",
- "cn": "塔底水冷控制柜加热器进入手动模式",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#50ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_08_089": {
- "subsystem": "CoolingSystem",
- "name": "SC_CCC_HeaterForceMode",
- "en": "",
- "cn": "塔底水冷控制柜加热器进入强制模式",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#50ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_08_090": {
- "subsystem": "CoolingSystem",
- "name": "SC_CCC_CoolerManualMode",
- "en": "",
- "cn": "塔底水冷控制柜风扇进入手动模式",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#50ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "04_08_091": {
- "subsystem": "CoolingSystem",
- "name": "SC_CCC_CoolerForceMode",
- "en": "",
- "cn": "塔底水冷控制柜风扇进入强制模式",
- "powerup_delay": "T#0s",
- "disable_level": "20",
- "repeat_n": "0",
- "repeat_period": "T#0s",
- "trigger_en": "",
- "trigger_cn": "",
- "set_delay": "T#50ms",
- "yp": "0",
- "reset_en": "",
- "reset_cn": "",
- "reset_mode": "A",
- "type": "I",
- "alarm": "False",
- "level": "",
- "src": "plc_dict_2014",
- "bp_runtime_2015": "10",
- "brake_state_design": "0"
- },
- "02_01_009": {
- "en": "Main contactor for pitch system 400V supply is NOT closed",
- "cn": "变桨系统的400V主接触器未闭合",
- "subsystem_label": "安全链/柜/机舱",
- "src": "scada_lang_2015",
- "brake_state_design": "40"
- },
- "02_04_033": {
- "en": "Tower acceleration value of Z axis exceeds the limit",
- "cn": "塔架Z方向的瞬时加速度越限",
- "subsystem_label": "转速/塔/发电机",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "02_04_036": {
- "en": "Tower acceleration value of Z axis exceeds the warning value",
- "cn": "塔架Z方向的瞬时加速度告警",
- "subsystem_label": "转速/塔/发电机",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "02_08_010": {
- "en": "Generator Power Caculated is too high",
- "cn": "变频器测得发电机功率高于过高设定值",
- "subsystem_label": "发电机/温度/水冷",
- "src": "scada_lang_2015",
- "brake_state_design": "170"
- },
- "02_09_034": {
- "en": "Rotor brake is applied, turbine should not start-up",
- "cn": "高速液压刹车未释放",
- "subsystem_label": "液压/压力/刹车",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "03_01_011": {
- "en": "Fault auto recovery process",
- "cn": "风机保护性停机——自恢复执行中",
- "subsystem_label": "安全链/塔/柜",
- "src": "scada_lang_2015",
- "brake_state_design": "185"
- },
- "04_01_020": {
- "en": "Safetychain is open by CVT emergency stop.",
- "cn": "变频器急停按钮被拍下触发紧急停机",
- "subsystem_label": "安全链/振动/转速",
- "src": "scada_lang_2015",
- "brake_state_design": "170"
- },
- "04_01_021": {
- "en": "Nacelle 24V fuse is abnormal.",
- "cn": "机舱柜安全链回路24V保护空开跳开",
- "subsystem_label": "安全链/振动/转速",
- "src": "scada_lang_2015",
- "brake_state_design": "170"
- },
- "04_01_022": {
- "en": "",
- "cn": "偏航黄盒子终极限位触发",
- "subsystem_label": "安全链/振动/转速",
- "src": "scada_lang_2015",
- "brake_state_design": "170"
- },
- "04_01_023": {
- "en": "",
- "cn": "安全控制器测得低速端编码器故障",
- "subsystem_label": "安全链/振动/转速",
- "src": "scada_lang_2015",
- "brake_state_design": "175"
- },
- "04_01_024": {
- "en": "",
- "cn": "安全控制器测得高速端接近开关故障",
- "subsystem_label": "安全链/振动/转速",
- "src": "scada_lang_2015",
- "brake_state_design": "175"
- },
- "04_02_143": {
- "en": "Pitch super capacitors charging.",
- "cn": "变桨超级电容正在充电",
- "subsystem_label": "温度/柜/变桨",
- "src": "scada_lang_2015",
- "brake_state_design": "30"
- },
- "04_02_144": {
- "en": "Repeated out of times of SC_PitchCommunicationError",
- "cn": "变桨系统通信中断频繁触发",
- "subsystem_label": "温度/柜/变桨",
- "src": "scada_lang_2015",
- "brake_state_design": "170"
- },
- "04_02_145": {
- "en": "Auto reset pitch communication failed",
- "cn": "自复位变桨通信故障失败",
- "subsystem_label": "温度/柜/变桨",
- "src": "scada_lang_2015",
- "brake_state_design": "170"
- },
- "04_02_146": {
- "en": "Auto reset El6751",
- "cn": "复位EL6751操作中",
- "subsystem_label": "温度/柜/变桨",
- "src": "scada_lang_2015",
- "brake_state_design": "230"
- },
- "04_02_147": {
- "en": "Repeated out of times of SC_CommunicationErrorTCU",
- "cn": "变桨系统与主控的通讯故障频繁触发",
- "subsystem_label": "温度/柜/变桨",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_02_148": {
- "en": "Auto reset SC_CommunicationErrorTCU failed",
- "cn": "变桨系统与主控的通讯故障自动复位失败",
- "subsystem_label": "温度/柜/变桨",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_02_149": {
- "en": "Repeated out of times of Overtemperature axis box 1",
- "cn": "1号轴控柜温度过高故障频繁触发",
- "subsystem_label": "温度/柜/变桨",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_02_150": {
- "en": "Auto reset Overtemperature axis box 1 failed",
- "cn": "1号轴控柜温度过高故障自动复位失败",
- "subsystem_label": "温度/柜/变桨",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_02_151": {
- "en": "Repeated out of times of Overtemperature axis box 2",
- "cn": "2号轴控柜温度过高故障频繁触发",
- "subsystem_label": "温度/柜/变桨",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_02_152": {
- "en": "Auto reset Overtemperature axis box 2 failed",
- "cn": "2号轴控柜温度过高故障自动复位失败",
- "subsystem_label": "温度/柜/变桨",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_02_153": {
- "en": "Repeated out of times of Overtemperature axis box 3",
- "cn": "3号轴控柜温度过高故障频繁触发",
- "subsystem_label": "温度/柜/变桨",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_02_154": {
- "en": "Auto reset Overtemperature axis box 3 failed",
- "cn": "3号轴控柜温度过高故障自动复位失败",
- "subsystem_label": "温度/柜/变桨",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_02_155": {
- "en": "Repeated out of times of Overtemperature motor axis 1",
- "cn": "1号变桨电机温度过高故障频繁触发",
- "subsystem_label": "温度/柜/变桨",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_02_156": {
- "en": "Auto reset Overtemperature motor axis 1 failed",
- "cn": "1号变桨电机温度过高故障自动复位失败",
- "subsystem_label": "温度/柜/变桨",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_02_157": {
- "en": "Repeated out of times of Overtemperature motor axis 2",
- "cn": "2号变桨电机温度过高故障频繁触发",
- "subsystem_label": "温度/柜/变桨",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_02_158": {
- "en": "Auto reset Overtemperature motor axis 2 failed",
- "cn": "2号变桨电机温度过高故障自动复位失败",
- "subsystem_label": "温度/柜/变桨",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_02_159": {
- "en": "Repeated out of times of Overtemperature motor axis 3",
- "cn": "3号变桨电机温度过高故障频繁触发",
- "subsystem_label": "温度/柜/变桨",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_02_160": {
- "en": "Auto reset Overtemperature motor axis 3 failed",
- "cn": "3号变桨电机温度过高故障自动复位失败",
- "subsystem_label": "温度/柜/变桨",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_02_161": {
- "en": "Repeated out of times of Overtemperature backup box 1",
- "cn": "1号后备电源柜温度过高故障频繁触发",
- "subsystem_label": "温度/柜/变桨",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_02_162": {
- "en": "Auto reset Overtemperature backup box 1 failed",
- "cn": "1号后备电源柜温度过高故障自动复位失败",
- "subsystem_label": "温度/柜/变桨",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_02_163": {
- "en": "Repeated out of times of Overtemperature backup box 2",
- "cn": "2号后备电源柜温度过高故障频繁触发",
- "subsystem_label": "温度/柜/变桨",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_02_164": {
- "en": "Auto reset Overtemperature backup box 2 failed",
- "cn": "2号后备电源柜温度过高故障自动复位失败",
- "subsystem_label": "温度/柜/变桨",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_02_165": {
- "en": "Repeated out of times of Overtemperature backup box 3",
- "cn": "3号后备电源柜温度过高故障频繁触发",
- "subsystem_label": "温度/柜/变桨",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_02_166": {
- "en": "Auto reset Overtemperature backup box 3 failed",
- "cn": "3号后备电源柜温度过高故障自动复位失败",
- "subsystem_label": "温度/柜/变桨",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_02_167": {
- "en": "Repeated out of times of Overtemperature center box",
- "cn": "中心柜温度过高故障频繁触发",
- "subsystem_label": "温度/柜/变桨",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_02_168": {
- "en": "Auto reset Overtemperature center box failed",
- "cn": "中心柜温度过高故障自动复位失败",
- "subsystem_label": "温度/柜/变桨",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_04_016": {
- "en": "The RMS of high speed via IIR fiter reaches warning level",
- "cn": "高速端转速IIR滤波后RMS值报警",
- "subsystem_label": "转速/主轴/润滑",
- "src": "scada_lang_2015",
- "brake_state_design": "170"
- },
- "04_04_017": {
- "en": "The RMS of high speed via IIR fiter reaches alarm level",
- "cn": "高速端转速IIR滤波后RMS值停机",
- "subsystem_label": "转速/主轴/润滑",
- "src": "scada_lang_2015",
- "brake_state_design": "170"
- },
- "04_04_018": {
- "en": "The RMS of high speed via IIR fiter reaches warning level repeatly",
- "cn": "高速端转速IIR滤波后RMS值报警重复出现",
- "subsystem_label": "转速/主轴/润滑",
- "src": "scada_lang_2015",
- "brake_state_design": "170"
- },
- "04_04_019": {
- "en": "The RMS of low speed via IIR fiter reaches warning level",
- "cn": "低速端转速IIR滤波后RMS值报警",
- "subsystem_label": "转速/主轴/润滑",
- "src": "scada_lang_2015",
- "brake_state_design": "170"
- },
- "04_04_020": {
- "en": "The RMS of low speed via IIR fiter reaches alarm level",
- "cn": "低速端转速IIR滤波后RMS值停机",
- "subsystem_label": "转速/主轴/润滑",
- "src": "scada_lang_2015",
- "brake_state_design": "170"
- },
- "04_04_021": {
- "en": "The RMS of low speed via IIR fiter reaches warning level repeatly",
- "cn": "低速端转速IIR滤波后RMS值报警重复出现",
- "subsystem_label": "转速/主轴/润滑",
- "src": "scada_lang_2015",
- "brake_state_design": "170"
- },
- "04_04_022": {
- "en": "The test result of drive train frequency is ok",
- "cn": "传动链频率检测正常",
- "subsystem_label": "转速/主轴/润滑",
- "src": "scada_lang_2015",
- "brake_state_design": "10"
- },
- "04_04_023": {
- "en": "The test result of drive train frequency is warning",
- "cn": "传动链频率检测异常",
- "subsystem_label": "转速/主轴/润滑",
- "src": "scada_lang_2015",
- "brake_state_design": "40"
- },
- "04_04_024": {
- "en": "The STD of generator speed is too high",
- "cn": "高速端转速的STD异常停机",
- "subsystem_label": "转速/主轴/润滑",
- "src": "scada_lang_2015",
- "brake_state_design": "170"
- },
- "04_04_025": {
- "en": "The STD of rotor speed is too high",
- "cn": "低速端转速的STD异常停机",
- "subsystem_label": "转速/主轴/润滑",
- "src": "scada_lang_2015",
- "brake_state_design": "170"
- },
- "04_04_026": {
- "en": "Main bearing lubrication MCB trip.",
- "cn": "主轴承润滑MCB跳开",
- "subsystem_label": "转速/主轴/润滑",
- "src": "scada_lang_2015",
- "brake_state_design": "40"
- },
- "04_04_027": {
- "en": "Main bearing lubrication ON.",
- "cn": "主轴承润滑系统启动",
- "subsystem_label": "转速/主轴/润滑",
- "src": "scada_lang_2015",
- "brake_state_design": "10"
- },
- "04_04_028": {
- "en": "Main bearing lubrication heater MCB tripped.",
- "cn": "主轴承润滑系统加热器MCB跳开",
- "subsystem_label": "转速/主轴/润滑",
- "src": "scada_lang_2015",
- "brake_state_design": "40"
- },
- "04_04_029": {
- "en": "Main bearing lubrication heater ON.",
- "cn": "主轴承润滑系统加热器启动",
- "subsystem_label": "转速/主轴/润滑",
- "src": "scada_lang_2015",
- "brake_state_design": "10"
- },
- "04_04_030": {
- "en": "Main bearing Lubrication OFF lasts over one week.",
- "cn": "主轴承润滑系统未运行超过一星期",
- "subsystem_label": "转速/主轴/润滑",
- "src": "scada_lang_2015",
- "brake_state_design": "170"
- },
- "04_04_031": {
- "en": "",
- "cn": "主轴润滑泵开启手动模式",
- "subsystem_label": "转速/主轴/润滑",
- "src": "scada_lang_2015",
- "brake_state_design": "10"
- },
- "04_04_032": {
- "en": "",
- "cn": "主轴润滑泵开启强制模式",
- "subsystem_label": "转速/主轴/润滑",
- "src": "scada_lang_2015",
- "brake_state_design": "10"
- },
- "04_04_033": {
- "en": "",
- "cn": "主轴润滑泵加热器开启手动模式",
- "subsystem_label": "转速/主轴/润滑",
- "src": "scada_lang_2015",
- "brake_state_design": "10"
- },
- "04_04_034": {
- "en": "",
- "cn": "主轴润滑泵加热器开启强制模式",
- "subsystem_label": "转速/主轴/润滑",
- "src": "scada_lang_2015",
- "brake_state_design": "10"
- },
- "04_04_035": {
- "en": "",
- "cn": "低速端转速与发电机转速不匹配复位失败",
- "subsystem_label": "转速/主轴/润滑",
- "src": "scada_lang_2015",
- "brake_state_design": "170"
- },
- "04_04_036": {
- "en": "",
- "cn": "低速端转速与发电机转速不匹配重复出现",
- "subsystem_label": "转速/主轴/润滑",
- "src": "scada_lang_2015",
- "brake_state_design": "170"
- },
- "04_04_037": {
- "en": "",
- "cn": "主控系统测得的发电机转速与从变频器读得的不匹配复位失败",
- "subsystem_label": "转速/主轴/润滑",
- "src": "scada_lang_2015",
- "brake_state_design": "170"
- },
- "04_04_038": {
- "en": "",
- "cn": "主控系统测得的发电机转速与从变频器读得的不匹配重复出现",
- "subsystem_label": "转速/主轴/润滑",
- "src": "scada_lang_2015",
- "brake_state_design": "170"
- },
- "04_04_039": {
- "en": "Rotor Speed mismatch generator speed for previous 10 minutes mean vallue",
- "cn": "低速端转速与发电机转速十分钟平均值不匹配",
- "subsystem_label": "转速/主轴/润滑",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_04_040": {
- "en": "",
- "cn": "低速端转速高于1级超速门限值复位失败",
- "subsystem_label": "转速/主轴/润滑",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_04_041": {
- "en": "",
- "cn": "发电机转速高于1级超速门限值复位失败",
- "subsystem_label": "转速/主轴/润滑",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_05_048": {
- "en": "The gearbox support gets extreme load warning",
- "cn": "齿轮箱弹性支撑达到极限载荷报警",
- "subsystem_label": "齿轮箱/温度/传感器",
- "src": "scada_lang_2015",
- "brake_state_design": "40"
- },
- "04_05_049": {
- "en": "The gearbox support failure warning",
- "cn": "齿轮箱弹性支撑失效报警",
- "subsystem_label": "齿轮箱/温度/传感器",
- "src": "scada_lang_2015",
- "brake_state_design": "170"
- },
- "04_05_050": {
- "en": "",
- "cn": "齿轮箱左扭力臂位置传感器损坏",
- "subsystem_label": "齿轮箱/温度/传感器",
- "src": "scada_lang_2015",
- "brake_state_design": "40"
- },
- "04_05_051": {
- "en": "",
- "cn": "齿轮箱右扭力臂位置传感器损坏",
- "subsystem_label": "齿轮箱/温度/传感器",
- "src": "scada_lang_2015",
- "brake_state_design": "40"
- },
- "04_05_052": {
- "en": "Gear filter pump has clogged to stop",
- "cn": "齿轮箱油泵过滤器滤网堵塞停机故障",
- "subsystem_label": "齿轮箱/温度/传感器",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_08_092": {
- "en": "",
- "cn": "塔底水冷系统三通阀MCB跳开",
- "subsystem_label": "塔/水冷/冷却",
- "src": "scada_lang_2015",
- "brake_state_design": "170"
- },
- "04_08_093": {
- "en": "",
- "cn": "塔底水冷进水口水温过低故障",
- "subsystem_label": "塔/水冷/冷却",
- "src": "scada_lang_2015",
- "brake_state_design": "170"
- },
- "04_08_094": {
- "en": "",
- "cn": "塔底水冷三通阀实际位置与设置值不匹配",
- "subsystem_label": "塔/水冷/冷却",
- "src": "scada_lang_2015",
- "brake_state_design": "40"
- },
- "04_08_095": {
- "en": "",
- "cn": "塔底水冷塔内风扇1启动",
- "subsystem_label": "塔/水冷/冷却",
- "src": "scada_lang_2015",
- "brake_state_design": "10"
- },
- "04_08_096": {
- "en": "",
- "cn": "塔底水冷塔内风扇2启动",
- "subsystem_label": "塔/水冷/冷却",
- "src": "scada_lang_2015",
- "brake_state_design": "10"
- },
- "04_08_097": {
- "en": "",
- "cn": "塔底水冷塔外冷却器1风扇启动",
- "subsystem_label": "塔/水冷/冷却",
- "src": "scada_lang_2015",
- "brake_state_design": "10"
- },
- "04_08_098": {
- "en": "",
- "cn": "塔底水冷塔外冷却器2风扇启动",
- "subsystem_label": "塔/水冷/冷却",
- "src": "scada_lang_2015",
- "brake_state_design": "10"
- },
- "04_08_099": {
- "en": "",
- "cn": "塔底水冷塔外冷却器3风扇启动",
- "subsystem_label": "塔/水冷/冷却",
- "src": "scada_lang_2015",
- "brake_state_design": "10"
- },
- "04_08_100": {
- "en": "",
- "cn": "塔底水冷塔外冷却器4风扇启动",
- "subsystem_label": "塔/水冷/冷却",
- "src": "scada_lang_2015",
- "brake_state_design": "10"
- },
- "04_08_101": {
- "en": "Nacelle cooling system water leak risk.",
- "cn": "机舱冷却系统有漏液风险",
- "subsystem_label": "塔/水冷/冷却",
- "src": "scada_lang_2015",
- "brake_state_design": "40"
- },
- "04_08_102": {
- "en": "Tower cooling system water leak risk.",
- "cn": "塔底冷却系统有漏液风险",
- "subsystem_label": "塔/水冷/冷却",
- "src": "scada_lang_2015",
- "brake_state_design": "40"
- },
- "04_08_103": {
- "en": "",
- "cn": "机舱冷却系统泵1启动压差低报警",
- "subsystem_label": "塔/水冷/冷却",
- "src": "scada_lang_2015",
- "brake_state_design": "40"
- },
- "04_08_104": {
- "en": "",
- "cn": "机舱冷却系统泵2启动压差低报警",
- "subsystem_label": "塔/水冷/冷却",
- "src": "scada_lang_2015",
- "brake_state_design": "40"
- },
- "04_08_105": {
- "en": "",
- "cn": "塔底冷却系统泵出口压力过高警告",
- "subsystem_label": "塔/水冷/冷却",
- "src": "scada_lang_2015",
- "brake_state_design": "170"
- },
- "04_08_106": {
- "en": "",
- "cn": "塔底水冷进水口水温过低故障自复位失败",
- "subsystem_label": "塔/水冷/冷却",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_08_107": {
- "en": "",
- "cn": "塔底水冷进水口水温过低故障重复出现",
- "subsystem_label": "塔/水冷/冷却",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_08_108": {
- "en": "",
- "cn": "机舱水冷系统水冷泵站需启动但未启动",
- "subsystem_label": "塔/水冷/冷却",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_08_110": {
- "en": "Cooling system Cabinet Fault Temp Repeat error",
- "cn": "塔底水冷控制柜温度过高或过低警告重复出现",
- "subsystem_label": "塔/水冷/冷却",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_09_050": {
- "en": "The foraft nacelle vibration throuth band filter reaches the alarm level",
- "cn": "机舱前后振动带通滤波值报警",
- "subsystem_label": "机舱/振动/传感器",
- "src": "scada_lang_2015",
- "brake_state_design": "170"
- },
- "04_09_051": {
- "en": "The foraft nacelle vibration throuth band filter reaches the fault level",
- "cn": "机舱前后振动带通滤波值停机",
- "subsystem_label": "机舱/振动/传感器",
- "src": "scada_lang_2015",
- "brake_state_design": "170"
- },
- "04_09_052": {
- "en": "The foraft nacelle vibration throuth band filter reaches the alarm level repeatly",
- "cn": "机舱前后振动带通滤波值报警重复出现",
- "subsystem_label": "机舱/振动/传感器",
- "src": "scada_lang_2015",
- "brake_state_design": "170"
- },
- "04_09_053": {
- "en": "The sideside nacelle vibration throuth band filter reaches the alarm level",
- "cn": "机舱左右振动带通滤波值报警",
- "subsystem_label": "机舱/振动/传感器",
- "src": "scada_lang_2015",
- "brake_state_design": "170"
- },
- "04_09_054": {
- "en": "The sideside nacelle vibration throuth band filter reaches the fault level",
- "cn": "机舱左右振动带通滤波值停机",
- "subsystem_label": "机舱/振动/传感器",
- "src": "scada_lang_2015",
- "brake_state_design": "170"
- },
- "04_09_055": {
- "en": "The sideside nacelle vibration throuth band filter reaches the alarm level repeatly",
- "cn": "机舱左右振动带通滤波值报警重复出现",
- "subsystem_label": "机舱/振动/传感器",
- "src": "scada_lang_2015",
- "brake_state_design": "170"
- },
- "04_09_056": {
- "en": "",
- "cn": "叶片面内振动超限报警",
- "subsystem_label": "机舱/振动/传感器",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_09_057": {
- "en": "",
- "cn": "风轮不平衡报警",
- "subsystem_label": "机舱/振动/传感器",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_09_060": {
- "en": "",
- "cn": "切换至备用风速仪",
- "subsystem_label": "机舱/振动/传感器",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_09_061": {
- "en": "",
- "cn": "PCH的通讯状态为\"Node not found\"",
- "subsystem_label": "机舱/振动/传感器",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_09_062": {
- "en": "",
- "cn": "发送重启PCH信号",
- "subsystem_label": "机舱/振动/传感器",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_10_015": {
- "en": "",
- "cn": "偏航摩擦片润滑系统(2L)油脂底",
- "subsystem_label": "偏航/润滑/加热",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_10_016": {
- "en": "",
- "cn": "偏航摩擦片润滑系统(2L)堵塞",
- "subsystem_label": "偏航/润滑/加热",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_10_017": {
- "en": "Something wrong for yaw sensor",
- "cn": "偏航传感器故障",
- "subsystem_label": "偏航/润滑/加热",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_10_018": {
- "en": "Yaw speed is NOT in the given region",
- "cn": "偏航速度异常,不在有效区间内",
- "subsystem_label": "偏航/润滑/加热",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_10_019": {
- "en": "Self test for yaw speed calculation",
- "cn": "偏航速度计算自检",
- "subsystem_label": "偏航/润滑/加热",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_12_028": {
- "en": "Converter has EtherCAT communication fault",
- "cn": "变频器EtherCAT通讯故障",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": "170"
- },
- "04_12_029": {
- "en": "Converter has multi syn fault",
- "cn": "变频器双通道同步故障",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": "170"
- },
- "04_12_030": {
- "en": "Converter has fastlink fault",
- "cn": "变频器Fastlink故障",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": "170"
- },
- "04_12_031": {
- "en": "Converter has watchdog fault",
- "cn": "变频器Watchdog错误",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": "170"
- },
- "04_12_032": {
- "en": "Converter has fault loop fault",
- "cn": "变频器FaultLoop故障",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": "170"
- },
- "04_12_033": {
- "en": "Converter has I2T fault",
- "cn": "变频器I2TFault",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": "170"
- },
- "04_12_034": {
- "en": "Converter has sharing fault",
- "cn": "变频器sharing故障",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": "170"
- },
- "04_12_035": {
- "en": "Converter has DBU fault",
- "cn": "变频器DB故障",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": "170"
- },
- "04_12_036": {
- "en": "Converter has cooling system fault",
- "cn": "变频器水冷故障",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": "170"
- },
- "04_12_037": {
- "en": "Converter has smoke detect fault",
- "cn": "变频器烟感报警",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": "170"
- },
- "04_12_038": {
- "en": "Converter has main CB fault",
- "cn": "变频器主CB故障",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": "170"
- },
- "04_12_039": {
- "en": "Converter has machine side CB fault",
- "cn": "变频器机侧CB故障",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": "170"
- },
- "04_12_040": {
- "en": "Converter has PWM filter fault",
- "cn": "变频器主PWM滤波器故障",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": "170"
- },
- "04_12_041": {
- "en": "Converter has pre charge fault",
- "cn": "变频器预充电回路故障",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": "170"
- },
- "04_12_042": {
- "en": "Converter has grid DIBe1 fault",
- "cn": "变频器网侧DIBe1故障",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": "170"
- },
- "04_12_043": {
- "en": "Converter has grid DIBe2 fault",
- "cn": "变频器网侧DIBe2故障",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": "170"
- },
- "04_12_044": {
- "en": "Converter has grid DIBe3 fault",
- "cn": "变频器网侧DIBe3故障",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": "170"
- },
- "04_12_045": {
- "en": "Converter has grid DIBe4 fault",
- "cn": "变频器网侧DIBe4故障",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": "170"
- },
- "04_12_046": {
- "en": "Converter has generator DIBe1 fault",
- "cn": "变频器机侧DIBe1故障",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": "170"
- },
- "04_12_047": {
- "en": "Converter has generator DIBe2 fault",
- "cn": "变频器机侧DIBe2故障",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": "170"
- },
- "04_12_048": {
- "en": "Converter has generator DIBe3 fault",
- "cn": "变频器机侧DIBe3故障",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": "170"
- },
- "04_12_049": {
- "en": "Converter has generator DIBe4 fault",
- "cn": "变频器机侧DIBe4故障",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": "170"
- },
- "04_12_050": {
- "en": "Converter has DC Link fault",
- "cn": "变频器报直流母线故障",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": "170"
- },
- "04_12_051": {
- "en": "Converter has PIBe fault",
- "cn": "变频器PIBe故障",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": "170"
- },
- "04_12_052": {
- "en": "Converter has Surge fault",
- "cn": "变频器机侧防雷故障",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": "170"
- },
- "04_12_053": {
- "en": "Converter has gen voltage fault",
- "cn": "变频器报电机相关故障",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": "170"
- },
- "04_12_054": {
- "en": "Converter has grid voltage fault",
- "cn": "变频器报电网相关故障",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": "170"
- },
- "04_12_055": {
- "en": "Converter has encoder fault",
- "cn": "变频器报编码器故障",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": "170"
- },
- "04_12_056": {
- "en": "Converter has firmware fault",
- "cn": "变频器固件不匹配",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": "170"
- },
- "04_12_057": {
- "en": "Converter has overspeed fault",
- "cn": "变频器报过速故障",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": "170"
- },
- "04_12_058": {
- "en": "Converter has generator control fault",
- "cn": "变频器电机控制故障",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": "170"
- },
- "04_12_059": {
- "en": "Converter has emergency fault",
- "cn": "变频器报急停",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": "170"
- },
- "04_12_060": {
- "en": "Converter has MVM fuse fault",
- "cn": "变频器电压检测板故障",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": "170"
- },
- "04_12_061": {
- "en": "Converter has gen fuse fault",
- "cn": "变频器机侧熔丝故障",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": "170"
- },
- "04_12_062": {
- "en": "The master converter detect warning signal",
- "cn": "变频器报告警告",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": "165"
- },
- "04_12_063": {
- "en": "canopen timeout level1",
- "cn": "变频器CAN通讯闪断",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": "165"
- },
- "04_12_064": {
- "en": "canopen timeout level2",
- "cn": "变频器CAN通讯长断",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": "50"
- },
- "04_12_065": {
- "en": "canopen timeout level1 repeat fault",
- "cn": "变频器CAN通讯闪断重复触发",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": "175"
- },
- "04_12_066": {
- "en": "converter auto reset failed",
- "cn": "变频器CAN通讯自复位失败",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": "175"
- },
- "04_12_067": {
- "en": "canopen timeout level2 repeat fault",
- "cn": "变频器CAN通讯长断重复触发",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": "175"
- },
- "04_12_068": {
- "en": "Air condition power fault",
- "cn": "变频柜空调电源故障",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": "165"
- },
- "04_12_069": {
- "en": "dclink charge timeout repeat fault",
- "cn": "变频器直流母线充电超时重复触发",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": "175"
- },
- "04_12_070": {
- "en": "dclink charge timeout auto reset failed",
- "cn": "变频器直流母线充电超时自复位失败",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": "175"
- },
- "04_12_071": {
- "en": "master slave configure is not finished on time",
- "cn": "主从配置正在进行",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": "10"
- },
- "04_12_072": {
- "en": "GEPC converter reports warning",
- "cn": "GEPC变频器报告警告",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": "165"
- },
- "04_12_073": {
- "en": "The ABB converter detect warning signal",
- "cn": "变频器报告警告",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": "165"
- },
- "04_12_074": {
- "en": "The master converter detect cooling fault signal",
- "cn": "变频器报告冷却故障",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": "165"
- },
- "04_12_075": {
- "en": "Actual torque differs much from set torque",
- "cn": "扭矩设定值与真实值的偏差过大",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_12_076": {
- "en": "Converter SDO time out",
- "cn": "变频器SDO通讯超时",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_12_101": {
- "en": "ABB CVT GEN_IGBT_Fault",
- "cn": "ABB变频器机侧IGBT故障",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_12_102": {
- "en": "ABB CVT Gen_PU_Fault",
- "cn": "ABB变频器机侧模块故障",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_12_103": {
- "en": "ABB CVT Gen_Current_Fault",
- "cn": "ABB变频器机侧电流异常故障",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_12_104": {
- "en": "ABB CVT DC_Link_Fault",
- "cn": "ABB变频器直流母线故障",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_12_105": {
- "en": "ABB CVT Precharge_Fault",
- "cn": "ABB变频器充电回路故障",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_12_106": {
- "en": "ABB CVT Gen_Controller_Fault",
- "cn": "ABB变频器机侧控制器故障",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_12_107": {
- "en": "ABB CVT LSU_Fault",
- "cn": "ABB变频器LSU故障",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_12_108": {
- "en": "ABB CVT LSU_Fan_Fault",
- "cn": "ABB变频器LSU风扇故障",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_12_109": {
- "en": "ABB CVT Cooling_System_Fault",
- "cn": "ABB变频器冷却系统故障",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_12_110": {
- "en": "ABB CVT Cooling_Fan_Fault",
- "cn": "ABB变频器风扇故障",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_12_111": {
- "en": "ABB CVT Gen_PU_Fan_Fault",
- "cn": "ABB变频器机侧模块风扇故障",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_12_112": {
- "en": "ABB CVT Gen_PU_Comm_Fault",
- "cn": "ABB变频器机侧模块通讯故障",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_12_113": {
- "en": "ABB CVT Gen_EFB_Comm_Fault",
- "cn": "ABB变频器机侧EFB故障",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_12_114": {
- "en": "ABB CVT Gen_Comm_Fault",
- "cn": "ABB变频器机侧通讯故障",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_12_115": {
- "en": "ABB CVT Motor_Fault",
- "cn": "ABB变频器电机侧故障",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_12_116": {
- "en": "ABB CVT Temperature_Fault",
- "cn": "ABB变频器变频器温度故障",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_12_117": {
- "en": "ABB CVT STO_Fault",
- "cn": "ABB变频器STO故障",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_12_118": {
- "en": "ABB CVT Measure_Unit_Fault",
- "cn": "ABB变频器测量监控信号故障",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_12_119": {
- "en": "ABB CVT DB_Fault",
- "cn": "ABB变频器动态刹车故障",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_12_120": {
- "en": "ABB CVT MB_Fault",
- "cn": "ABB变频器机械刹车故障",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_12_121": {
- "en": "ABB CVT Emergency_Fault",
- "cn": "ABB变频器急停信号异常故障",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_12_122": {
- "en": "ABB CVT Speed_Fault",
- "cn": "ABB变频器转速信号故障",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_12_123": {
- "en": "ABB CVT FSO_Fault",
- "cn": "ABB变频器FSO故障",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_12_124": {
- "en": "ABB CVT Gen_Cable_Fault",
- "cn": "ABB变频器机侧电缆异常故障",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_12_125": {
- "en": "ABB CVT Reserve_Fault",
- "cn": "ABB变频器其他故障",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_12_126": {
- "en": "ABB CVT Gen_Ext_Fault",
- "cn": "ABB变频器机侧外部故障",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_12_127": {
- "en": "ABB CVT Grid_IGBT_Fault",
- "cn": "ABB变频器网侧IGBT故障",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_12_128": {
- "en": "ABB CVT Grid_PU_Fault",
- "cn": "ABB变频器网侧模块故障",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_12_129": {
- "en": "ABB CVT Grid_Current_Fault",
- "cn": "ABB变频器网侧电流故障",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_12_130": {
- "en": "ABB CVT Grid_Fault",
- "cn": "ABB变频器电网故障",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_12_131": {
- "en": "ABB CVT Grid_Controller_Fault",
- "cn": "ABB变频器网侧控制器故障",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_12_132": {
- "en": "ABB CVT Grid_PU_Comm_Fault",
- "cn": "ABB变频器网侧模块通讯故障",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_12_133": {
- "en": "ABB CVT Grid_EFB_Comm_Fault",
- "cn": "ABB变频器EFB通讯故障",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_12_134": {
- "en": "ABB CVT Grid_Comm_Fault",
- "cn": "ABB变频器网侧通讯故障",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_12_135": {
- "en": "ABB CVT Grid_Ext_Fault",
- "cn": "ABB变频器网侧外部故障",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_12_136": {
- "en": "ABB CVT Grid_Cable_Fault",
- "cn": "ABB变频器网侧电缆异常故障",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_12_137": {
- "en": "ABB CVT CB_Fault",
- "cn": "ABB变频器断路器故障",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_12_138": {
- "en": "ABB CVT Liquid_Cooling_Fault",
- "cn": "ABB变频器水冷系统故障",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_12_139": {
- "en": "ABB CVT Faults",
- "cn": "ABB变频器故障停机",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_12_140": {
- "en": "ABB CVT Other Faults",
- "cn": "ABB变频器未拆分故障",
- "subsystem_label": "变频/通讯/柜",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_13_010": {
- "en": "",
- "cn": "塔底控制柜左侧温度传感器故障",
- "subsystem_label": "柜/塔/机舱",
- "src": "scada_lang_2015",
- "brake_state_design": "40"
- },
- "04_13_011": {
- "en": "",
- "cn": "塔底控制柜右侧温度传感器故障",
- "subsystem_label": "柜/塔/机舱",
- "src": "scada_lang_2015",
- "brake_state_design": "40"
- },
- "04_13_012": {
- "en": "690V SPD in tower base panel trip",
- "cn": "塔底690V防雷器触发",
- "subsystem_label": "柜/塔/机舱",
- "src": "scada_lang_2015",
- "brake_state_design": "40"
- },
- "04_13_013": {
- "en": "400V SPD in tower base panel trip",
- "cn": "塔底400V防雷器触发",
- "subsystem_label": "柜/塔/机舱",
- "src": "scada_lang_2015",
- "brake_state_design": "40"
- },
- "04_13_014": {
- "en": "230V SPD in tower base panel trip",
- "cn": "塔底230V防雷器触发",
- "subsystem_label": "柜/塔/机舱",
- "src": "scada_lang_2015",
- "brake_state_design": "40"
- },
- "04_13_015": {
- "en": "690V SPD in nacelle panel trip",
- "cn": "机舱690V防雷器触发",
- "subsystem_label": "柜/塔/机舱",
- "src": "scada_lang_2015",
- "brake_state_design": "40"
- },
- "04_13_016": {
- "en": "400V SPD in nacelle panel trip",
- "cn": "机舱400V防雷器触发",
- "subsystem_label": "柜/塔/机舱",
- "src": "scada_lang_2015",
- "brake_state_design": "40"
- },
- "04_13_017": {
- "en": "230V SPD in nacelle panel trip",
- "cn": "机舱230V防雷器触发",
- "subsystem_label": "柜/塔/机舱",
- "src": "scada_lang_2015",
- "brake_state_design": "40"
- },
- "04_13_018": {
- "en": "Towerbase Cabinet 24V Redundancy Power Fail.",
- "cn": "塔底柜24V电源冗余失效",
- "subsystem_label": "柜/塔/机舱",
- "src": "scada_lang_2015",
- "brake_state_design": "40"
- },
- "04_13_019": {
- "en": "Nacelle Cabinet 24V Redundancy Power Fail.",
- "cn": "机舱柜24V电源冗余失效",
- "subsystem_label": "柜/塔/机舱",
- "src": "scada_lang_2015",
- "brake_state_design": "40"
- },
- "04_13_020": {
- "en": "",
- "cn": "塔底柜左侧加热器与通风风扇230V供电开关断开",
- "subsystem_label": "柜/塔/机舱",
- "src": "scada_lang_2015",
- "brake_state_design": "165"
- },
- "04_13_021": {
- "en": "",
- "cn": "塔底柜右侧加热器与冷却风扇230V供电开关断开",
- "subsystem_label": "柜/塔/机舱",
- "src": "scada_lang_2015",
- "brake_state_design": "165"
- },
- "04_13_022": {
- "en": "",
- "cn": "机舱柜通风风扇230V供电开关断开",
- "subsystem_label": "柜/塔/机舱",
- "src": "scada_lang_2015",
- "brake_state_design": "165"
- },
- "04_13_023": {
- "en": "",
- "cn": "机舱柜加热器230V供电开关断开",
- "subsystem_label": "柜/塔/机舱",
- "src": "scada_lang_2015",
- "brake_state_design": "165"
- },
- "04_13_024": {
- "en": "",
- "cn": "风机尚有问题禁止离开",
- "subsystem_label": "柜/塔/机舱",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_15_020": {
- "en": "IPC 45 degree sensor fault",
- "cn": "IPC45度传感器故障",
- "subsystem_label": "桨叶/振动/传感器",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_15_021": {
- "en": "IPC 135 degree sensor fault",
- "cn": "IPC135度传感器故障",
- "subsystem_label": "桨叶/振动/传感器",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_15_022": {
- "en": "IPC 225 degree sensor fault",
- "cn": "IPC225度传感器故障",
- "subsystem_label": "桨叶/振动/传感器",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_15_023": {
- "en": "IPC 315 degree sensor fault",
- "cn": "IPC315度传感器故障",
- "subsystem_label": "桨叶/振动/传感器",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_16_016": {
- "en": "Start Mode Timeout Repeat",
- "cn": "启动模式运行超时重复",
- "subsystem_label": "机舱/塔",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_21_038": {
- "en": "Restore Statistics From File Failed Warning",
- "cn": "读取统计量参数文件失败警告",
- "subsystem_label": "通讯/机舱/塔",
- "src": "scada_lang_2015",
- "brake_state_design": "40"
- },
- "04_21_039": {
- "en": "Restore Unique Parameter From File Failed Warning",
- "cn": "读取个性化参数文件失败警告",
- "subsystem_label": "通讯/机舱/塔",
- "src": "scada_lang_2015",
- "brake_state_design": "40"
- },
- "04_21_040": {
- "en": "Restore Golden Parameter From File Failed Warning",
- "cn": "读取通用性参数文件失败警告",
- "subsystem_label": "通讯/机舱/塔",
- "src": "scada_lang_2015",
- "brake_state_design": "40"
- },
- "04_21_041": {
- "en": "Restore Storage Variables From File Failed Warning",
- "cn": "读取掉电保存变量文件失败警告",
- "subsystem_label": "通讯/机舱/塔",
- "src": "scada_lang_2015",
- "brake_state_design": "40"
- },
- "04_21_042": {
- "en": "Store Statistics To File Failed Warning",
- "cn": "存储统计量参数文件失败警告",
- "subsystem_label": "通讯/机舱/塔",
- "src": "scada_lang_2015",
- "brake_state_design": "40"
- },
- "04_21_043": {
- "en": "Store Unique Parameter To File Failed Warning",
- "cn": "存储个性化参数文件失败警告",
- "subsystem_label": "通讯/机舱/塔",
- "src": "scada_lang_2015",
- "brake_state_design": "40"
- },
- "04_21_044": {
- "en": "Store Golden Parameter To File Failed Warning",
- "cn": "存储通用性参数文件失败警告",
- "subsystem_label": "通讯/机舱/塔",
- "src": "scada_lang_2015",
- "brake_state_design": "40"
- },
- "04_21_045": {
- "en": "Store Storage Variables To File Failed Warning",
- "cn": "存储掉电保存变量文件失败警告",
- "subsystem_label": "通讯/机舱/塔",
- "src": "scada_lang_2015",
- "brake_state_design": "40"
- },
- "04_21_046": {
- "en": "Store Storage Variables To File Failed Error",
- "cn": "存储掉电保存变量文件失败故障",
- "subsystem_label": "通讯/机舱/塔",
- "src": "scada_lang_2015",
- "brake_state_design": "165"
- },
- "04_21_047": {
- "en": "Store Statistics To File Failed Error",
- "cn": "存储统计量参数文件失败故障",
- "subsystem_label": "通讯/机舱/塔",
- "src": "scada_lang_2015",
- "brake_state_design": "165"
- },
- "04_21_048": {
- "en": "Store Unique To File Failed Error",
- "cn": "存储个性化参数文件失败故障",
- "subsystem_label": "通讯/机舱/塔",
- "src": "scada_lang_2015",
- "brake_state_design": "165"
- },
- "04_21_049": {
- "en": "Store Golden To File Failed Error",
- "cn": "存储通用性参数文件失败故障",
- "subsystem_label": "通讯/机舱/塔",
- "src": "scada_lang_2015",
- "brake_state_design": "165"
- },
- "04_21_050": {
- "en": "Restore Storage Variables To File Failed Error",
- "cn": "读取掉电保存变量文件失败故障",
- "subsystem_label": "通讯/机舱/塔",
- "src": "scada_lang_2015",
- "brake_state_design": "170"
- },
- "04_21_051": {
- "en": "Restore Statistics To File Failed Error",
- "cn": "读取统计量参数文件失败故障",
- "subsystem_label": "通讯/机舱/塔",
- "src": "scada_lang_2015",
- "brake_state_design": "165"
- },
- "04_21_052": {
- "en": "Restore Unique To File Failed Error",
- "cn": "读取个性化参数文件失败故障",
- "subsystem_label": "通讯/机舱/塔",
- "src": "scada_lang_2015",
- "brake_state_design": "170"
- },
- "04_21_053": {
- "en": "Restore Golden To File Failed Error",
- "cn": "读取存储通用性参数文件失败故障",
- "subsystem_label": "通讯/机舱/塔",
- "src": "scada_lang_2015",
- "brake_state_design": "170"
- },
- "04_21_054": {
- "en": "Ethercat Error Auto Recovery",
- "cn": "Ethercat通讯故障自恢复",
- "subsystem_label": "通讯/机舱/塔",
- "src": "scada_lang_2015",
- "brake_state_design": "230"
- },
- "04_21_055": {
- "en": "Ethercat Error Auto Reset Failed",
- "cn": "Ethercat故障自恢复失败",
- "subsystem_label": "通讯/机舱/塔",
- "src": "scada_lang_2015",
- "brake_state_design": "175"
- },
- "04_21_056": {
- "en": "Ethercat Repeat Error",
- "cn": "Ethercat故障重复出现",
- "subsystem_label": "通讯/机舱/塔",
- "src": "scada_lang_2015",
- "brake_state_design": "175"
- },
- "04_21_057": {
- "en": "Backup EtherCAT Wire Link Error",
- "cn": "EtherCAT冗余网线连接故障",
- "subsystem_label": "通讯/机舱/塔",
- "src": "scada_lang_2015",
- "brake_state_design": "165"
- },
- "04_21_058": {
- "en": "Master Or Slave Devices Lost",
- "cn": "EtherCat模块通讯断开",
- "subsystem_label": "通讯/机舱/塔",
- "src": "scada_lang_2015",
- "brake_state_design": "175"
- },
- "04_21_059": {
- "en": "EtherCAT Built up Failed Error",
- "cn": "EtherCAT通讯建立失败",
- "subsystem_label": "通讯/机舱/塔",
- "src": "scada_lang_2015",
- "brake_state_design": "175"
- },
- "04_21_060": {
- "en": "EtherCAT Communication ReBuilt",
- "cn": "EtherCAT通讯环网重组",
- "subsystem_label": "通讯/机舱/塔",
- "src": "scada_lang_2015",
- "brake_state_design": "10"
- },
- "04_21_061": {
- "en": "EtherCAT Communication ReBuilt Repeat",
- "cn": "EtherCAT通讯环网重组警告",
- "subsystem_label": "通讯/机舱/塔",
- "src": "scada_lang_2015",
- "brake_state_design": "165"
- },
- "04_29_001": {
- "en": "Gearbox Metal Scan Not Available.",
- "cn": "齿轮箱颗粒检测装置异常",
- "subsystem_label": "齿轮箱/发电机/主轴",
- "src": "scada_lang_2015",
- "brake_state_design": "40"
- },
- "04_29_002": {
- "en": "Gearbox Oil Particle value too large warning.",
- "cn": "齿轮箱颗粒检测数量异常警告",
- "subsystem_label": "齿轮箱/发电机/主轴",
- "src": "scada_lang_2015",
- "brake_state_design": "40"
- },
- "04_29_003": {
- "en": "Gearbox Oil Particle value too large Alarm.",
- "cn": "齿轮箱颗粒检测数量异常故障",
- "subsystem_label": "齿轮箱/发电机/主轴",
- "src": "scada_lang_2015",
- "brake_state_design": "170"
- },
- "04_29_004": {
- "en": "ACOEM CMS Communication error",
- "cn": "Acoem CMS通讯故障",
- "subsystem_label": "齿轮箱/发电机/主轴",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_29_005": {
- "en": "CMS reach danger value in a row",
- "cn": "Acoem CMS多次触发危险值",
- "subsystem_label": "齿轮箱/发电机/主轴",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_29_006": {
- "en": "Front main bearing reach alarm value",
- "cn": "前主轴承报警值超限",
- "subsystem_label": "齿轮箱/发电机/主轴",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_29_007": {
- "en": "Rear main bearing reach alarm value",
- "cn": "后主轴承报警值超限",
- "subsystem_label": "齿轮箱/发电机/主轴",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_29_008": {
- "en": "Gearbox reach alarm value",
- "cn": "齿轮箱报警值超限",
- "subsystem_label": "齿轮箱/发电机/主轴",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_29_009": {
- "en": "Generator NDE reach alarm value",
- "cn": "发电机驱动端报警值超限",
- "subsystem_label": "齿轮箱/发电机/主轴",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "04_29_010": {
- "en": "Generator DE reach alarm value",
- "cn": "发电机非驱动端报警值超限",
- "subsystem_label": "齿轮箱/发电机/主轴",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- },
- "sc04_04_044": {
- "en": "Main bearing lub heater not work for over 1 week",
- "cn": "主轴承润滑系统加热器未运行一周",
- "subsystem_label": "",
- "src": "scada_lang_2015",
- "brake_state_design": ""
- }
- }
- }
|